[an error occurred while processing this directive]
United States Nuclear Regulatory Commission - Protecting People and the Environment

Request for Action Related to Resolution of Unresolved Safety Issue A-47 "Safety Implication of Control Systems in LWR Nuclear Power Plants" Pursuant to 10 CFR 50.54(f) (Generic Letter 89-19)



September 20, 1989


TO:         ALL LICENSEES OF OPERATING REACTORS, APPLICANTS FOR OPERATING 
            LICENSES AND HOLDERS OF CONSTRUCTION PERMITS FOR LIGHT WATER 
            REACTOR NUCLEAR POWER PLANTS   

SUBJECT:    REQUEST FOR ACTION RELATED TO RESOLUTION OF UNRESOLVED SAFETY 
            ISSUE A-47 "SAFETY IMPLICATION OF CONTROL SYSTEMS IN LWR 
            NUCLEAR POWER PLANTS" PURSUANT TO 10 CFR 50.54(f) - GENERIC 
            LETTER 89-19

As a result of the technical resolution of USI A-47, "Safety Implications of 
Control Systems in LWR Nuclear Power Plants," the NRC has concluded that 
protection should be provided for certain control system failures and that 
selected emergency procedures should be modified to assure that plant 
transients resulting from control system failures do not compromise public 
safety.  

The NRC has provided to all utility and reactor vendor executives copies of 
NUREG-1217, "Evaluation of Safety Implications of Control Systems in LWR 
Nuclear Power Plants" and NUREG-1218, Regulatory Analysis for Resolution of 
USI A-47."  These reports are identified as items 1 and 2 in Enclosure 1.  
These reports summarize the results of the analyses conducted for USI A-47.  
During the A-47 review a number of different designs for reactor vessel and 
steam generator overfill protection were evaluated.  Plant specific features 
such as:  power supply interdependence, sharing of sensors between control and
trip logic, operator training, and designs for indication and alarms available
to the operator were considered in developing risk estimates associated with 
failures of the feedwater trip system.  The results of NRC's studies of the 
A-47 issue including the analysis for other events evaluated, such as overheat
and overcool events, are provided for information.  It is expected that each 
licensee and applicant will review the information for applicability to its 
facility.  The results of the analyses and the technical bases for the NRC 
conclusions are documented in the references listed in Enclosure 1.  

The staff has concluded that all PWR plants should provide automatic steam 
generator overfill protection, all BWR plants should provide automatic reactor
vessel overfill protection, and that plant procedures and technical specifica-
tions for all plants should include provisions to verify periodically the 
operability of the overfill protection and to assure that automatic overfill 
protection is available to mitigate main feedwater overfeed events during 
reactor power operation.  Also, the system design and setpoints should be 
selected with the objective of minimizing inadvertant trips of the main feed-
water system during plant startup, normal operation, and protection system 
surveillance.  The Technical Specifications recommendations are consistent 
with the criteria and the risk considerations of the Commission Interim Policy
Statement on Technical Specification Improvement.  In addition, the staff 
recommends that all BWR recipients reassess and modify, if needed, their 
operating procedures and operator training to assure that the operators can 
mitigate reactor vessel overfill events that may occur via the condensate 



890920223 
.

Generic Letter 89-19                    2              September 20, 1989


booster pumps during reduced system pressure operation.  Enclosure 2 (Sections
1 through 4, a and b) describes the requested action for the different NSSS 
designs. 

Enclosure 2 outlines a number of designs that satisfy the objectives for 
overfill protection and provides guidance for an acceptable design.  The staff
believes that a significant number of plants already provide satisfactory 
designs for overfill protection; many plants also have technical 
specifications dealing with overfill protection system surveillance which were
previously approved by the staff.  

The staff also concluded that certain Babcock and Wilcox plants should provide
either automatic initiation of auxiliary feedwater on low steam generator 
level or another acceptable design to prevent steam generator dryout on a loss
of power to the control system.  Most B&W plants have already incorporated 
automatic initiation circuits for this purpose.  Enclosure 2, Section 3c, 
identifies the plants that have not, and describes the requested action.  

The staff also concluded that certain Combustion Engineering plants should 
reassess their emergency procedures and operator training to assure safe shut-
down of the plants during any postulated small break loss of coolant accident. 
Enclosure 2, Section 4c, identifies these plants and describes the requested 
action.  

