United States Nuclear Regulatory Commission - Protecting People and the Environment

ACCESSION #: 9801220116


                                                NSD-NRC-98-5516



Westinghouse   Energy Systems      Nuclear Services Division

Electric Corporation               PO Box 355

                                   Pittsburgh Pennsylvania 15230-0355



                                        January 15, 1998



U.S. Nuclear Regulatory Commission

ATTN: Document Control Desk

Washington, DC 20555-0001



ATTENTION: NRC Operations Center



Subject:  Notification of the Potential Existence of Defects Pursuant to

          10CFR21



Westinghouse has identified a possible defect in a basic component that

could potentially create a substantial safety hazard and therefore is

deemed reportable under 10CFR21.21(a).



Background/Evaluation



Westinghouse was recently notified of Solid State Protection System

(SSPS) circuits that were not fully tested during semi-automatic testing

of the system.  The circuits not fully tested are the Feedwater Isolation

Memory Circuit and the P10 Source Range Block Memory Circuit.  These

circuits rely on paralleling each input to provide an output without

utilizing the retentive memory.  The original testing arrangement did not

verify that both of the parallel inputs are operational because the

signal (e.g., P-4 for feedwater isolation) that initiates the retentive

memory was present at the logic gate input during testing.  An open logic

input isolation diode may prevent the desired output from the logic gate.



Safety Significance



For all plants that utilize the SSPS, this logic gate initiates feedwater

isolation on a safety injection signal or a hi-hi steam generator water

level signal.  Safety injection initiates a reactor trip and, for most pl

ants, the hi-hi steam generator water level initiates a turbine trip

through separate logic which leads to a reactor trip.  These functions

provide a P-4 (reactor trip) signal so feedwater isolation is initiated

with only a slight delay (milliseconds).  For Sequoyah Units 1 & 2 and

Watts Bar the turbine trip signal from hi-hi steam generator water level

is not initiated separately and depends on the proper functioning of the

logic gate with parallel inputs, as does feedwater isolation.  The lack

of feedwater isolation could lead to water carryover into the steam lines

for these plants.



The same type of circuit is used for the P-10 Source Range Block

function.  This is a back-up function to P-6 and if both of these

malfunctioned it would be detectable by observing that the source range

was not blocked as power increased.



Plant Applicability



The 10CFR Part 21 notification applies to the feedwater isolation

function at Sequoyah Units 1 & 2 and Watts Bar.



Illegible print



NSD-NRC-98-5516                    2                     January 15, 1998



Recommendations/Corrective Actions



Westinghouse has determined that circuit modifications are DOE required

to test both parallel inputs.  By pressing the reset switch, the

retentive memory signal (e.g., P-4 for feedwater isolation) is defeated

and the ability to obtain an output from the logic gate confirms that

both inputs are functioning.  Westinghouse has communicated this

information to all plants utilizing the SSPS via Technical Bulletin ESBU-

TB-97-09, dated December 17, 1997 (attached).  It is the understanding of

Westinghouse that Sequoyah and Watts Bar have made procedural changes to

implement the recommended testing.



If you have any questions regarding the notification, please call me at

412/374-5282.



Sincerely



H. A. Sepp, Manager

Regulatory and Licensing Engineering



Illegible print



                                             Westinghouse

ENERGY                                    Technical Bulletin

SYSTEMS

BUSINESS

UNIT



An advisory notice of a recent technical development pertaining to the

installation or operation of Westinghouse-supplied Nuclear Plant

equipment.  Recipients should evaluate the information and

recommendation, and initiate action where appropriate.



                                       P.O. BOX 355, Pittsburgh, PA 15230

Subject                                Number

SSPS Testing For Feedwater Isolation   ESBU-TB-97-09



System(s)                              Date

Solid State Protection System (SSPS)   December 17, 1997



Affected Plants                        S.O.(s) 387

Westinghouse NSSS With Solid State

Protection System



References          Affects Safety      Yes [x]   Sheet

                    Related Equipment   No  [ ]   1 of 8



SUMMARY



Westinghouse was notified of Solid State Protection System circuits that

were not fully tested during Semiautomatic testing of the system.  This

condition was discovered by a utility during a generic review of Logic

System testing.  The circuits not fully tested are the Feedwater

Isolation Memory Circuit and the P10 Source Range Block Memory Circuit.

