Event Notification Report for February 9, 2001

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           02/08/2001 - 02/09/2001

                              ** EVENT NUMBERS **

37727  37728  37729  

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37727       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SUSQUEHANNA              REGION:  1  |NOTIFICATION DATE: 02/08/2001|
|    UNIT:  [] [2] []                 STATE:  PA |NOTIFICATION TIME: 17:35[EST]|
|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        02/08/2001|
+------------------------------------------------+EVENT TIME:        14:47[EST]|
| NRC NOTIFIED BY:  ROLAND                       |LAST UPDATE DATE:  02/08/2001|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |RONALD BELLAMY       R1      |
|10 CFR SECTION:                                 |                             |
|ADEG 50.72(b)(1)(ii)     DEGRAD COND DURING OP  |                             |
|AINC 50.72(b)(2)(iii)(C) POT UNCNTRL RAD REL    |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| BOTH REACTOR RECIRCULATING SAMPLE LINE CONTAINMENT ISOLATION VALVES DECLARED |
| INOPERABLE                                                                   |
|                                                                              |
| During operation of Unit 2 at 100% power, it has been determined that both   |
| Primary Containment Isolation Valves for the Reactor Recirculating Sample    |
| Line are inoperable.  During restoration from maintenance activities on the  |
| line, the outboard isolation valve[HV243F020] failed to stroke closed.       |
| Following several attempts the valve was closed.  The valve was declared     |
| inoperable, and as required by Technical Specifications an attempt was made  |
| to close the inboard isolation valve[HV243F019].  The inboard valve also     |
| failed to close.  The air supply was isolated to the outboard valve to       |
| deactivate it, and the pathway was confirmed to be isolated.  The problem    |
| with the outboard valve is due to a bad solenoid.   The problem with the     |
| inboard valve is under investigation.  They were able to get both valves     |
| closed when the inboard valve finally closed on its own an hour later.       |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37728       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: COOK                     REGION:  3  |NOTIFICATION DATE: 02/08/2001|
|    UNIT:  [1] [] []                 STATE:  MI |NOTIFICATION TIME: 20:07[EST]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        02/08/2001|
+------------------------------------------------+EVENT TIME:        19:00[EST]|
| NRC NOTIFIED BY:  FOSTER                       |LAST UPDATE DATE:  02/08/2001|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |BRENT CLAYTON        R3      |
|10 CFR SECTION:                                 |TAD MARSH            NRR     |
|ASHU 50.72(b)(1)(i)(A)   PLANT S/D REQD BY TS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |60       Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| PLANT DECLARED SSPS(SOLID STATE PROTECTION SYSTEM) INOPERABLE                |
|                                                                              |
| Reactor shutdown was initiated at 1900 due to train "B" SSPS being declared  |
| inoperable.  Technical Specifications 3.3.1.1 and 3.3.2.1, which were        |
| entered at 1628, requires the Unit to be in hot standby within 6 hours.      |
| The problem was caused by a redundant power supply to the "B" train being    |
| declared inoperable, and an incorrect procedure.  Procedure changes are      |
| currently being developed to correct it.                                     |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
|                                                                              |
| * * * UPDATE ON 2/8/01 BY JOHNSON TO GOULD * * *                             |
|                                                                              |
| Procedural changes were complete at 2030 and power reduction was terminated  |
| at 58% and power was stabilized between 50 and 55 percent.  The plant will   |
| maintain that power level until feed pump repairs are complete(approx. 4-5   |
| hrs).                                                                        |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
|                                                                              |
| The Reg 3 RDO(Clayton) and NRR EO(Marsh) were informed.                      |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   37729       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  DRAPER ADEN ASSOCIATES               |NOTIFICATION DATE: 02/08/2001|
|LICENSEE:  DRAPER ADEN ASSOCIATES               |NOTIFICATION TIME: 23:09[EST]|
|    CITY:  RICHMOND                 REGION:  2  |EVENT DATE:        02/08/2001|
|  COUNTY:                            STATE:  VA |EVENT TIME:        21:00[EST]|
|LICENSE#:  45-25246-01           AGREEMENT:  N  |LAST UPDATE DATE:  02/08/2001|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |RONALD BELLAMY       R1      |
|                                                |PHILIP TING          NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  WEIFORD                      |                             |
|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NINF                     INFORMATION ONLY       |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| LOST TROXLER GAUGE                                                           |
|                                                                              |
| The licensee reported that a Troxler model 3411 serial #16727 (8.5           |
| millicuries Cs-137 and 40 millicuries Am-241 Be) fell out of the back of an  |
| employees truck between work and home (approx. 15 to 20 miles).  They made a |
| search of the route taken by the employee, but they did not find it.  The    |
| licensee notified the local police department.                               |
+------------------------------------------------------------------------------+