On the basis of the technical studies the staff requests that the recommen-
dations in Enclosure 2 be implemented by all LWR plants to enhance safety.  
These recommendations result from the staff interpretation of General Design 
Criteria 13, 20, and 33, identified in 10CFR50, Appendix A. 

The implementation schedule for actions on which commitments are made by 
licensees or applicants in response to this letter should be prior to start-up
after the first refueling outage, beginning nine (9) months following receipt 
of the letter.  

In order to determine whether any license or construction permit for 
facilities covered by this request should be modified, suspended or revoked, 
we require, pursuant to Section 182 of the Atomic Energy Act and 10 CFR 
50.54(f), that you provide the NRC, within 180 days of the date of this 
letter, a statement as to whether you will implement the recommendations in 
Enclosure 2 and, if so, that you provide a schedule for implementation of the 
items in Enclosure 2 and the basis for the schedule.  If you do not plan to 
implement these recommendations, provide appropriate justification.  This 
information shall be submitted to the NRC, signed under oath and affirmation. 

The licensee should retain, supporting documentation consistent with the 
records retention program for their facility.  

With regard to the recommendations in Enclosure 2 that specify modification to
plant procedures and Technical Specifications, the intent is that the 
appropriate plant procedures be modified in the short-term to provide periodic
verification and testing of the overfill protection system.  As part of future
upgrades to Technical Specifications, licensees should consider including 
appropriate limiting conditions of operation and surveillance requirements in 
future Technical Specification improvements.  

.

Generic Letter 89-19                    3              September 20, 1989


This request is covered by Office of Management andudget Clearance Number 
3150-0011 which expires December 31, 1989.  The estimated average burden hours
is 240 person hours per licensee response, including assessment of the new 
recommendations, searching data sources, gathering and analyzing the data, and
the required reports.  These estimated average burden hours pertain only to 
these identified response-related matters and do not include the time for 
actual implementation of the requested actions.  Send comments regarding this 
burden estimate or any other aspect of this collection of information, 
including suggestions for reducing this burden, to the Record and Reports 
Management Branch, Division of Information Support Services, Office of 
Information Resources Management, U.S. Nuclear Regulatory Commission, 
Washington, D.C. 20555; and to the Paperwork Reduction Project (3150-0011), 
Office of Manage-ment and Budget, Washington, D.C. 20503. 

If you have any questions on this matter, please contact your project manager.


                                   Sincerely, 

                                   James G. Partlow 
                                   Associate Director for Projects 
                                   Office of Nuclear Reactor Regulation

Enclosures: 
1.  Enclosure 1, List of References
2.  Enclosure 2, Control System Design and Procedural Modification for
    Resolution of USI A-47
3.  Enclosure 3, List of Recently Issued NRC Generic Letters
.

                                                                   Enclosure 1


                                  REFERENCE

                              LIST OF SIGNIFICANT
                             INFORMATION RELATED TO
                             RESOLUTION OF USI A-47



 1.  NUREG-1217     "Evaluation of Safety Implications of Control 
                    Systems in LWR Nuclear Power Plants" - Technical 
                    Findings Related to USI A-47.

 2.  NUREG-1218     "Regulatory Analysis for Resolution 
                    of USI A-47."

 3.  NUREG/CR-4285  "Effects of Control System Failures on 
                    Transients, Accidents and Core-Melt Frequencies 
                    at a Westinghouse PWR."  

 4.  NUREG/CR-4386  "Effects of Control System Failures on 
                    Transients, Accidents and Core-Melt Frequencies 
                    at a Babcock and Wilcox Pressurized Water 
                    Reactor." 

 5.  NUREG/CR-4387  "Effects of Control System Failures on 
                    Transients, Accidents and Core-Melt Frequencies at a 
                    General Electric Boiling Water Reactor." 

 6.  NUREG/CR-3958  "Effects of Control System Failures on 
                    Transients, Accidents and Core-Melt Frequencies 
                    at a Combustion Engineering Pressurized Water 
                    Reactor." 

 7.  NUREG/CR-4326  "Effects of Control System Failures on Transients and
                    Accidents at a 3 Loop Westinghouse.  Pressurized 
                    Water Reactor."  Vol. 1 and 2.

 8.  NUREG/CR-4047  "An Assessment of the Safety Implications of Control 
                    at the Oconee 1 Nuclear Plant-Final Report."

