Event Notification Report for December 10, 1999

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           12/09/1999 - 12/10/1999

                              ** EVENT NUMBERS **

35790  36455  36496  36497  

+------------------------------------------------------------------------------+
|Fuel Cycle Facility                              |Event Number:   35790       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PADUCAH GASEOUS DIFFUSION PLANT      |NOTIFICATION DATE: 06/03/1999|
|   RXTYPE: URANIUM ENRICHMENT FACILITY          |NOTIFICATION TIME: 14:44[EDT]|
| COMMENTS: 2 DEMOCRACY CENTER                   |EVENT DATE:        06/02/1999|
|           6903 ROCKLEDGE DRIVE                 |EVENT TIME:        16:30[CDT]|
|           BETHESDA, MD 20817    (301)564-3200  |LAST UPDATE DATE:  12/09/1999|
|    CITY:  PADUCAH                  REGION:  3  +-----------------------------+
|  COUNTY:  McCRACKEN                 STATE:  KY |PERSON          ORGANIZATION |
|LICENSE#:  GDP-1                 AGREEMENT:  Y  |DAVID HILLS          R3      |
|  DOCKET:  0707001                              |DON COOL             NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  THOMAS WHITE                 |                             |
|  HQ OPS OFFICER:  FANGIE JONES                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|OCBA 76.120(c)(2)(i)     ACCID MT EQUIP FAILS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| THREE SPRINKLER SYSTEMS DECLARED INOPERABLE DUE TO CORRODED HEADS (24-hour   |
| report)                                                                      |
|                                                                              |
| The following text is a portion of a facsimile received from Paducah:        |
|                                                                              |
| "On 06/02/99 at 1630 CDT, the Plant Shift Superintendent (PSS) was notified  |
| that numerous sprinkler heads were corroded, affecting 16 sprinkler systems  |
| in C-337 and one system in C-333, such that the ability of the sprinklers to |
| flow sufficient water was called into question.  Subsequently, these         |
| sprinkler systems were declared inoperable, and TSR-required actions         |
| establishing roving fire patrols were initiated.  This deficiency was        |
| detected during scheduled system inspections conducted by Fire Protection    |
| personnel.  Currently, functionality of the sprinkler heads has not been     |
| fully evaluated by Fire Protection personnel, and the remaining cascade      |
| buildings are currently being inspected, and if necessary, this report will  |
| be updated to identify any additional areas.  It has been determined that    |
| this event is reportable under 10CFR76.120(c)(2) as an event in which        |
| equipment is disabled or fails to function as designed."                     |
|                                                                              |
| The NRC resident inspector has been notified of this event by Paducah        |
| personnel.                                                                   |
|                                                                              |
| * * * UPDATE AT 1022 EDT ON 06/04/99 FROM CAGE TO TROCINE * * *              |
|                                                                              |
| The following text is a portion of a facsimile received from Paducah:        |
|                                                                              |
| "Two sprinkler heads on system D-1 in C-337 and two sprinkler heads on       |
| system 27 in C-335 were identified to also be corroded.  These were          |
| identified to the PSS on 06/03/99 at 1600 CDT and 1601 CDT, respectively,    |
| and determined to require an update to this report by the PSS.  It has been  |
| determined that this event is reportable under 10CFR76.120(c)(2) as an event |
| in which equipment is disabled or fails to function as designed."            |
|                                                                              |
| Paducah personnel notified the NRC resident inspector of this update.  The   |
| NRC operations officer notified the R3DO (Hills) and NMSS EO (Combs).        |
|                                                                              |
| * * * UPDATE AT 2152 EDT ON 06/17/99 FROM WALKER TO POERTNER * * *           |
|                                                                              |
| The following text is a portion of a facsimile received from Paducah:        |
|                                                                              |
| "Three sprinkler heads on system C-15 and five sprinkler heads on system B-8 |
| in C-333 were identified to also be corroded.  The PSS was notified of this  |
| condition at 1300 CDT on 06/17/99 and determined that an update to this      |
| report was required.  It has been determined that this event is reportable   |
| under 10CFR76.120(c)(2) as an event in which equipment is disabled or fails  |
| to function as designed."                                                    |
|                                                                              |
| Paducah personnel notified the NRC resident inspector of this update.  The   |
| NRC operations officer notified the R3DO (Madera).                           |
|                                                                              |
