Event Notification Report for August 21, 2002
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
08/20/2002 - 08/21/2002
** EVENT NUMBERS **
38602 39134 39139
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38602 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CRYSTAL RIVER REGION: 2 |NOTIFICATION DATE: 01/01/2002|
| UNIT: [3] [] [] STATE: FL |NOTIFICATION TIME: 10:08[EST]|
| RXTYPE: [3] B&W-L-LP |EVENT DATE: 01/01/2002|
+------------------------------------------------+EVENT TIME: 09:19[EST]|
| NRC NOTIFIED BY: BILL BANDHAUER |LAST UPDATE DATE: 08/20/2002|
| HQ OPS OFFICER: FANGIE JONES +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |ANNE BOLAND R2 |
|10 CFR SECTION: | |
|APRE 50.72(b)(2)(xi) OFFSITE NOTIFICATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|3 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION DUE RESCUED SEA TURTLE |
| |
| EN #37902 started the biennial report period. |
| |
| On January 1, 2002 at 0919, a rescued sea turtle was identified as a green |
| sea turtle. This is the 62nd rescue of a live sea turtle at Crystal River |
| Unit 3 (CR-3) in this biennial period. Notification to the National Marine |
| Fisheries Service and the Florida Fish and Wildlife Conservation Commission. |
| |
| |
| The licensee intends to notify the NRC Resident Inspector. |
| |
| * * * UPDATE ON 1/05/02 @ 1002 BY RAWLS TO GOULD * * * |
| |
| On January 5, 2002, at 0720, a rescued sea turtle was identified as a |
| Loggerhead Sea Turtle. This is the 63rd rescue of a live sea turtle at |
| Crystal River Unit 3 (CR3) in this biennial period. This is reportable as a |
| 4-hour report under 10 CFR 50.72(b)(2)(xi) as this event is related to the |
| protection of the environment for which a notification to other government |
| agencies (National Marine Fisheries Service and Florida Fish and Wildlife |
| Conservation Commission) has been or will be made. |
| |
| The NRC Resident Inspector was notified. |
| |
| Reg 2 RDO (Decker) was notified. |
| |
| * * * UPDATE ON 01/09/02 @ 1107 EST BY ANDY BARNES TAKEN BY MACKINNON * * * |
| |
| On January 9, 2002, at 0838, a rescued sea turtle was identified as a Kemp's |
| Ridley Sea Turtle. This is the 64th rescue of a live turtle at Crystal River |
| Unit 3 (CR-3) in this biennial period. This is reportable as a 4-hour 10 CFR |
| 50.72(b)(2)(xi) as this event is related to the protection of the |
| environment for which a notification to other government agencies (National |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation |
| Commission) has been or will be made. |
| |
| The NRC Resident Inspector was notified. |
| |
| Reg 2 (Brian Bonser) was notified. |
| |
| * * * UPDATE ON 02/17/02 at 0940 EST BY RICKY RAWLS TO FANGIE JONES * * * |
| |
| "On February 17, 2002 at 0820, a rescued injured sea turtle was identified |
| as a Kemp's Ridley Sea Turtle. The injury will require transportation to |
| Clearwater Marine Science Center or Florida Fish and Wildlife Conservation |
| Refuge. The Injury appears to be from a boat propeller. This is the 65th |
| rescue of a live sea turtle at Crystal River Unit 3 (CR-3) in this biennial |
| period. This is Reportable as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi) |
| as this event is related to the protection of the environment for which a |
| notification to other government agencies (National Marine Fisheries Service |
| and Florida Fish and Wildlife Conservation Commission) has been or will be |
| made. This Is an update to event 38602." |
| |
| The NRC Resident Inspector will be notified. R2DO (Stephen Cahill) has been |
| notified. |
| |
| * * * UPDATE ON 03/01/02 AT 1122 EST BY RICKY RAWLS TO GERRY WAIG * * * |
| |
| "On March 1, 2002 at 0952, a healthy rescued sea turtle was identified as a |
| Green Sea Turtle. This is the 66th rescue of a live sea turtle at Crystal |
| River Unit 3 (CR-3) in this biennial period. This is Reportable as a 4-Hour |
| Report under 10 CFR 50.72(b)(2)(xi) as this event is related to the |
