Part 21 Report - 1999-400
ACCESSION #: 9909290055
ENGINE SYSTEMS, INC.
1220 S. Washington St.,
Rocky Mount, NC 27801
P.O. Box 1928,
Rocky Mount, NC 27802-1928
Telephone: 919/977-2720
Fax: 919/446-1134
September 23, 1999
U.S. Nuclear Regulator Commission
Document Control Desk
Mail Stop 0-11A1
Washington, DC 20555
Subject: | 10CFR21 Reporting of Defects and Non-Compliance Engine Systems, Inc. Report No. 10CFR21-0079 Woodward EGM controllers |
Dear Sir:
The enclosed report addresses a reportable defect and the corrective action to be taken by users of the EGM controllers.
Should you have any questions, please feel free to call.
Please sign below, acknowledging receipt of this report, and return a copy to the attention of Engineering Document Control at the address below (or, fax to number 919/446-1134) within 10 working days after receipt.
| Yours very truly, ENGINE SYSTEMS, INC. Jo-Ann Mason Engineering Document Control |
Please let us know if ANY of your mailing information changes - name of recipient, name of company/facility, address, etc. Mark the changes on this acknowledgment form and send to us by mail or FAX to the number above.
Quality Performance With Pride
ENGINE SYSTEMS, INC.
1220 S. Washington St.,
Rocky Mount, NC 27801
P.O. Box 1928,
Rocky Mount, NC 27802-1928
Telephone: 252/977-2720
Fax: 252/446-1134
| Report No. 10CFR21-0079 |
| Rev. 0: September 21, 1999 |
10CFR21 REPORTING OF DEFECTS AND NON-COMPLIANCE
COMPONENT: | Woodward EGM Controls (P/N 9903-081, 9903-085, 9903-109 & 9903-150) |
SYSTEM: | Turbine control systems |
CONCLUSION: | Defect is reportable in accordance with 10CFR21. |
PREPARED BY: | DATE: |
| Donald D. Galeazzi Engineering Manager | |
REVIEWED BY: | DATE: |
| Michael/Nuding Quality Assurance Manager | |
Quality Performance With Pride
REPORT NO. 10CFR21-0079
REVISION 0: 9/21/99
PAGE: 1 OF 2
SUMMARY: | Engine Systems Inc. (ESI) has received notification from Woodward that EGM controllers manufactured between December 1997 and May 1999 may have questionable soldering workmanship. Soldering workmanship was affected because of inadequate personnel training. This issue was discovered by PECO, Limerick Station during a visual inspection of internal components of an EGM controller. Deficiencies identified included wire strands, excessive solder flux (splash) and cold solder connections. To date, users have not reported any operabitiy issues with the suspect EGM's. ESI has thermally, radiation and seismically tested two (2) (#9903-085 & #9903-109) of the suspect EGM's without any failures. Each part was also subjected to an additional seismic test by ESI; again, no failures were observed. In addition, each EGM was subjected to a 50 hour burn-in test at Woodward as part of their normal manufacturing tests. |
COMPONENT: | Woodward EGM controllers (P/N 9903-081, 9903-085, 9903-109 and 9903-150) manufactured between December 1997 and May 1999. |
CUSTOMERS AFFECTED: | Woodward has provided a list of all suspect EGM's by serial number. Only new EGM's are suspect and these are identified in Exhibit 1. The listing contains all suspect EGM's; and identifies controllers supplied by ESI as well as controllers supplied directly by Woodward. Only customers with suspect EGM's supplied by ESI are listed below. |
| Carolina Power & Light, H.B. Robinson Commonwealth Edison Georgia Power, Hatch Illinois Power, Clinton Nebraska Public Power, Cooper Northern States Power, Prairie Island PECO Energy, Limerick |
DEFECT: | The controller circuit boards may have soldering workmanship deficiencies because of inadequate personnel training at the time of assembly. |
CORRECTIVE ACTION: | 1. Engine Systems issued a Corrective Action Report. Woodward had already performed corrective action to require proper personnel training/certification in the assembly area. |
| 2. Users should return suspect controllers for repair. For controllers supplied by ESI, please contact ESI's Customer Service Department. Please contact Woodward (Steve Thompson @ 970/498-3196) for repair of controllers supplied directly by Woodward. |
Because operability problems have not been identified, controllers can be returned at customer's convenience.
| REPORT NO. 10CFR21-0079 REVISION 0: 9/21/99 PAGE: 2 OF 2 |
EXHIBIT 1: SUSPECT WOODWARD EGM CONTROLLERS
| REPORT NO. 10CFR21-0079 REVISION 0: 9/21/99 EXHIBIT 1 PAGE: 1 OF 2 |
SUSPECT WOODWARD EGM CONTROLLERS SUPPLIED BY ENGINE SYSTEMS, INC.