Westinghouse recommends a special Memory function test to verify proper

operation of these circuits.  No circuit modifications are required to

perform the recommended tests.



BACKGROUND INFORMATION



Westinghouse was notified of a Solid State Protection System circuit that

was not fully tested during Semiautomatic testing of the system.  This

condition was discovered during a generic review of logic system testing.



Additional Information, if Required, may be Obtained from the Originator.

Telephone 412-314-3630   or (WIN) 284-3630.



                    Originator                    Approval



Thomas D. Harbaugh, Sr. Engineer        H. A. Sepp, Manager

Vintage I&C; Engineering, SSPS System    Regulatory and

Engineer                                Licensing Engineering



Thomas N Miller, Manager

Vintage I&C; Engineering, NPD, I & C Engineering



Neither Westinghouse Electric Corporation nor its employees make any

warranty or representation with respect to the accuracy, completeness or

usefulness of the information contained in (his report or assume any

responsibility for liability or damage which may result from the use of

such information.



1874A



                                                            ESBU-TB-97-09

                                                        Page 2 of 8 Pages



The circuits nor fully tested are the Feedwater Isolation Memory Circuit

and the P10 Source Range Block Memory Circuit.  Both circuits are tested

as a memory function.  However, both circuits also provide outputs from

the memory circuit even if all of the memory inputs are not present at

the circuit inputs.  The Demand or SET inputs to the Memory function use

parallel inputs to allow for circuit outputs without using the retentive

memory.



The current testing arrangement does not verify that the parallel inputs

to the memory function are viable.  Open input isolation diodes in the

circuit could prevent having required outputs when desired.  This

Technical Bulletin identifies the two Memory circuits within the Solid

State Protection System.  that use parallel inputs and are not fully

tested with the Semi-automatic tester.



CIRCUIT DESCRIPTION



Feedwater Isolation Memory Circuits



In some plants the Close Feedwater Valves signal closes both the

Feedwater Isolation valves and the Modulating Feedwater valves from the

same isolation signal.  In other applications, the Feedwater Isolation

valves are operated by the Turbine trip/Feed Pump trip signal and the

memory circuit only operates the modulating valves.  Typical descriptions

of the logic and testing problems are covered in this description.  This

discussion coven the typical arrangement for most plant sites.  This

description centers on the problem of not fully testing parallel inputs

into a logic board used to provide a memory function within the SSPS.  A

review of the SSPS schematics shows many small differences between

implementation of the feedwater isolation.  It was determined that two

main logic schemes were used to implement feedwater isolation and that

specific implementation of these schemes allows for variances in the

application.  Each plant is encouraged to review their SSPS System

schematic to determine which portions of the following descriptions apply

to their application.  Both of the logic schemes explained in this

bulletin are taken from typical SSPS schematics.



1874A



                                                            ESBU-TB-97-09

                                                        Page 3 of 8 Pages



The first logic scheme for closing the feedwater valves is shown in the

following figure:

Figure "TYPICAL FEEDWATER ISOLATION LOGIC (1)"


The above logic diagram shows that the feedwater valves are to be closed

on either a demand from an SI actuation or a Steam Generator HI-HI Water

level.  This close feedwater valve demand is latched in as a memory

function where the P4 (RX Trip Breaker Open) signal is present.



The demand for Feedwater Valves close is a SI "OR" HI-HI Water Level "OR"

retentive memory latch output based on P4 "AND" P4 Seal-in (Demand

feedback).  Feedwater valves are also closed by P4 "AND" Low Tavg.  It is

the first "OR" (SI/SG HI-HI) that the following circuit description

details.  The Low Tavg "AND" P4 close the feedwater valves if the reactor

is tripped (P4) and the plant is at Low Tavg and a manual reset c tears

the feedwater demand.



Because the circuit must pass the close feedwater valve demand with or

without the retentive memory function.  The logic board must be connected

in such a way as to pass the demand signal without having the P4 signal

present at the logic input. A retentive memory circuit must perform a 2/4

logic function before the signal will pass through to the memory output.

