Part 21 Report - 1996-570
ACCESSION #: 9608300075
Public Service
Electric and Gas
Company
E. C. Simpson Public Service Electric and Gas Company P.O. Box 236,
Hancocks Bridge, NJ 08038 609-339-1700
Senior Vice President - Nuclear Engineering
AUG 21 1996
LR-N96257
United States Nuclear Regulatory Commission
Document Control Desk
Washington, DC 20555
Gentlemen:
10CFR21 INTERIM REPORT, GENERAL ELECTRIC 4 KV MAGNE-BLAST BREAKER
LATCHING MECHANISM PROPS
SALEM GENERATING STATION UNITS 1 AND 2
FACILITY OPERATING LICENSE NO. DPR-70 AND DPR-75
DOCKET NOS. 50-272 AND 50-311
Pursuant to the notification requirements of 10 CFR 21.21(a)(2), Public
Service Electric and Gas Company (PSE&G) is providing this interim report
regarding chipping of latching mechanism props installed in General
Electric 4 kV Magne-Blast circuit breakers, Type AM-4.16-350-2H. PSE&G
identified this deviation on June 25, 1996.
During 4 kV breaker testing, chipping was observed on the side edge of
props in four spare breakers. The prop functions to latch the breaker
closed after a closing demand. No prop failures have occurred. However,
an evaluation of the effect of the chipping on the structural integrity
of the prop has not been completed.
Two of the affected breakers have been returned to the vendor. The props
on these breakers will be removed and will be evaluated metallurgically.
The four breakers will not be returned to the plant until the cause for
the chipping has been determined and any required corrective actions
implemented.
PSE&G's evaluation to date has not identified a substantial safety
hazard. The evaluation for reportability in accordance with 10 CFR 21 is
scheduled to be completed by October 23, 1996.
Document Control Desk -2-
LR-N96257 AUG 21 1996
Should you have any questions, please contact us.
Sincerely,
C Mr. H. J. Miller, Administrator - Region I
U. S. Nuclear Regulatory Commission
475 Allendale Road
King of Prussia, PA 19406
Mr. L. N. Olshan, Licensing Project Manager Salem
U. S. Nuclear Regulatory Commission
One White Flint North
11555 Rockville Pike
Mail Stop 14E21
Rockville, MD 20852
Mr. C. Marschall (X24)
USNRC Senior Resident Inspector
Mr. K. Tosch, Manager IV
Bureau of Nuclear Engineering
33 Arctic Parkway
CN 415
Trenton, NJ 08625
*** END OF DOCUMENT ***
Page Last Reviewed/Updated Wednesday, March 24, 2021