 9.  NUREG/CR-4262  "Effects of Control System Failures on Transients and 
                    Accidents At A General Electric Boiling Water 
                    Reactor."   Vol. 1 and 2.

10.  NUREG/CR-4265  "An Assessment of the Safety Implications of Control 
                    at the Calvert Cliffs - 1 Nuclear Plant" Vol. 1 and 
                    2.

11.  Letter Report  "Generic Extensions to Plant Specific Findings of the 
                    ORNL/NRC/ Safety Implications of Control Systems 
                    Program."  LTR-86/19
.

                                                                 Enclosure 2




                CONTROL SYSTEM DESIGN AND PROCEDURAL MODIFICATION
                           FOR RESOLUTION OF USI A-47


As part of the resolution of USI A-47, "Safety Implications of Control 
Systems," the staff investigated control system failures that have occurred, 
or are postulated to occur, in nuclear power plants.  The staff concluded that
plant transients resulting from control system failures can be mitigated by 
the operator, provided that the control system failures do not also compromise
operation of the minimum number of protection system channels required to trip
the reactor and initiate safety systems.  A number of plant-specific designs 
have been identified, however, that should provide additional protection from 
transients leading to reactor vessel or steam generator overfill or reactor 
core overheating. 

Reactor vessel or steam generator overfill can affect the safety of the plant 
in several ways.  The more severe scenarios could potentially lead to a steam-
line break and a steam generator tube rupture.  The basis for this concern is 
the following:  (1) the increased dead weight and potential seismic loads 
placed on the main steamline and its supports should the main steamline be 
flooded; (2) the loads placed on the main steamlines as a result of the 
potential for rapid collapse of steam voids resulting in water hammer; (3) the
potential for secondary safety valves sticking open following discharge of 
water or two-phase flow; (4) the potential inoperability of the main steamline
isolation valves (MSIVs), main turbine stop or bypass valves, feedwater 
turbine valves, or at-mospheric dump valves from the effects of water or 
two-phase flow; and (5) the potential for rupture of weakened tubes in the 
once-through steam generator on B&W nuclear steam supply system (NSSS) plants 
due to tensile loads caused by the rapid thermal shrinkage of the tubes 
relative to the generator shell.  These concerns have not been addressed in a 
number of plant designs, because overfill transients normally have not been 
analyzed. 

To minimize some of the consequences of overfill, early plant designs provided
commercial-grade protection for tripping the turbine or relied on operator 
action to control water level manually in the event the normal-water-level 
control system failed.  Later designs, including the most recent designs, 
provide overfill protection which automatically stops main feedwater flow on 
vessel high-water-level signals.  These designs provide various degrees of 
coincident logic and redundancy to initiate feedwater isolation and to ensure 
that a single failure would not inhibit isolation.  A large number of plants 
provide safety-grade designs for this protection. 

On the basis of the technical studies conducted by the staff and its 
contractors, the staff recommends that certain actions should be taken by some
plants to enhance plant safety.  These actions are described in the material 
that follows, and include design and procedural modifications to ensure that 
(1) all plants provide overfill protection, (2) all plants provide plant 
procedures and 
.

                                     - 2 -


technical specifications for periodic surveillance of the overfill protection,
(3) certain Babcock and Wilcox plants provide an acceptable design to prevent 
steam generator dryout on a loss of power to the control system, and (4) 
certain Combustion Engineering plants reassess their emergency procedures and 
operator training to ensure safe shutdown during any postulated small break 
loss of coolant accident.  With regard to the recommendations that specify 
modification to plant procedures and Technical Specifications, the intent is 
that the appropriate plant procedures be modified in the short-term to provide
periodic verification and testing of the overfill protection system.  As part 
of future upgrades to Technical Specifications, licensees should consider 
including appropriate limiting conditions of operation and surveillance 
requirements in future Technical Specification improvements.  

(1) GE Boiling-Water-Reactor Plants 

(a)  It is recommended that all GE boiling-water-reactor (BWR) plant designs 
     provide automatic reactor vessel overfill protection to mitigate main 
     feedwater (MFW) overfeed events.  The design for the overfill-protection 
     system should be sufficiently separate from the MFW control system to 
     ensure that the MFW pump will trip on a reactor high-water-level signal 
     when required, even if a loss of power, a loss of ventilation, or a fire 
     in the control portion of the MFW control system should occur.  Common-
     mode failures that could disable overfill protection and the feedwater 
     control system, but would still result in a feedwater pump trip, are 
     considered acceptable failure modes.  