| * * * UPDATE AT 1440 EDT ON 06/18/99 FROM UNDERWOOD TAKEN BY STRANSKY * * *  |
|                                                                              |
| The following text is a portion of a facsimile received from Paducah:        |
|                                                                              |
| "Two sprinkler heads on system C-15 and one sprinkler head on system B-8 in  |
| C-333 were identified to have corrosion.  The PSS was notified of this       |
| condition at 1350 CDT on 06/18/99.  The area of the fire patrol for system   |
| C-15 was expanded to include the two heads identified as corroded.  The one  |
| head on system B-8 was in the area already being patrolled.  The PSS         |
| determined that an update to this report was required."                      |
|                                                                              |
| The NRC resident inspector has been informed of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Madera).           |
|                                                                              |
| * * * UPDATE AT 1315 EDT ON 06/25/1999 FROM WALKER TAKEN BY STRANSKY * * *   |
|                                                                              |
| The following text is a portion of a facsimile received from Paducah:        |
|                                                                              |
| "Two sprinkler heads on system D-8 and three sprinkler heads on system D-7   |
| in C-337 were identified to have corrosion.  The PSS was notified of the     |
| condition on system D-8 at 0125 CDT on 06/25/99 and at 1019 CDT on 06/25/99  |
| for system D-7.  Both systems were immediately declared inoperable and LCO   |
| fire patrol actions were implemented.  It was determined that an update to   |
| this report was required."                                                   |
|                                                                              |
| The NRC resident inspector has been informed of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Jordan).           |
|                                                                              |
| * * * UPDATE AT 2119 EDT ON 07/30/99 FROM CAGE TAKEN BY STRANSKY * * *       |
|                                                                              |
| The following text is a portion of a facsimile received from Paducah:        |
|                                                                              |
| "Five sprinkler heads and one sprinkler piping tee on C-337 system D-7 were  |
| identified to have corrosion. The PSS was notified of these corroded system  |
| parts and declared the system inoperable at 0931 CDT on 07/30/99.  LCO       |
| required fire patrols of the affected area were initiated.  The PSS          |
| determined that an update to this event report was required."                |
|                                                                              |
| The NRC resident inspector has been informed of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Wright).           |
|                                                                              |
| * * * UPDATE AT 1655 EDT ON 07/31/99 FROM WHITE TAKEN BY STRANSKY * * *      |
|                                                                              |
| The following text is a portion of a facsimile received from Paducah:        |
|                                                                              |
| "Two sprinkler heads on C-337 System D-1 were identified to have corrosion.  |
| The PSS was notified of these corroded system parts and declared the system  |
| inoperable at 1155 CDT on 7/31/99.  LCO required fire patrols of the         |
| affected area were initiated.  The PSS determined that an update to this     |
| report was required."                                                        |
|                                                                              |
| The NRC resident inspector has been informed of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Wright).           |
|                                                                              |
| * * * UPDATE AT 1546 EDT ON 08/10/99 FROM WHITE TAKEN BY STRANSKY * * *      |
|                                                                              |
| The following text is a portion of a facsimile received from Paducah:        |
|                                                                              |
| "Two sprinkler heads on C-337 system C-15 were identified to have corrosion. |
| The PSS was notified of these corroded system parts and declared the system  |
| inoperable at 1130 CDT on 8/10/99.  LCO required fire patrols of the         |
| affected area were initiated.  The PSS determined that an update to this     |
| report was required."                                                        |
|                                                                              |
| The NRC resident inspector has been informed of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Burgess).          |
|                                                                              |
| * * * UPDATE AT 1154 EDT ON 08/22/99 FROM WALKER TO POERTNER * * *           |
|                                                                              |
| Four adjacent sprinkler heads on the C-333 building System B-1 were          |
