Part 21 Report - 1997-572
ACCESSION #: 9709230255
NSD-NRC-97-5330
Westinghouse Energy Systems Nuclear Services Division
Electric Corporation
Box 355
Pittsburgh Pennsylvania
15230-0355
September 18, 1997
U.S. Nuclear Regulatory Commission
ATTN: Document Control Desk
Washington, DC 20555-0001
ATTN: NRC Operations Center
Subject: Follow-up to Notification of the Potential Existence of Defects
Pursuant to 10CFR 21.21
Westinghouse provided a Notification of the Potential Existence of
Defects Pursuant to 10CFR 21.21 regarding HMCP (Motor Circuit Protectors)
molded case circuit breakers on August 19, 1997 via NSD-NRC-97-5267.
Attached, with the original notification is a Nuclear Safety Advisory
Letter (NSAL-97-007, dated 9/17/97) which transmitted recommendations
regarding this issue to potentially impacted plans. The plants are
identified in the NSAL.
If you have any questions regarding this information, please call me at
412/374-5292.
Sincerely,
H. A. Sepp, Manager
Regulatory and Licensing Engineering
/p
Attachment
"The mission of NSD is to provide our customers with people,
equipment and services that set the standards of excellence in the
nuclear industry."
2536C-RBM-1:091897
Westinghouse NUCLEAR SAFETY ADVISORY LETTER
Energy Systems
Business
Unit
THIS IS A NOTIFICATION OF A RECENTLY IDENTIFIED POTENTIAL SAFETY ISSUE
PERTAINING TO BASIC COMPONENTS SUPPLIED BY WESTINGHOUSE. THIS
INFORMATION IS BEING PROVIDED TO YOU SO THAT A REVIEW OF THIS ISSUE
CAN
BE CONDUCTED BY YOU TO DETERMINE IF ANY ACTION IS REQUIRED.
P.O. Box 355, Pittsburgh, PA 15230-0355
Subject: Breaker Trip Settings Number: NSAL-97-007
Basic Component: HMCP Molded Case Circuit Breakers Date: 9/17/97
Plants: See Sheet 3
Substantial Safety Hazard of Failure to Comply Pursuant to 10 CFR
21.21(a) Yes [x] No [ ]
Transfer of Information Pursuant to 10 CFR 21.21(b) Yes [ ]
Advisory Information Pursuant to 10 CFR 21.21(d)(2) Yes [ ]
Reference: NSD-NRC-97-5267, 8/19/97
SUMMARY
Three HMCP (Motor Circuit Protectors) molded case circuit breakers were
returned when a utility determined that some of the poles were tripping
outside the specified range. The settings had been verified through a
commercial dedication process. This issue was reported to the NRC
pursuant to 10 CFR Part 21 (copy attached). Recommendations for on-site
testing are provided.
Additional information, if required, may be obtained from the originator.
Telephone 412-374-5953.
Originator(s):
R. B. Miller H. A. Sepp, Manager
Regulatory & Licensing Regulatory & Licensing
Engineering Engineering
1810A/NSAL-97-00 Sheet 1 of 3
ISSUE DESCRIPTION
Three HMCP (Motor Circuit Protectors) molded case circuit breakers were
recently returned to Westinghouse's vendor, Cutler-Hammer when the
utility determined that some of the poles were tripping outside the
setpoint calibration range. These breakers were verified to be within
specification before shipment as part of the Westinghouse commercial
dedication process, but two tested out of specification before
installation at the plant and one tripped in service when the motor was
started. All were found with at least one pole out of specification when
returned.
TECHNICAL EVALUATION
HMCP Series C breakers, through magnetic trip action, provide
instantaneous short circuit protection for motor circuits. These
breakers have ratings from 3 amps to 600 amps in three frame sizes, The
three breakers returned were all 400 amp, but there is no evidence that
limits the issues to this, size breaker. The breakers am tested at the
lowest setting and the highest setting as part of the commercial
dedication process. Intermediate settings are not tested during the
commercial dedication process. The returned breakers were verified to be
out of specification at the low and high setting positions. Although
many utilities will perform a verification test before installation,
Westinghouse has not included this as part of maintenance
recommendations.
ASSESSMENT OF SAFETY SIGNIFICANCE
The setpoint on a HMCP breaker is selected to provide circuit protection
without tripping on motor starting current. Several trip ranges are
available for selection on each breaker. If the setpoint is not within
the selected range, the possibility exists that the circuit will open
preventing a safety-related motor from starting. Westinghouse determined
that this issue could potentially create a substantial safety hazard and
therefore reported it under 10 CFR Part 21, Confidence in continued
system performance can be established by a history of successful motor
start tests even if the breaker was not tested at the plant prior to
installation.
RECOMMENDED ACTIONS
Westinghouse recommends that the setpoint selected on the HMCP breakers
be verified prior to installation in addition to periodic surveillance
testing. Each pole should be tested separately. It is not recommended
that the breakers be tested with all poles in series since all pole trip
actuators would be exerting a force on the trip bar at the same time,
which could result in tripping at a lower current.
1810A/NSAL-97-00 Sheet 2 of 3
POTENTIALLY AFFECTED PLANTS
H. B. Robinson Unit 2
Shearon Harris
Haddam Neck
McGuire Units 1 & 2
Catawba Units 1 & 2
Turkey Point Unit 3
Wolf Creek
Callaway
Point Beach Unit 1
Yonggwang Units 1 & 2
Maanshan Units 1 & 2
Crystal River Unit 3
Three Mile Island Unit 1
Chinshan Units 1 & 2
Brunswick Units 1 & 2
Peach Bottom Units 2 & 3
Vermont Yankee
Kuosheng Unit 2
Laguna Verde Units 1 & 2
1810A/NSAL-97-00 Sheet 3 of 3
*** END OF DOCUMENT ***
Page Last Reviewed/Updated Wednesday, March 24, 2021