Part 21 Report - 1997-840
LICENSEE: CONSOLIDATED EDISON CO. OF N.Y./NEW
SITE: INDIAN POINT 2 EN NUMBER:33273
DOCKET: 05000247 EVENT DATE: 11-17-97
RX TYPE: PWR EVENT TIME: 16:45
VENDORS: W-4-LP NOTIFY DATE: 11-17-97
EMERGENCY CLASS: N/A REGION: 1 STATE: NY TIME: 17:41
OPS OFFICER: DICK JOLLIFFE
10 CFR SECTION: CDEG 21.21(c)(3)(i) DEFECTS/NONCOMPLIANCE
UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE
CODE CRIT PWR PWR
2 N N 0 COLD SHUTDOWN 0 COLD SHUTDOWN
- 10CFR21 REPORT OF DEFECTIVE T-DRAINS ON ENVIRONMENTALLY
QUALIFIED MOVs -
INDIAN POINT UNIT 2 IS IN MODE 5 (COLD SHUTDOWN) IN A MAINTENANCE
OUTAGE.
WHILE PREPARING TO INSTALL A SPARE MOTOR ON ENVIRONMENTALLY
QUALIFIED (EQ) MOTOR OPERATED VALVE (MOV) #MOV-856D, THE LICENSEE
DISCOVERED THAT THE MOV HAD A DEFECTIVE T-DRAIN. IN ORDER FOR AN
EQ MOV TO BE OPERABLE, THE VALVE MUST HAVE A T-DRAIN INSTALLED TO
RELIEVE MOISTURE BUILDUP IN A HARSH ENVIRONMENT FOLLOWING A MAJOR
ACCIDENT.
THE T-DRAIN, SUPPLIED BY LIMITORQUE, INC, LYNCHBURG, VA, WAS NOT
DRILLED THROUGH AND WOULD ACT AS A PIPE PLUG RATHER THAN AS A
PIPE DRAIN. THE LICENSEE OBSERVED THIS CONDITION TO BE AN
APPARENT MANUFACTURER'S DEFECT.
THE SPARE MOTOR HAD BEEN REMOVED FROM THE SPARE ACTUATOR FOR
#MOV-536 WHICH HAD BEEN REMOVED FROM SERVICE IN 1993, REBUILT,
AND STORED FOR FUTURE USE.
THE LICENSEE INSPECTED ALL EQ MOVs AND FOUND SEVERAL WITH A
SIMILAR DEFECTIVE T-DRAIN. THE LICENSEE HAS REMOVED ALL
DEFECTIVE T-DRAINS AND INSTALLED PROPERLY DRILLED T-DRAINS ON ALL
EQ MOVs.
THE LICENSEE PLANS TO PREPARE A WRITTEN REPORT OF THIS CONDITION
AND
SUBMIT IT TO THE NRC PER 10CFR21.21.
THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.