| identified to have corrosion.  The PSS was notified of the corroded system   |
| parts and declared the system inoperable at 0918 CDT on 08/22/99.  LCO       |
| required fire patrols were initiated.                                        |
|                                                                              |
| The NRC resident inspector will be notified by Paducah personnel.  The NRC   |
| operations officer notified the R3DO (Clayton).                              |
|                                                                              |
| * * * UPDATE AT 2015 EDT ON 08/28/99 FROM W. F. GAGE TO S. SANDIN * * *      |
|                                                                              |
| Two adjacent sprinkler heads on the C-337 building System D-11 were          |
| identified to have corrosion.  The PSS was notified of these corroded system |
| parts and declared the system inoperable at 1420 CDT on 08/28/99.   LCO      |
| required fire patrols of the affected area were initiated.                   |
|                                                                              |
| Paducah personnel informed the NRC resident inspector.  The NRC operations   |
| officer notified the R3DO (Leach) and NMSS EO (Piccone).                     |
|                                                                              |
| * * * UPDATE AT 2037 EDT ON 08/29/99 FROM KEVIN BEASLEY TO S. SANDIN * * *   |
|                                                                              |
| Two adjacent sprinkler heads on the C-337 building System D-15 were          |
| identified to have corrosion and the PSS declared the system inoperable at   |
| 0925 CDT on 08/29/99.  Also two adjacent heads on the C-337 building System  |
| D-10 were identified to have corrosion and the PSS declared the system       |
| inoperable at 1450 CDT.   LCO required fire patrols for both of the affected |
| areas were initiated in the time frame required by TSR.                      |
|                                                                              |
| Paducah personnel informed the NRC resident inspector.  The NRC operations   |
| officer notified the R3DO (Leach) and NMSS EO (Piccone).                     |
|                                                                              |
| * * * UPDATE AT 0930 EDT ON 09/01/99  FROM ERIC WALKER TO FANGIE JONES * *   |
| *                                                                            |
|                                                                              |
| Add two adjacent sprinkler heads on the C-337 building System D-14 were      |
| declared inoperable.                                                         |
|                                                                              |
| Paducah personnel informed the NRC resident inspector.  The NRC operations   |
| officer notified the R3DO (David Hills) and NMSS EO (Robert Pierson).        |
|                                                                              |
| * * * UPDATE AT 1133 EDT ON 09/08/99  FROM TOM WHITE TO FANGIE JONES * * *   |
|                                                                              |
| Add two adjacent sprinkler heads on the C-331 building System 26 were        |
| declared inoperable at 2155 CDT on 09/07/99.  An LCO required fire patrol    |
| for the affected area was initiated in the time frame required by the TSR.   |
|                                                                              |
| Paducah personnel informed the NRC resident inspector.  The NRC operations   |
| officer notified the R3DO (Monte Phillips) and NMSS EO (Josie Piccone).      |
|                                                                              |
| * * * UPDATE AT 0948 ON 09/30/99 FROM ERIC WALKER TO DOUG WEAVER * * *       |
|                                                                              |
| Add two adjacent sprinkler heads on the C-333 building System B-15 were      |
| identified to have corrosion and the PSS declared the system inoperable at   |
| 0815 CDT on 9/30/99.  An LCO required fire patrol for the affected area was  |
| initiated in the time frame required by the TSR.                             |
|                                                                              |
| Paducah personnel informed the NRC resident inspector.   The NRC operations  |
| officer notified the R3DO (Vegel) and NMSS EO (Cool).                        |
|                                                                              |
| * * * UPDATE AT 1600 ON 10/13/99 FROM WALKER TO GOULD * * *                  |
|                                                                              |
| Two adjacent sprinkler heads on the C-333 building System A-11 were          |
| identified to have corrosion and the PSS declared the system inoperable at   |
| 1307 CDT on 10/13/99.  An LCO required fire patrol for the affected area was |
| initiated in the time frame required by the TSR.                             |
|                                                                              |
| Paducah personnel informed the NRC resident inspector.   The NRC operations  |
| officer notified the R3DO (Madera) and NMSS EO (Moore).                      |
|                                                                              |
| * * * UPDATE AT 1520 ON 10/19/99 FROM UNDERWOOD TAKEN BY STRANSKY * * *      |