     It is recommended that plant designs with no automatic reactor vessel 
     overfill protection be upgraded by providing a commercial-grade (or 
     better) MFW isolation system actuated from at least a 1-out-of-1 reactor 
     vessel high-water-level system, or justify the design on some defined 
     basis.

     In addition, it is recommended that all plants reassess their operating 
     procedures and operator training and modify them if necessary to ensure 
     that the operators can mitigate reactor vessel overfill events that may 
     occur via the condensate booster pumps during reduced pressure operation 
     of the system. 
     
(b)  It is recommended that plant procedures and technical specifications for 
     all BWR plants with main feedwater overfill protection include provisions
     to verify periodically the operability of overfill protection and ensure 
     that automatic overfill protection to mitigate main feedwater overfeed 
     events is operable during power operation. The instrumentation should be 
     demonstrated to be operable by the performance of a channel check, 
     channel functional testing, and channel calibration, including setpoint 
     verification.  The technical specifications should include appropriate 
     limiting conditions for operation (LCOs).  These technical specifications
     should be commensurate with the requirements of existing plant technical 
     specifications for channels that initiate protective actions.  Previously
     approved technical specifications for surveillance intervals and limiting 
     conditions for operation (LCOs) for overfill protection are considered 
     acceptable. 
.
                                     - 3 -



Designs for Overfill Protection 

Several different designs for overfill protection have already been 
incorporated into a large number of operating plants.  The following 
discussion identifies the different groups of plant designs and provides 
guidance for acceptable designs. 

Group I:  Plants that have a safety-grade or a commercial-grade overfill 
protection system initiated on a reactor vessel high-water-level signal based 
on a 2-out-of-3 or a 1-out-of-2 taken twice (or equivalent) initiating logic. 

The system isolates MFW flow by tripping the feedwater pumps. 

The staff concludes that this design is acceptable, provided that (1) the 
overfill protection system is separate from the control portion of the MFW 
control system so that it is not powered from the same power source, not 
located in the same cabinet, and not routed so that a fire is likely to affect
both systems and (2) the plant procedures and technical specifications include
requirements to periodically verify operability of this system.  Licensees of 
plants that already have these design features that have been previously 
approved by the staff should state this in their response.  

Group II:  Plants that have safety-grade or commercial-grade 
overfill-protection systems initiated on a reactor vessel high-water-level 
signal based on a 1-out-of-1, 1-out-of-2, or a 2-out-of-2 initiating logic.  
The system isolates MFW flow by tripping the feedwater pumps.  

The staff concludes that these designs are acceptable provided conditions (1) 
and (2) stated for Group I are met.  Licensees of plants that already have 
these design features that have been previously approved by the staff should 
state this in their response.  Plant designs with a 1-out-of-1 or a 1-out-of-2
trip logic for overfill protection should provide bypass capabilities to 
prevent feedwater trips during channel functional testing when at power 
operation. 

Group III:  Plants without automatic overfill protection. 

It is recommended that the licensee have a design to prevent reactor vessel 
overfill and justify the adequacy of the design.  The justification should 
include verification that the overfill protection system is separated from the
feedwater control system so that it is not powered from the same power source,
not located in the same cabinet, and not routed so that a fire is likely to 
affect both systems.  Common-mode failures that could disable overfill pro-
tection and the feedwater control system, but would still result in a 
feedwater pump trip, are considered acceptable failure modes.  The staff 
review identified three plants; i.e., Big Rock, LaCrosse (permanently 
shutdown), and Oyster Creek; that fall into this group.  If any of these 
plants wish to justify not including overfill protection, part of the 
requested justification should demonstrate that the risk reduction in 
implementing an automatic overfill protection system is significantly less 
than the staff's generic estimates of risk reduction.  In determining the risk
reduction, specific factors such as low plant power and population density 
should be considered.  Other applicable factors that are plant unique should 
also be addressed. 

