Bulletin 86-01: Minimum Flow Logic Problems That Could Disable RHR Pumps
SSINS No.: 6820 OMB No.: 3150-0012 IEB 86-01 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, DC 20555 May 23, 1986 IE COMPLIANCE BULLETIN NO. 86-01: MINIMUM FLOW LOGIC PROBLEMS THAT COULD DISABLE RHR PUMPS Addressees: All GE boiling water reactor (BWR) facilities holding an operating license (OL) or a construction permit (CP). Purpose: The purposes of this bulletin are: (1) to inform BWR licensees and applicants of a recently identified problem with the minimum flow logic for which a single failure could disable all RHR pumps, (2) to request that licensees affected by the problem immediately provide appropriate instructions and training to plant operators on how to recognize the problem if it occurs and take appropriate mitigating actions, (3) to request that licensees notify the NRC of the existence of the problem at their facility within 7 days of receipt of this bulletin, and (4) to request that licensees inform the NRC of measures taken to correct design or installation problems that are identified as a result of this bulletin. Description of Circumstances: During a recent review of IE Information Notice 85-94, "Potential For Loss Of Minimum Flow Paths Leading To ECCS Pump Damage During A LOCA," the Pilgrim Nuclear Power Plant discovered that a single failure under certain accident sequences could result in all RHR minimum flow bypass valves being signaled to close while all other pump discharge valves are also closed. This condition could result in no flow through the RHR pumps and could lead to the pumps running dead headed with potential for pump damage in a few minutes. If this single failure occurred in conjunction with an automatic start of the RHR system, RHR pump damage may occur if unrecognized by the operator. This event could disable RHR functions including Low Pressure Coolant Injection (LPCI), head spray, drywell spray, shutdown cooling, torus spray and suppression pool cooling. As a result of the loss of suppression pool cooling over a long period of time, core spray pumps could ultimately lose net positive suction head and also be unavailable. The NRC staff has judged that the overall probability of a serious core damage accident due to this problem is low. Nevertheless, such a single failure vulnerability is not in compliance with the regulatory requirement for independence in emergency core cooling systems and could compromise several important systems. 8605230308 . IEB 86-O1 May 23, 1986 Page 2 of 3 GE's initial review identified the following plants with some potential for having the single failure problem: Pilgrim; Browns Ferry 1, 2 and 3; Peach Bottom 2 and 3; Duane Arnold; Millstone 1; Monticello; Quad Cities 1 and 2; Dresden 2 and 3; Cooper; and Fermi 2. The staff understands that GE has notified these potentially affected facilities and informal communications from GE indicate that the list was narrowed to Pilgrim, Quad Cities and possibly Dresden during preparation of the bulletin. The above listed plants are being provided the bulletin by telecopy. Since there is not complete certainty that other BWR's do not have the problem, they are also addressed by this bulletin. Their copies are being sent by mail. At Pilgrim, to prevent the pump from running dead headed, each pair of RHR pumps is provided with a minimum flow bypass capability. The minimum flow bypass consists of an orificed flow bypass which allows a flow of approximately 10 percent of rated flow. The minimum flow bypass lines for each pair of RHR pumps are connected to a single line and controlled by a single minimum flow bypass valve. The minimum flow bypass valve is normally open. The valve will close upon sensing flow in either of the RHR loops. The current logic configuration for Pilgrim minimum flow bypass valves is that a high flow signal from either the A or B RHR loops will close both A and B bypass valves. Thus, a postulated single failure of a flow sensing instrument may result in all RHR pumps running without bypass flow. If this failure occurs during an event with a high drywell signal or low water level signal, such as during small or intermediate size loss of cooling accidents (LOCA) or spurious actuation, the RHR pumps may start and run dead headed. One of the potential fixes being proposed by GE is to remove the automatic closing signal from the RHR minimum flow bypass valves. This fix will result in some of the LPCI flow being diverted through the minimum flow line. For other RHR modes of operation, the values may be manually closed. Although safety analyses may justify this interim fix, there are a number of problems that need to be considered. For example, on many plants the minimum flow bypass valves must be closed during shutdown cooling in order to prevent draining the reactor vessel inventory to the torus. The minimum flow bypass valves are considered containment isolation valves on some plants. REQUIRED ACTION FOR GE BWR FACILITIES 1. Promptly determine whether or not your facility has this single failure vulnerability. 2. If the problem exists, immediately instruct all operating shifts of the problem and measures to recognize and mitigate the problem. 3. Within 7 days of receipt of this bulletin, provide (a) a written report to the NRC which identifies whether or not this problem exists at your facility, (b) if the problem exists, identify the short-term modifications to plant operating procedures or hardware that have been or are being implemented to assure safe plant operations. . IEB 86-01 May 23, 1986 Page 3 of 3 4. If the problem exists, provide a written report within 30 days of receipt of this bulletin informing the NRC of the schedule for long-term resolution of problems that are identified as a result of this bulletin. Should a licensee determine that any action requested by this bulletin jeopardizes overall plant safety, the NRC should be notified of that fact and provided with appropriate justification for not implementing the requested action. Such notification shall be made within 7 days of receipt of this bulletin. The written reports shall be submitted to the appropriate Regional Administrator under oath or affirmation under provisions of Section 182a, Atomic Energy Act of 1954, as amended. Also, the original copy of the cover letters and a copy of the reports shall be transmitted to the U.S. Nuclear Regulatory Commission, Document Control Desk, Washington, D.C. 20555 for reproduction and distribution. This request for information was approved by the Office of Management and Budget under a blanket clearance number 3150-0011. Comments on burden and duplication may be directed to the Office of Management and Budget, Reports Management, Room 3208, New Executive Office Building, Washington, D. C. 20503. If you have questions regarding this matter, please contact the Regional Administrator of the appropriate NRC Regional Office or one of the technical contacts listed below. James M. Taylor, Director Office of Inspection and Enforcement Technical Contacts: Eric Weiss, IE (301) 492-9005 M. Wayne Hodges, NRR (301) 492-7483 Attachment: List of Recently Issued IE Bulletins
Page Last Reviewed/Updated Tuesday, March 09, 2021
Page Last Reviewed/Updated Tuesday, March 09, 2021