WESTINGHOUSE DHP CIRCUIT BREAKERS FAILED TO CLOSE ON DEMAND DUE
TO A DIRTY AND BINDING MOTOR CUT-OFF SWITCH AND SPRING CHARGE
INDICATOR MECHANISM. THE VENDOR LITERATURE FAILED TO PROVIDE
GUIDANCE FOR INSPECTING, CLEANING, ADJUSTING, OR LUBRICATING
THESE VITAL COMPONENTS. THE LICENSEE HAS EVALUATED THIS ISSUE
AND CONCLUDES THAT IT IS REPORTABLE UNDER THE PROVISIONS OF 10
CFR PART 21.