.
                                     - 4 -


(2)  Westinghouse-Designed PWR Plants 

(a)  It is recommended that all Westinghouse plant designs provide automatic 
     steam generator overfill protection to mitigate MFW overfeed events.  The
     design for the overfill protection system should be sufficiently separate
     from the MFW control system to ensure that the MFW pump will trip on a 
     reactor high-water-level signal when required, even if a loss of power, a
     loss of ventilation, or a fire in the control portion of the MFW control 
     system should occur.  Common-mode failures that could disable overfill 
     protection and the feedwater control system, but would still result in 
     the feedwater pump trip, are considered acceptable failure modes.

(b)  It is recommended that plant procedures and technical specifications for 
     all Westinghouse plants include provisions to periodically verify the 
     operability of the MFW overfill protection and ensure that the automatic 
     overfill protection is operable during reactor power operation.  The 
     instrumentation should be demonstrated to be operable by the performance 
     of a channel check, channel functional testing, and channel calibration, 
     including setpoint verification.  The technical specifications should 
     include appropriate LCOs.  These technical specifications should be 
     commensurate with existing plant technical specification requirements for
     channels that initiate protective actions.  Plants that have previously 
     approved technical specifications for surveillance intervals for overfill
     protection are considered acceptable.  
     
Designs for Overfill Protection 

Several different designs for overfill-protection are already provided in most
operating plants.  The following discussion identifies the different groups of
plant designs and provides guidance for acceptable designs. 

Group I:  Plants that have an overfill-protection system initiated on a steam 
generator high-water-level signal based on a 2-out-of-4 initiating logic which
is safety grade, or a 2-out-of-3 initiating logic which is safety grade but 
uses one out of the three channels for both control and protection.  The 
system isolates MFW by closing the MFW isolation valves and tripping the MFW 
pumps. 

The staff concludes that the design is acceptable, provided that (1) the 
overfill protection system is sufficiently separate from the control portion 
of the MFW control system so that it is not powered from the same power 
source, not located in the same cabinet, and not routed so that a fire is 
likely to affect both systems, and (2) the plant procedures and technical 
specifications include requirements to periodically verify operability of this
system.

Group II:  Plants with a safety-grade or a commercial-grade overfill 
protection system initiated on a steam generator high-water-level signal based
on either a 1-out-of-1, 1-out-of-2, or 2-out-of-2 initiating logic.  The 
system isolates MFW by closing the MFW control valves.  

.

                                     - 5 -



The staff finds that only one early plant (i.e., Haddam Neck) falls into this 
group; therefore, a risk assessment was not conducted.  Considering the 
successful operating history of the plant regarding overfill transients (i.e.,
no overfill events have been reported), this design may be found acceptable, 
provided that (1) justification for the adequacy of the design on a plant-
specific basis is included and (2) plant procedures and technical specifica-
tions are modified to include requirements to periodically verify operability 
of this system.  As part of the justification, it is requested that the 
licensee include verification that the overfill-protection system is separate 
from the feedwater-control system so that it is not powered from the same 
power source, not located in the same cabinet, and not routed so that a fire 
is likely to affect both systems.  Common-mode failures that could disable 
overfill protection and the feedwater-control system, but would still cause a 
feedwater pump trip, are considered acceptable failure modes. 

Group III:  Plants without automatic overfill protection. 

It is recommended that the licensee have a design to prevent steam generator 
overfill and justify the adequacy of the design.  The justification should 
include verification that the overfill-protection system is separated from the
feedwater-control system so that it is not powered from the same power source,
not located in the same cabinet, and not routed so that a fire is likely to 
affect both systems.  Common-mode failures that could disable overfill pro-
tection and the feedwater-control system, but would still result in a 
feedwater pump trip, are considered acceptable failure modes.  The staff's 
review identified two plants; i.e., Yankee Rowe and San Onofre 1; that fall 
into this category.  If either of these plants wish to justify not including 
overfill protection, part of the requested justification should demonstrate 
that the risk reduction in implementing an automatic overfill protection 
system is significantly less than the staff's generic estimates of risk 
reduction.  In determining the risk reduction, specific factors such as low 
plant power and population density should be considered.  Other applicable 
factors that are plant unique should also be addressed. 

(3)  Babcock and Wilcox-Designed PWR Plants* 

(a)  It is recommended that all Babcock and Wilcox plant designs have auto-
     matic steam generator overfill protection to mitigate MFW overfeed 
     events.  
           

