Event Notification Report for March 10, 2022

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/09/2022 - 03/10/2022

EVENT NUMBERS
55762 55763 55775 55780
Agreement State
Event Number: 55762
Rep Org: Colorado Dept of Health
Licensee: Avago Tech
Region: 4
City: Fort Collins   State: CO
County:
License #: GL002495
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Gerond George
Notification Date: 03/02/2022
Notification Time: 12:04 [ET]
Event Date: 03/02/2022
Event Time: 12:04 [MST]
Last Update Date: 03/02/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
Agrawal, Ami (R4)
NMSS_Events_Notification, (EMAIL)
ILTAB, (EMAIL)
Event Text
EN Revision Imported Date: 3/10/2022

EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGNS

The following information was received via E-mail:

On 01/27/22, Avago Tech reported four tritium exit signs (2.3 Ci each) as lost during their final wrap up shipment for disposal.

NMED No.: CO220005

THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf.


Agreement State
Event Number: 55763
Rep Org: Iowa Department of Public Health
Licensee: Arconic Davenport, LLC
Region: 3
City: Bettendoff   State: IA
County:
License #: 0162182FG
Agreement: Y
Docket:
NRC Notified By: Dahlin Randal
HQ OPS Officer: Karen Cotton-Gross
Notification Date: 03/03/2022
Notification Time: 09:57 [ET]
Event Date: 03/02/2022
Event Time: 00:00 [CST]
Last Update Date: 03/03/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
Feliz-Adorno, Nestor (R3)
NMSS_Events_Notification, (EMAIL)
Event Text
EN Revision Imported Date: 3/10/2022

EN Revision Text: AGREEMENT STATE REPORT - STUCK SHUTTER GAUGE
The following information was provided by the Iowa Department of Public Health via email:

"A stuck shutter was discovered Wednesday, March 2nd on the B-gauge, shutter 1. Entry to the gauge house has been prohibited per protocol. Measurements indicate an increase dose rate relative to background at the south side adjacent to the gauge and shutter 1 position, with a maximum reading of 0.11 mR/hr. The licensee's service provider, SenTek, has been requested to perform emergency repair work. The B-Gauge was repaired last night around 1900 CST. The shutter failed to close due to the solenoid valve that opens and closes the shutter, which would not vent pressure. The failed solenoid valve was replaced by a new valve. The project to replace these gauges with x-ray technology is ongoing and on track to be replaced by first quarter, 2023."

"Source/Radioactive Material: SEALED SOURCE GAUGE
Manufacturer: Isotope Measuring Systems, Inc.
Model Number: NOT KNOWN IAEA Category: 3
Serial Number: 2332-2336L
Radionuclide: AM-241
Activity: 5 Ci (185 GBq)"

Iowa Event Number: IA220001


Power Reactor
Event Number: 55775
Facility: Davis Besse
Region: 3     State: OH
Unit: [1] [] []
RX Type: [1] B&W-R-LP
NRC Notified By: Robert Oesterle
HQ OPS Officer: Donald Norwood
Notification Date: 03/09/2022
Notification Time: 00:47 [ET]
Event Date: 03/08/2022
Event Time: 19:19 [EST]
Last Update Date: 03/09/2022
Emergency Class: Non Emergency
10 CFR Section:
26.719 - Fitness For Duty
Person (Organization):
Hanna, John (R3DO)
FFD Group, (EMAIL)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Refueling 0 Refueling
Event Text
EN Revision Imported Date: 3/10/2022

EN Revision Text: FITNESS-FOR-DUTY REPORT - CONTRACT SUPERVISOR FAILED FITNESS-FOR-DUTY TEST

The following information was provided by the licensee via phone and email:

A non-licensed, contract employee supervisor had a confirmed positive for alcohol during a follow-up fitness-for-duty test. The employee's access to the plant has been terminated.

The NRC Resident Inspector has been notified.


Power Reactor
Event Number: 55780
Facility: Brunswick
Region: 2     State: NC
Unit: [2] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: Jason Krupp
HQ OPS Officer: Dan Livermore
Notification Date: 03/09/2022
Notification Time: 23:20 [ET]
Event Date: 03/09/2022
Event Time: 20:13 [EST]
Last Update Date: 03/09/2022
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(3)(v)(D) - Accident Mitigation
Person (Organization):
Miller, Mark (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
HIGH PRESSURE COOLANT INJECTION (HPCI) INOPERABLE

The following information was provided by the licensee:

"At 2013 EST on March 9, 2022, the HPCI System was declared inoperable following evaluation of routine HPCI surveillance testing data indicating that the required response time for reaching rated conditions was not met. Therefore, this condition is being reported as an eight-hour, non-emergency notification per 10 CFR 50.72(b)(3)(v)(D). The Reactor Core Isolation Cooling (RCIC) System and Automatic Depressurization System (ADS) are operable.

"There was no impact on the health and safety of the public or plant personnel. Investigation is in-progress to determine the cause.

"Unit 1 is not affected by this event. Unit 1 is in a refueling outage.

"The NRC Resident Inspector has been notified."