Usually this is provided by a demand and set signal and unlatched by a

reset signal.  A normal retentive circuit would have the SI or SG HI-HI

provide the demand as one-of-two inputs to the memory logic.  The second

input would be provided by the P4 signal.  The output would be tied back

to an input to keep the memory latched until P4 was removed.



The following Figure shows the circuit arrangement to implement the logic

shown in the above referenced logic figure and description.  Because the

current problem involves testing of the circuit, the figure shows test

input configurations.  Actual inputs are identified by signal input names

and would be paralleled to the rest inputs.



1874A



                                                            ESBU-TB-97-09

                                                        Page 4 of 8 Pages

Figure "TYPICAL LOGIC BOARD CONNECTIONS (1)".


                                  NOTE:



     The above circuit shows SI and SG HI-HI being "ORed" at the input to

     the memory circuit.  Some applications use a separate logic circuit

     to "OR" these two signals.



The above figure shows That the O1 output is tied back to the I2 input.

The switch inputs are for circuit testing and can be disregarded for this

description, The SI demand is tied to both the I3 input and the I4 input.

The 14 input connects back to the O3 output which connects to the I2

input.  The Steam Generator HI-HI level connects to the T3 and to the T4

inputs.  If an SI demand signal is present, the I4 input connects

internally to O3 out-put which is connected externally to the I2 input.

The O3 to I2 to O1 connection bypasses the memory function and causes the

Feedwater Isolation demand to be present at the O1 output any time the 14

input is set.  The same S1 demand is tied to the I3 input and has no

affect at the O1 output as long as the I4 input is present.  The O1

output tied back to the I2 input provides no function at this time.  If

the SI demand is removed the feedwater isolation demand at the O1 output

is removed as long as P4 is not present at the I1 input.



If a Steam Generator HI-HI demand is present at the T3 and T4 inputs, the

2/4 logic is met and the output at O1 demands the feedwater valves to

close.  The O1 output still has no effect on the circuit.  If the S/G HI-

HI demand is removed at the input, the 2/4 logic would not be met to

maintain the output at O1.  If the S/G HI-HI demand is present at the

input without P4 present, the O1 output will change to demand feedwater

isolation as long as the demand signals are present at the T3/T4 inputs.

Only if P4 input becomes present while either input (SI or SG HI-HI) is

being demanded will the retentive memory (seal-in) function,



The circuit is tested by the Memory function test on the Semi-automatic

Test Panel.  Test switch S506 uses two of its positions for this circuit

operation.  These are shown on the above figure as the SET and RESET

inputs To the logic circuit. The RESET portion of the test is tied at the

P4/I1 input line for both memory tests.  This maintains a logic set (low)

condition to the memory circuit as if P4 were present.  Pressing the

RESET switch opens the contact and causes the memory circuit to unlatch.

The first of the two memory tests input the SET input as if it were a

Steam Generator HI-HI input.  Pressing the SET switch inputs a S/G HI-HI

demand (low) at the T3 and T4 inputs causing the 2/4 logic to be met and

setting the O1 output (LOW).  This ties back to the I2 input and in

combination with the P4 (RESET) at



1874A



                                                            ESBU-TB-97-09

                                                        Page 5 of 8 Pages



I1 maintains the 2/4 logic when the SET switch is released, Although not

shown, the Memory Test lamp is tied to the O1 output.



The second memory test inputs the S1 demand (low) at the I4 and I3

inputs.  This memory output makes up as soon as the 14 input Is set and

latches the output via the O1/O3 to I2 input and the P4 (RESET).  The I3

input is bypassed in this arrangement and has no affect on the circuit

operation.  As long as the 14 input is functional, the O3/O1 connection

actuates the feedwater valve closed demand.  If P4 occurs during this I4

demand, the I2 (I4/O3) input and the I1 (N) input meet the 2/4 logic to

latch the memory.



Logic circuits that provide the inputs to this memory circuit are tested

for their operation by the semiautomatic tester.  The Safeguards Driver

circuit that is tied at the O1 output is tested by the Semiautomatic

tester, The Memory function provided by this circuit is tested by the SET

and RESET functions of the Semi-automatic tester, The function of the SI

or S/G HI-HI demand causing the feedwater valves to close without P4 is

not fully tested.  The following describes this test circuit operation.