| protection of the environment for which a notification to other government |
| agencies (National Marine Fisheries Service and Florida Fish and Wildlife |
| Conservation Commission) has been or will be made. This is an update to |
| event 38602." |
| |
| The NRC Resident Inspector was notified. R2DO (Julian) was notified. |
| |
| * * * UPDATE ON 03/07/02 AT 1114 EST BY CHUCK MORRIS TO MIKE NORRIS * * * |
| |
| "On March 7, 2002 at 0835, two healthy sea turtles rescued at CR#3 were |
| identified as Green Sea Turtles. These are the 67th and 68th live sea turtle |
| rescues at the Crystal River Energy Complex in this biennial period. This is |
| Reportable as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi) as this event is |
| related to the protection of the environment for which a notification to |
| other government agencies (National Marine Fisheries Service and Florida |
| Fish and Wildlife Conservation Commission) has been or will be made. This is |
| an update to event 38602." |
| |
| The NRC Resident Inspector was notified. R2DO (Henson) was notified. |
| |
| * * * UPDATE ON 04/02/02 at 0408 EST BY RICKY RAWLS TO FANGIE JONES * * * |
| |
| "On April 2, 2002 at 0236, two sea turtles previously rescued at CR#3 intake |
| area were identified by FPC Mariculture staff as Kemp Ridley Sea Turtles. |
| One of the turtles appears to be in distress and may require transportation |
| to Clearwater Marine Science Center of Florida Fish and Wildlife |
| Conservation Refuge. These are the 69th and 70th live sea turtle rescues at |
| the Crystal River Energy Complex in this biennial period. This is Reportable |
| as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi) as this event is related to |
| the protection of the environment for which a notification to other |
| government agencies (National Marine Fisheries Service and Florida Fish and |
| Wildlife Conservation Commission) has been or will be made. This is an |
| update to event 38602." |
| |
| The NRC Resident Inspector will be notified. The R2DO (Carolyn Evans) was |
| notified. |
| |
| ***** UPDATE AT 1023 EDT ON 05/19/02 FROM PELLERIN TO LEIGH TROCINE ***** |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "On May 19, 2002, at 0916, a sea turtle previously rescued at CR#3 intake |
| area was identified by FPC Mariculture staff as Green Sea Turtle. This is |
| the 71st live sea turtle rescue at the Crystal River Energy Complex in this |
| biennial period. This is Reportable as a 4-Hour Report under 10 CFR |
| 50.72(b)(2)(xi) as this event is related to the protection of the |
| environment for which a notification to other government agencies (National |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation |
| Commission) has been or will be made. This is an update to event 38602." |
| |
| The licensee plans to notify the National Marine Fisheries Service and |
| Florida Fish and Wildlife Conservation Commission and the NRC resident |
| inspector. The NRC operations officer notified the R2DO (Paul |
| Fredrickson). |
| |
| * * * UPDATE 1816 EDT ON 5/28/02 FROM BERRY FOSTER TO S. SANDIN * * * |
| |
| "On May 28, 2002 at 1700, a sea turtle previously rescued at CR#3 intake |
| area was identified by FPC Mariculture staff as a Green Sea Turtle. This is |
| the 72nd live sea turtle rescue at the Crystal River Energy Complex in this |
| biennial period. The turtle is being transported to the Clearwater Marine |
| Science Center. This is Reportable as a 4-Hour Report under 10 CFR 50.72 (b) |
| (2) (xi) as this event is related to the protection of the environment for |
| which a notification to other government agencies (National Marine Fisheries |
| Service and Florida Fish and Wildlife Conservation Commission) has been or |
| will be made. This is an update to event 38602." |
| |
| The licensee will inform the NRC Resident Inspector. Notified |
| R2DO(Landis). |
| |
| * * * UPDATE 1602 EDT ON 5/31/02 FROM BILL BANDHAUER TO MIKE NORRIS * * * |
| |
