Part 21 Report - 1998-350
LICENSEE: CONSOLIDATED EDISON CO. OF N.Y./NEW
SITE: INDIAN POINT 3 EN NUMBER:34155
DOCKET: 05000286 EVENT DATE: 04-29-98
RX TYPE: PWR EVENT TIME: 10:30
VENDORS: W-4-LP NOTIFY DATE: 04-30-98
EMERGENCY CLASS: N/A REGION: 1 STATE: NY TIME: 15:39
OPS OFFICER: CHAUNCEY GOULD
10 CFR SECTION: CCCC 21.21 UNSPECIFIED PARAGRAPH
UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE
CODE CRIT PWR PWR
3 N Y 100 POWER OPERATION 100 POWER OPERATION
PART 21 REPORT ON FAILURE OF 480 VAC BREAKER DUE TO LACK OF
LUBRICATION.
AN ENGINEERING EVALUATION CONCLUDED THE WESTINGHOUSE TYPE DS-416
CIRCUIT BREAKER FAILED TO OPEN ON DEMAND BECAUSE LUBRICATION AT
KEY PIVOT POINTS
IN THE BREAKER MECHANISM WAS MISSING. THE LACK OF PROPER
LUBRICATION WAS DETERMINED TO BE THE RESULT OF A BREAKER OVERHAUL
PERFORMED BY POWER DISTRIBUTION TECHNOLOGY (PDT) WHICH REMOVED
THE LUBRICANTS AND FAILED TO REAPPLY THEM. PDT HAD OVERHAULED
THE FAILED BREAKER AND THREE OTHER TYPE DS-416 BREAKERS IN 1994
IN ACCORDANCE WITH THE LICENSEE'S PURCHASE ORDER WHICH CONTAINED
SPECIFIC REQUIREMENTS RELATED TO LUBRICATION. THE LACK OF
LUBRICATION ON THE BREAKERS OVERHAULED BY PDT, WHICH IS NO LONGER
IN BUSINESS, COULD HAVE PREVENTED A BREAKER FROM PERFORMING ITS
SAFETY FUNCTION, RESULTING IN A SUBSTANTIAL SAFETY HAZARD.
THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.
Page Last Reviewed/Updated Wednesday, March 24, 2021