When the memory circuit is tested, the P4 demand is present until the

RESET switch is pressed.  This always provides half of the 2/4 logic for

the memory function, Any input at T4 or T3 will meet the second half of

the 2/4 logic for memory operation.  For example, if CR10 is open, the P4

(RESET) input at I1 is present.  The S/G HI-HI is input by pressing the

SET Switch.  This input passes to both the T3 and T4 inputs, CR10 is part

of the isolation for the T3 input.  The T3 input would be blocked by the

open CR10.  However, the T4 input will pass through CR12 and fulfill the

2/4 logic for the memory function to operate.  The same is true if CR12

is open and diode CR10 is operational.  Because of the I4, O3, I2, and O1

arrangement, the SI input is not affected by this rest arrangement.  The

13 inputs acts like a parallel input that has no affect on circuit

operation.  Only the circuit for the I4 input requires extra testing.  If

CR6 (I4) input were open, the SET input would be tied to only the I3

input.  The combination of the RESET (P4 at I1) and the SET input at I3

will allow the memory circuit to pass its memory function test.  If only

a SI signal were present at the I3 input, the circuit would not operate

until P4 became present.



1874A



                                                            ESBU-TB-97-09

                                                        Page 6 of 8 Pages



The following figure shows the logic for the second logic arrangement

used to close the Feedwater valves:

Figure "TYPICAL FEEDWATER ISOLATION LOGIC (2)".


The above logic is similar to the first logic description, The main

difference in this logic arrangement is the implementation of the P4 and

Low Tavg- Low Tavg "OR" Feedback from the with P4 seal-in can latch the

memory function.  The Low Tavg "AND" P4 will close the feedwater valves.

This is similar to the first logic scheme.  If the reactor is tripped (N)

and the plant is at Low Tavg, the feedwater valves will close.  The logic

arrangement allows for feedback of the close Feedwater valves demand (P4

seal-in) signal "OR" Low Tavg in coincidence with P4 to latch the memory

function.



The following circuit description implements the logic diagram and its

functional description just referenced.  As before, because the current

problem involves testing, the circuit shows the test input connections;

Actual trip and ESF actuation inputs would be parallel to the test inputs

and are identified on the drawing by signal names.



1874A



                                                            ESBU-TB-97-09

                                                        Page 7 of 8 Pages


Figure "TYPICAL LOGIC BOARD CONNECTIONS (2)".


                                  NOTE:



     The above circuit shows an application where the SI and SG HI-HI

     signals were "ORed" on 2 separate logic circuit and input to the

     memory circuit on the same input line.  Some applications "OR" these

     two inputs at the input to the memory circuit.



The parallel arrangement of I4 and I2 are similar to the first other

logic arrangement discussed.  For passing the SI/SG HI-HI signals

immediately, only CR6 must be capable of conduction.  The I4 input ties

to the O3 output which ties to both the T3 input and 01 output.  This

arrangement bypasses the I2 input as long as CR6 is viable, The circuit

requires an output as soon as an SI or SG HI-HI input is set.  This is

accomplished by I4 to O3 to T3 and I2.  If CR6 is open, the circuit will

not output on just SI/SG HI-HI demand because the I2 input does not meet

the 2/4 logic input for the memory function.  If CR3 is open, the circuit

will provide an output from the I4 input alone.  The 12 input serves no

function as long as I4 input can be processed.



The testing scheme uses two Memory function tests to verify the circuit

operation.  The RESET is applied to the I1 input and simulates P4 being

present at all times.  The first memory test applies a SET to I4/I2 and

simulates SI/SG HI-HI inputs.  The second memory test applies a SET to I3

and simulates the Low Tavg inputs.  This test arrangement does not test

the CR6 and CR3 diodes.



P10 Source Range Block Memory Circuit



The other memory test that has the same type of application is found in

the Source Range Block circuit.  This arrangement is present at the P10

inputs on Logic card A408 in the Source Range Block circuits.  In this

case, P10 is applied to both the I1 and I2 inputs of the SR Block memory

card.  P6 is applied at T4 and the manual block function is applied at

the 13 input.  The O1 output is tied back to the T3 input to provide the

retentive memory function.