| "On May 30, 2002 at 1323, a sea turtle previously rescued at CR#3 intake |
| area was identified by FPC Mariculture staff as a Kemp's Ridley Sea Turtle. |
| This is the 72nd live sea turtle rescue at the Crystal River Energy Complex |
| in this biennial period. (Note: The sequential numbering of the live sea |
| turtle takes has been modified to reflect the actual live sea turtle takes, |
| On 4/02/02, a live rescue of two turtles was reported, however, one of the |
| turtles died and was reclassified as a non-causal mortality, which is |
| non-reportable). This event is Reportable as a 4-Hour Report under 10 CFR |
| 50.72(b) (2) (xi) as this event is related to the protection of the |
| environment for which a notification to other government agencies (National |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation |
| Commission) has been or will be made. This is an update to event 38602." |
| |
| The NRC Resident Inspector has been notified. Notified R2DO (Landis). |
| |
| *****UPDATE AT 13:58 EDT ON 7/18/02 FROM SWEENEY TO LAURA***** |
| |
| An offsite notification to the State regarding a green sea turtle that was |
| rescued from the CR#3 intake area by the FPC Mariculture staff. |
| |
| The NRC resident inspector was notified. Notified R2DO (C. Payne). |
| |
| * * * UPDATE 1126 EDT ON 8/1/02 FROM BILL BANDHAUER TO FANGIE JONES * * * |
| |
| "At 0915 on August 1,2002, a dead sea turtle recovered at the CR#3 intake |
| area was identified by FPC Mariculture staff as a Kemps Ridley Turtle. FPC |
| determined that the cause of death was non-causally related to the operation |
| of CR3. This is the 7th dead Kemps Ridley Turtle recovery at the Crystal |
| River Energy Complex in this biennial period. The threshold for reporting |
| non-causal sea turtle deaths is 6 in a biennial period. This event is |
| Reportable as a 4-Hour Report under 10 CFR 50.72 (b) (2) (xi) as this event |
| is related to the protection of the environment for which a notification to |
| other government agencies (National Marine Fisheries Service and Florida |
| Fish and Wildlife Conservation Commission) will be made. This is an update |
| to event 38602." |
| |
| The licensee intends to notify the NRC Resident Inspector. The R2DO (Mike |
| Ernstes) has been notified. |
| |
| * * * UPDATE 1529 EDT ON 8/8/02 FROM DAN DeBOER TO GERRY WAIG * * * |
| |
| "At 1234 on August 8, 2002, FPC determined that the dead Kemps-Ridley sea |
| turtle recovered at 1930 on May 11, 2002, at the Crystal River Unit 3 intake |
| area was reportable as a 4-Hour Report under 10 CFR 50.72 (b) (2) (xi). This |
| event is related to the protection of the environment for which a |
| notification to other government agencies (National Marine Fisheries Service |
| and Florida Fish and Wildlife Conservation Commission) has been made. At |
| 1347 on May 13, 2002 the FPC Mariculture Center determined that the cause of |
| death was non-causally related to the operation of Crystal River Unit 3. |
| This was the 6th non-causal dead turtle recovery at the Crystal River Energy |
| Complex in this biennial period. The threshold for reporting non-causal sea |
| turtle deaths is 6 in a biennial period. This is an update to event 38602." |
| |
| The licensee notified the NRC Resident Inspector. The R2DO (Claude Julian) |
| has been notified. |
| |
| ***UPDATE 11:10 EDT ON 8/20/02 FROM McCallum to LAURA*** |
| |
| "On August 20, 2002 at 0932, a sea turtle previously rescued at CR#3 intake |
| area was identified by FPC Mariculture staff as a Kemp's Ridley Sea Turtle. |
| This is the 74th live sea turtle rescue at the Crystal River Energy Complex |
| in this biennial period. This event is Reportable as a 4-Hour Report under |
| 10 CFR 50.72(b) (2) (xi) as this event is related to the protection of the |
| environment for which a notification to other government agencies (National |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation |
| Commission) has been or will be made. This is an update to event 38602." |