Customer | Part Number | Serial Number |
Carolina Power & Light, Robinson | 9903-109 | 11985991 |
| 9903-109 | 11985992 |
Commonwealth Edison | 9903-085 | 12049616 |
| 9903-085 | 12049617 |
| 9903-085 | 12049618 |
| 9903-085 | 12049619 |
| 9903-085 | 12049620 |
| 9903-085 | 12049621 |
| 9903-085 | 12049622 |
| 9903-085 | 12049623 |
| 9903-085 | 12049624 |
Georgia Power, Hatch | 9903-085 | 11983380 |
| 9903-085 | 11983381 |
| 9903-085 | 11983382 |
| 9903-085 | 11953484 |
| 9903-085 | 11953485 |
| 9903-109 | 11983332 |
| 9903-109 | 11983333 |
| 9903-109 | 11983335 |
| 9903-109 | 11955402 |
| 9903-109 | 11955403 |
Illinois Power, Clinton | 9903-085 | 12048589 |
| 9903-085 | 12048590 |
| 9903-085 | 12048591 |
Nebraska Public Power, Cooper | 9903-085 | 12047526 |
| 9903-085 | 12047527 |
| 9903-109 | 11983334 |
| 9903-109 | 12048594 |
| 9903-109 | 12048596 |
Northern States Power, Prairie Island | 9903-109 | 12044586 |
Peco, Limerick | 9903-085 | 12046552 |
| 9903-085 | 12046553 |
| 9903-085 | 12046554 |
| 9903-085 | 12046555 |
| 9903-085 | 12046556 |
| 9903-085 | 12046557 |
| 9903-109 | 12048592 |
| 9903-109 | 12048593 |
| 9903-109 | 12048595 |
| 9903-109 | 12048597 |
| 9903-109 | 12049425 |
| 9903-109 | 12049426 |
| REPORT NO. 10CFR21-0079 REVISION 0: 9/21/99 EXHIBIT 1 PAGE: 2 OF 2 |
SUSPECT WOODWARD EGM CONTROLLERS SUPPLIED DIRECTLY BY WOODWARD
Customer | Part Number | Serial Number |
Arizona Public Service | 9903-085 | 12004728 |
| 9903-085 | 12019248 |
Commonwealth Edison | 9903-085 | 12071911 |
Dresser Rand | 9903-085 | 12086357 |
| 9903-109 | 12049427 |
Energy Northwest (Wash Pub Ser) | 9903-085 | 12017603 |
| 9903-085 | 12017604 |
GE Nuclear - San Jose | 9903-085 | 11946520 |
| 9903-085 | 11946948 |
| 9903-085 | 12034000 |
| 9903-085 | 12034001 |
| 9903-085 | 12034002 |
| 9903-085 | 12034003 |
| 9903-085 | 12034004 |
| 9903-085 | 12034005 |
| 9903-085 | 12054126 |
| 9903-085 | 12054127 |
| 9903-085 | 12054128 |
| 9903-109 | 11993328 |
| 9903-109 | 11993329 |
| 9903-109 | 12036290 |
| 9903-109 | 12036291 |
| 9903-109 | 12036292 |
| 9903-109 | 12036293 |
| 9903-109 | 12036294 |
| 9903-109 | 12036295 |
| 9903-109 | 12036296 |
Northern States Power, Prairie Island | 9903-085 | 12017640 |
Pennsylvania Power & Light | 9903-085 | 12083808 |
| 9903-085 | 12083809 |
| 9903-085 | 12083810 |
| 9903-109 | 12056912 |
| 9903-109 | 12056913 |
Woodward - Japan | 9903-081 | 11937746 |
| 9903-085 | 11925080 |
| 9903-085 | 11948690 |
| 9903-085 | 11984451 |
| 9903-085 | 11984452 |
| 9903-085 | 11984453 |
| 9903-085 | 11992393 |
| 9903-150 | 11955454 |
*** END OF DOCUMENT ***
Page Last Reviewed/Updated Thursday, March 25, 2021