One of the two memory tests for this circuit applies a SET at the P10

input.  P10 provides an automatic SR Block if this has not been provided

by the time the P10 power level is reached.  It is intended to be a 1874A







                                                            ESBU-TB-97-09

                                                        Page 8 of 8 Pages



back-up to P6 and keep the SR High Voltage deenergized.  Two inputs are

used by P10 to meet the 2/4 logic for Memory Circuit operation, The

memory test does not separate P10 inputs and no other Tests in SSPS

verify this P10 operation.  In this case either CR1 or CR3 being open may

not be detected by The memory function test



WESTINGHOUSE RECOMMENDATIONS.



Westinghouse has determined that no circuit modifications are required to

test the above referenced conditions.  Westinghouse does recommend that a

special Memory function test be accomplished to verify the operation of

the isolation diodes in these circuits.



Westinghouse recommends that each site review their specific application

and implementation of the Feedwater Isolation circuit.  Some applications

show the SI and SO HI-HI inputs to the circuit are "ORed" at the input to

the memory circuit.  Other applications show the SI and SG HI-HI signals

are "ORed" on a separate logic circuit and are input to the memory

circuit on the same input lines.  For the applications where the SI and

SG HI-HI inputs are "ORed" at the memory circuit inputs, two special

memory tests are required because both signal inputs use parallel inputs

to the memory circuit (see the figure for Typical Logic Board Connections

(1) in this bulletin).  The applications that use a separate logic

circuit to "OR" the SI and SG HI-HI signals require only one special

memory test.  The single input is t@e only parallel input (see figure

Typical Logic Board Connections (2) in this bulletin).



For the SI and S/G HI-HI circuits, opening the P4 input while operating

the SET inputs will allow only the SI and S/G HI-HI input to operate the

O1 output.  Opening P4 can be accomplished by pressing the RESET switch

when performing this memory function test.



Special Memory Tests



The special memory test can be performed as part of the bimonthly

surveillance already being performed on the SSPS.  Each plant must review

the SSPS schematics and Technical Manual documentation to determine which

position(s) of the Memory Test switch are used to test the A213 memory

circuit.  When aligned to perform the Memory function test for the A213

memory circuit, press the RESET Switch and hold it down.  At the same

time press the SET switch and verify that the memory test lamp lights.

Release The SET switch and verify that the memory test lamp goes off.

Release the RESET switch and complete the normal memory function test for

that position.



By holding the RESET switch, the 2/4 logic for the memory circuit is only

met by the two inputs from the SET switch.  If either of the two input

diodes are open.  this test will not light the output memory test lamp.

This test must be completed for each of the inputs that provide parallel

inputs to the logic circuit.



For the Source Range Circuit, align the Memory function for the P10 input

(e.g. S506-4).  Press the RESET switch and hold it down.  At the same

time, press the SET switch and verify the Memory test lamp Turns on.

Release the SET switch and verify the Memory rest lamp is off.  Release

the RESET switch and complete a normal memory function test.  The memory

test lamp will not light if either CR1 or CR3 are open on the A408 Logic

Board.



For additional information, questions, or comments please contact the

appropriate Westinghouse Commercial Product Manager (CPM) for each

affected plant.  The CPM will forward all information to the appropriate

product line system engineer.



1874A



GENERAL INFORMATION or OTHER              EVENT NUMBER: 33542



LICENSEE: WESTINGHOUSE ELECTRIC COMPANY   NOTIFICATION DATE: 01/15/98

    CITY: PITTSBURGH          REGION: 1   NOTIFICATION TIME: 14:07 [ET]

  COUNTY:                      STATE: PA  EVENT DATE:        01/15/98

LICENSE#:                  AGREEMENT: N   EVENT TIME:        00:00[EST]

  DOCKET:                                 LAST UPDATE DATE:  01/15/98



                                                  NOTIFICATIONS



NRC NOTIFIED BY: JOHN GALEMBUSH           VERN HODGE      NRR

HQ OPS OFFICER:  BOB STRANSKY



EMERGENCY CLASS: NOT APPLICABLE

10 CFR SECTION:

CCCC 21.21     UNSPECIFIED PARAGRAPH



                               EVENT TEXT



10 CFR PART 21 REPORT REGARDING TESTING OF SOLID STATE PROTECTION

SYSTEM

LOGIC



WESTINGHOUSE WAS RECENTLY NOTIFIED OF SOLID STATE PROTECTION

SYSTEM

(SSPS) CIRCUITS THAT WERE NOT FULLY TESTED DURING SEMI-AUTOMATIC

TESTING

OF THE SYSTEM.  THE CIRCUITS NOT FULLY TESTED ARE THE FEEDWATER

ISOLATION

MEMORY CIRCUIT AND THE P-10 SOURCE RANGE BLOCK MEMORY CIRCUIT. 