| |
| The licensee notified the NRC Resident Inspector. The R2DO (M. LESSER) has |
| been notified. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 39134 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: MA RADIATION CONTROL PROGRAM |NOTIFICATION DATE:
08/16/2002|
|LICENSEE: BRISTOL-MYERS SQUIBB MEDICAL IMAGING |NOTIFICATION TIME:
11:02[EDT]|
| CITY: BILLERICA REGION: 1 |EVENT DATE: 08/14/2002|
| COUNTY: STATE: MA |EVENT TIME: [EDT]|
|LICENSE#: 60-0088 AGREEMENT: Y |LAST UPDATE DATE: 08/16/2002|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |GLENN MEYER R1 |
| |C.W. (BILL) REAMER NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: KENATH TRAEGDE | |
| HQ OPS OFFICER: FANGIE JONES | |
+------------------------------------------------+ |
|EMERGENCY CLASS: NON EMERGENCY | |
|10 CFR SECTION: | |
|NAGR AGREEMENT STATE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT - PERSONNEL OVER EXPOSURE |
| |
| "Cyclotron chemistry technician received 4.56 rem TEDE in one week. The |
| worker's exposure for the calendar year is now 5.79 rem. The cause of the |
| additional exposure is related to work performed directly with cyclotron |
| target material. This exposure was incurred over a period of one week. The |
| details of the event are under investigation." |
| |
| The exposure took place the week of July 28 to August 4, 2002. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39139 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: WOLF CREEK REGION: 4 |NOTIFICATION DATE: 08/20/2002|
| UNIT: [1] [] [] STATE: KS |NOTIFICATION TIME: 16:50[EDT]|
| RXTYPE: [1] W-4-LP |EVENT DATE: 08/20/2002|
+------------------------------------------------+EVENT TIME: 10:30[CDT]|
| NRC NOTIFIED BY: STEVEN A. HENRY |LAST UPDATE DATE: 08/20/2002|
| HQ OPS OFFICER: MIKE NORRIS +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |WILLIAM JOHNSON R4 |
|10 CFR SECTION: | |
|AUNA 50.72(b)(3)(ii)(B) UNANALYZED CONDITION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| UNANALYZED CONDITION FOR POST FIRE SAFE SHUTDOWN |
| |
| "On August 20, 2002, conditions were discovered where a postulated fire |
| could cause the loss of both Centrifugal Charging Pumps (CCP) capability to |
| successfully inject borated water to the reactor and to keep the Reactor |
| Coolant Pump (RCP) seals cool. Wolf Creek is in Mode 1, at 100% power. |
| |
| "During reviews associated with post fire safe shutdown reanalysis work, |
| Wolf Creek personnel discovered that power and control cables for both CCP |
| train minimum flow valves, both train CCP discharge valves to the RCP seals, |
| and both train CCP suction valves from the Volume Control Tank (VCT) and |
| Refueling Water Storage Tank (RWST) are routed in electrical raceways in the |
| same fire area with intervening combustibles between the two redundant |
| trains. This does not meet our commitments to 10CFR50 Appendix R.lll.G as |
| reflected in our approved Fire Protection Plan. |
| |
| "Following a fire In the plant that requires a plant shutdown, the function |
| of the CCP is to inject borated water into the reactor to maintain reactor |
| water inventory, maintain shutdown reactivity margin, and to maintain a |
| cooling water flow to the RCP seals to prevent damage to the seals. A fire |
| in this fire area has the potential to cause the above-mentioned valves to |
| not function properly and cause a loss of the capability to borate, maintain |
| inventory, and to cool the RCP seals. |
| |
| "Based on the guidance provided in NUREG 1022, Revision 2, this situation |
| meets the criterion of 10CFR50.72(b)(3)(ii)(B) for an 8-hour ENS |
| notification, as it relates to being in an unanalyzed condition. |
| |
| "The licensee has previously implemented a 1-hour fire watch in this fire |
| area." |
| |
| The NRC Resident Inspector has been notified. |
+------------------------------------------------------------------------------+
Page Last Reviewed/Updated Wednesday, March 24, 2021