* On December 26, 1985, an overcooling event occurred at Rancho Seco Nuclear 
Generating Station, Unit 1.  This event occurred as a result of loss of power 
to the integrated control system (ICS).  Subsequently, the B&W Owners Group 
initiated a study to reassess all B&W plant designs including, but not limited
to, the ICS and support systems such as power supplies and maintenance.  As 
part of the USI A-47 review, failure scenarios resulting from a loss of power 
to control systems were evaluated; and the results were factored into the A-47
requirements.  However, other recommended actions for design modifications, 
maintenance, and  any changes to operating procedures (if any) developed for 
the utilities by the B&W owners group is being resolved separately. 
.

                                     - 6 -



     The design for the overfill-protection system should be sufficiently 
     separate from the MFW control system to ensure that the MFW pump will 
     trip on a steam generator high-water-level signal (or other equivalent 
     signals) when required, even if a loss of power, a loss of ventilation, 
     or a fire in the control portion of the main feedwater control system 
     should occur.  Common failure modes that could disable overfill 
     protection and the feedwater-control system, but would still result in a 
     feedwater pump trip, are considered acceptable failure modes.

     It is recommended that plants that are similar to the reference plant 
     design (i.e., Oconee Units 1, 2, and 3) have a steam generator 
     high-water-level feedwater-isolation system that satisfies the 
     single-failure criterion.  An acceptable design would be to provide 
     automatic MFW isolation by either (1) providing an additional system that
     terminates MFW flow by closing an isolation valve in the line to each 
     steam generator (this system is to be independent from the existing 
     overfill protection which trips the main feedwater pumps on steam 
     generator high-water level); (2) modifying the existing 
     overfill-protection system to preclude undetected failures in the trip 
     system and facilitate online testing; or (3) upgrading the existing 
     overfill-protection system to a 2-out-of-4 (or equivalent) 
     high-water-level trip system that satisfies the single-failure criterion. 
   
(b)  It is recommended that plant procedures and technical specifications for 
     all B&W plants include provisions to periodically verify the operability 
     of overfill protection and ensure the automatic main feedwater overfill 
     protection is operable during reactor power operation.  The 
     instrumentation should be demonstrated to be operable by the performance 
     of a channel check, channel functional testing, and channel calibration, 
     including setpoint verification.  Technical specifications should include
     appropriate LCOs.  These technical specifications should be commensurate 
     with the requirements of existing technical specifications for channels 
     that initiated protective actions.  

(c)  It is recommended that plant designs with no automatic protection to 
     prevent steam generator dryout upgrade their design and the appropriate 
     technical specifications and provide an automatic protection system to 
     prevent steam generator dryout on loss of power to the control system.  
     Automatic initiation of auxiliary feedwater on steam generator low-water 
     level is considered an acceptable design.  Other corrective actions 
     identified in Section 4.3(4) of NUREG-1218 could also be taken to avoid a
     steam generator dryout scenario on loss of power to the control system.  
     The staff believes that only three B&W plants, i.e., Oconee 1, 2, and 3, 
     do not have automatic auxiliary feedwater initiation on steam generator 
     low water level).

Designs for Overfill Protection 

Several different designs for overfill protection are already provided on most
operating plants.  The following discussion identifies the different groups of
plant designs and provides guidelines for acceptable designs. 

.

                                     - 7 -


Group I:  Plants that provide a safety-grade overfill-protection system initi-
ated on a steam generator high-water-level signal based on either a 2-out-of-3
or a 2-out-of-4 (or equivalent) initiating logic.  The system isolates main 
feedwater (MFW) by (1) closing at least one MFW isolation valve in the MFW 
line to each steam generator and (2) tripping the MFW pumps. 

The staff concludes that this design is acceptable, provided that (1) the 
overfill protection system is sufficiently separated from the feedwater 
control system so that it is not powered from the same power source, not 
located in the same cabinet, and not routed so that a fire is likely to affect
both systems (common-mode failures that could disable overfill protection and 
the feedwater control system, but still result in a feedwater pump trip are 
considered acceptable failure modes) and (2) the plant procedures and 
technical specifications include requirements to periodically verify
operability of this system. 

Group II:  Plants that have a commercial-grade overfill-protection system ini-
tiated on a steam generator high-water level based on coincident logic that 
minimizes inadvertent initiation.  The system isolates MFW by tripping the MFW
pumps. 

