Part 21 Report - 1995-210
HARRIS 1 29397 09-27-95 POW
LICENSEE: CAROLINA POWER & LIGHT CO.
SITE: .HARRIS 1 . EN NUMBER:29397
DOCKET: 05000400 EVENT DATE: 09-27-95
RX TYPE: PWR EVENT TIME: 00:00
VENDORS: W-3-LP NOTIFY DATE: 09-29-95
EMERGENCY CLASS: N/A REGION: 2 STATE: NC TIME: 16:27
OPS OFFICER: RUDY KARSCH
10 CFR SECTION: CDEF 21.21(b)(2) DEFECTS/NONCOMPLIANCE
UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE
CODE CRIT PWR PWR
1 N N 0 REFUELING 0 REFUELING
ANCHOR DARLING 2" CHECK GLOBE VALVES DO NOT MEET MINIMUM FORWARD
FLOW REQUIREMENTS AND EXHIBIT EXCESSIVE BACKSEAT LEAKAGE, THESE
VALVES ARE USED IN CHARGING SAFETY INJECTION PUMP MINIFLOW LINES.
THE FORWARD FLOW DEFICIENCY COULD CREATE A SUBSTANTIAL SAFETY
HAZARD. THESE VALVES MAY ALSO BE USED IN SIMILAR APPLICATIONS AT
OTHER NUCLEAR SITES.
Page Last Reviewed/Updated Wednesday, March 24, 2021