THESE

CIRCUITS RELY ON PARALLELING EACH INPUT TO PROVIDE AN OUTPUT

WITHOUT

UTILIZING THE RETENTIVE MEMORY.  THE ORIGINAL TESTING ARRANGEMENT

DID NOT

VERIFY THAT BOTH OF THE PARALLEL INPUTS ARE OPERATIONAL BECAUSE THE

SIGNAL (E.G., P-4 FOR FEEDWATER ISOLATION) THAT INITIATES THE RETENTIVE

MEMORY WAS PRESENT AT THE LOGIC GATE INPUT DURING TESTING.  AN OPEN

LOGIC

INPUT ISOLATION DIODE MAY PREVENT THE DESIRED OUTPUT FROM THE LOGIC

GATE.



FOR ALL PLANTS THAT UTILIZE THE SSPS, THIS LOGIC GATE INITIATES

FEEDWATER

ISOLATION ON A SAFETY INJECTION SIGNAL OR A HI-HI STEAM GENERATOR

WATER

LEVEL SIGNAL.  SAFETY INJECTION INITIATES A REACTOR TRIP AND, FOR MOST

PLANTS, THE HI-HI STEAM GENERATOR WATER LEVEL INITIATES A TURBINE

TRIP

THROUGH SEPARATE LOGIC WHICH LEADS TO A REACTOR TRIP.  THESE

FUNCTIONS

PROVIDE A P-4 (REACTOR TRIP) SIGNAL SO FEEDWATER ISOLATION IS INITIATED

WITH ONLY A SLIGHT DELAY (MILLISECONDS).  FOR SEQUOYAH UNITS 1 AND 2

AND

WATTS BAR THE TURBINE TRIP SIGNAL FROM HI-HI STEAM GENERATOR WATER

LEVEL

IS NOT INITIATED SEPARATELY AND DEPENDS ON THE PROPER FUNCTIONING OF

THE

LOGIC GATE WITH PARALLEL INPUTS, AS DOES FEEDWATER ISOLATION.  THE

LACK

OF FEEDWATER ISOLATION COULD LEAD TO WATER CARRYOVER INTO THE

STEAM LINES

FOR THESE PLANTS.



THE SAME TYPE OF CIRCUIT IS USED FOR THE P-10 SOURCE RANGE BLOCK

FUNCTION.



(Continued on next page)

LICENSEE: WESTINGHOUSE ELECTRI     PAGE # 2 OF EVENT NUMBER: 33542



THIS IS A BACK-UP FUNCTION TO P-6 AND IF BOTH OF THESE MALFUNCTIONED IT

WOULD BE DETECTABLE BY OBSERVING THAT THE SOURCE RANGE WAS NOT

BLOCKED AS

POWER INCREASED.



WESTINGHOUSE HAS DETERMINED THAT CIRCUIT MODIFICATIONS ARE NOT

REQUIRED

TO TEST BOTH PARALLEL INPUTS.  BY PRESSING THE RESET SWITCH, THE

RETENTIVE MEMORY SIGNAL (E.G., P-4 FOR FEEDWATER ISOLATION) IS

DEFEATED

AND THE ABILITY TO OBTAIN AN OUTPUT FROM THE LOGIC GATE CONFIRMS

THAT

BOTH INPUTS ARE FUNCTIONING.  WESTINGHOUSE HAS COMMUNICATED THIS

INFORMATION TO ALL PLANTS UTILIZING THE SSPS VIA TECHNICAL BULLETIN

ESBU-

TB-97-09, DATED DECEMBER 17, 1997.


*** END OF DOCUMENT ***