This design may be found acceptable, provided that (1) the overfill-protection
system is sufficiently separate from the feedwater control system so that it 
is not powered from the same power source, not located in the same cabinet, 
and not routed so that a fire is likely to affect both systems and (2) the 
design modifications are implemented per the guidelines identified in the 
second paragraph of item (3)(a) above and that the plant procedures and 
technical specifications include requirements to periodically verify 
operability of this system.  The technical specifications should be 
commensurate with existing plant technical specification requirements for 
channels that initiate protection actions. 

It is also recommended that plant designs that provide a separate 1-out-of-1 
or a 1-out-of-2 trip logic to close the feedwater isolation valves for 
additional overfill protection provide bypass capabilities to prevent 
feedwater trips during channel functional testing when at power or during 
hot-standby operation.  

(4)  Combustion Engineering-Designed PWR Plants 

(a)  It is recommended that all Combustion Engineering plants provide 
     automatic, steam generator overfill protection to mitigate main feedwater
     (MFW) over-feed events.  The design for the overfill-protection system 
     should be sufficiently separate from the MFW control system to ensure 
     that the MFW pump will trip on a steam generator high-water-level signal 
     when required, even if a loss of power, a loss of ventilation, or a fire 
     in the control portion of the MFW control system should occur.  Common 
     failure modes that could disable overfill protection and the feedwater 
     control system, but would still result in a feedwater pump trip, are 
     considered acceptable failure modes.  
.

                                     - 8 -


(b)  It is recommended that plant procedures and technical specifications for 
     all Combustion Engineering plants include provisions to verify 
     periodically the operability of overfill protection and ensure that 
     automatic MFW overfill protection is operable during reactor power 
     operation.  The instrumentation should be demonstrated to be operable by 
     the performance of a channel check, channel functional testing, and 
     channel calibration, including setpoint verification, and by identifying 
     the LCOs.  These technical specifications should be commensurate with 
     existing plant technical specifications requirements for channels that 
     initiate protection actions.  
     
(c)  It is recommended that all utilities that have plants designed with high-
     pressure-injection pump-discharge pressures less than or equal to 1275 
     psi reassess their emergency procedures and operator training programs 
     and modify them, as needed, to ensure that the operators can handle the 
     full spectrum of possible small-break loss-of-coolant accident (SBLOCA) 
     scenarios.  This may include the need to depressurize the primary system 
     via the atmospheric dump valves or the turbine bypass valves and cool 
     down the plant during some SBLOCA.  The reassessment should ensure that a
     single failure would not negate the operability of the valves needed to 
     achieve safe shutdown.  
     
     The procedure should clearly describe any actions the operator is 
     required to perform in the event a loss of instrument air, or electric 
     power prevents remote operation of the valves.  The use of the 
     pressurizer PORVs to depressurize the plant during an SBLOCA, if needed, 
     and the means to ensure that the RTNDT (reference temperature, nil 
     ductility transition) limits are not compromised should also be clearly 
     described.  Seven plants have been identified that have high pressure 
     injection pump discharge pressures less than or equal to 1275 psi that 
     may require manual pressure-relief capabilities using the valves to 
     achieve safe shutdown.  They are: Calvert Cliffs 1 and 2, Fort Calhoun, 
     Millstone 2, Palisades, and St. Lucie 1 and 2.  

Designs for Overfill Protection

CE-designed plants do not provide automatic steam generator overfill protec-
tion that terminates MFW flow.  Therefore, it is recommended that licensees 
and applicants for CE plants provide a separate and independent safety-grade 
or commercial-grade steam generator overfill-protection system that will serve
as backup to the existing feedwater runback, control system.  Existing 
water-level sensors may be used in a 2-out-of-4 initiating logic to isolate 
MFW flow on a steam generator high-water-level signal.  The proposed design 
should ensure that the overfill protection system is separate from the 
feedwater-control system so that it is not powered from the same power source,
is not located in the same cabinet, and is not routed so that a fire is likely
to affect both systems (common-mode failures described above are considered 
acceptable) and the plant procedures and technical specifications should 
include requirements to periodically verify operability of the system.  The 
information that is requested to be addressed in the plant procedures and the 
technical specifications is provided in item (4)(b) above. 
Page Last Reviewed/Updated Thursday, February 28, 2013