Part 21 Report - 1997-570
LICENSEE: WESTINGHOUSE ELECTRIC CORPORATION
SITE: WESTINGHOUSE ELECTRIC CORPORAT EN NUMBER:32788
DOCKET: EVENT DATE: 08-19-97
RX TYPE: EVENT TIME: 00:00
VENDORS: NOTIFY DATE: 08-20-97
EMERGENCY CLASS: N/A REGION: 1 STATE: PA TIME: 10:46
OPS OFFICER: BOB STRANSKY
10 CFR SECTION: CDEG 21.21(c)(3)(i) DEFECTS/NONCOMPLIANCE
10 CFR PART 21 REPORT
TYPE HMPC SERIES 'C' MOLDED CASE CIRCUIT BREAKERS HAVE BEEN FOUND
TO HAVE AS-FOUND TRIP SETPOINTS OUTSIDE OF THE SPECIFIED
CALIBRATION RANGE WHEN TESTED. THESE BREAKERS HAD BEEN TESTED
SATISFACTORILY BY THE VENDOR BEFORE SHIPMENT AS PART OF THE
VENDOR'S COMMERCIAL DEDICATION PROCESS. THE VENDOR RECOMMENDS
THAT UTILITIES VERIFY THE SETPOINTS FOR BREAKERS USED IN SAFETY
RELATED APPLICATIONS PRIOR TO INSTALLATION.