Part 21 Report - 1997-440

LICENSEE: NORTHEAST UTILITIES SITE: MILLSTONE 1 EN NUMBER:32442 DOCKET: 05000245 EVENT DATE: 06-06-97 RX TYPE: BWR EVENT TIME: 00:00 VENDORS: GE-3 NOTIFY DATE: 06-06-97 EMERGENCY CLASS: N/A REGION: 1 STATE: CT TIME: 15:16 OPS OFFICER: BOB STRANSKY 10 CFR SECTION: CDEG 21.21(c)(3)(i) DEFECTS/NONCOMPLIANCE UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE CODE CRIT PWR PWR 1 N N 0 COLD SHUTDOWN 0 COLD SHUTDOWN 10 CFR PART 21 REPORT - GE MODEL #IFCS RELAYS PROCURED FROM GENERAL ELECTRIC NUCLEAR ENERGY UNDER A SAFETY RELATED PURCHASE ORDER WERE DELIVERED WITH LOOSE HARDWARE AND WERE UNSUITABLE FOR USE AT MILLSTONE UNIT 1. SUBSEQUENT SURVEILLANCE BY YANKEE ATOMIC ELECTRIC COMPANY REVEALED DEFICIENCIES IN THE GENERAL ELECTRIC COMMERCIAL DEDICATION PROCESS. THE MANUFACTURING DEFECTS WHICH WERE IDENTIFIED BY NORTHEAST UTILITIES WOULD HAVE IMPACTED OPERATION OF THE RELAY. THE LICENSEE HAS DETERMINED THIS CONDITION TO BE A SUBSTANTIAL SAFETY HAZARD. REFER TO THE HOO LOG FOR LICENSEE CONTACT NAME AND TELEPHONE NUMBER.