|                                                                              |
| Six sprinkler heads on the C-337 building System D-16 were identified to     |
| have corrosion and the PSS declared the system inoperable at 1052 CDT on     |
| 10/19/99.  An LCO required fire patrol for the affected area was initiated   |
| in the time frame required by the TSR.                                       |
|                                                                              |
| The NRC resident inspector has been informed of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Jorgensen).        |
|                                                                              |
| * * * UPDATE AT 2140 ON 10/19/99 FROM WALKER TAKEN BY STRANSKY * * *         |
|                                                                              |
| Seven sprinkler heads on the C-337 building System A-7 were identified to    |
| have corrosion, and another four had been painted over.  In addition, three  |
| adjacent sprinkler heads on the C-337 building System A-8 were identified to |
| have corrosion.  The PSS declared the systems inoperable at 1900 CDT on      |
| 10/19/99.  An LCO required fire patrols for the affected areas were          |
| initiated in the time frame required by the TSR.                             |
|                                                                              |
| The NRC resident inspector has been informed of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Wright).           |
|                                                                              |
| * * * UPDATE AT 1713 ON 10/21/99 FROM CAGE TAKEN BY JOLLIFFE * * *           |
|                                                                              |
| Four sprinkler heads on the C-337 building System A-5, twelve sprinkler      |
| heads on the C-337 building System A-8, three sprinkler heads on the C-337   |
| building System A-9, and six sprinkler heads on the C-337 building System    |
| B-8 were identified to have corrosion.  On 10/21/99, the PSS declared        |
| Systems A-5 and A-9 inoperable at 1028 CDT, System A-8 inoperable at 1227    |
| CDT and System B-8 inoperable at 1406 CDT.   An LCO required fire patrol for |
| the affected areas was initiated in the time frame required by the TSR.      |
|                                                                              |
| The NRC resident inspector has been informed of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Bruce Jorgensen).  |
|                                                                              |
| * * * UPDATE AT 2128 ON 10/22/99 FROM ERIC WALKER TAKEN BY JOLLIFFE * * *    |
|                                                                              |
| At 1400 CDT on 10/22/99, the PSS was notified that numerous corroded         |
| sprinkler heads were discovered in the C-337 building on sprinkler systems   |
| B-1, B-3, B-5, B-6, B-7, B-11, and D-17.  Due to the number of systems       |
| called into question, the PSS declared all of the sprinkler systems in C-337 |
| on the cell floor (a total of 66 systems) inoperable and TSR required        |
| actions establishing roving fire patrols were initiated within the required  |
| time frame.                                                                  |
|                                                                              |
| The NRC resident inspector has been informed of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Bruce Jorgensen).  |
|                                                                              |
| * * * UPDATE AT 1239 ON 10/24/99 FROM TOM WHITE TAKEN BY JOLLIFFE * * *      |
|                                                                              |
| At 1200 CDT on 10/23/99, the PSS was notified that numerous corroded         |
| sprinkler heads were discovered in the C-337 building on sprinkler systems   |
| B-13 and B-14 on the ground floor,  The PSS declared these systems           |
| inoperable and TSR required actions establishing roving fire patrols were    |
| initiated within the required time frame.  At 1600 CDT on 10/23/99, the PSS  |
| was notified that numerous corroded sprinkler heads were discovered in the   |
| C-337 building on sprinkler systems A-16, B-12, C-8, C-12, C-15, D-5, and    |
| D-8 on the cell floor,  These systems have already been declared inoperable  |
| and fire patrols are already being performed.                                |
|                                                                              |
| The NRC resident inspector has been notified of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Bruce Jorgensen).  |
|                                                                              |
| * * * UPDATE AT 1117 ON 10/25/99 FROM W. F. CAGE TAKEN BY SANDIN * * *       |
|                                                                              |
| At 1940 CDT on 10/24/99, the PSS was notified that numerous corroded         |
| sprinkler heads had been discovered on High Pressure Fire Water Systems C-4, |
| C-5, C-6 and C-8, located in the C-337 building.  These systems had          |
| previously been declared inoperable and fire patrols were already being      |
| performed at the time of discovery.                                          |
|                                                                              |
| The NRC resident inspector has been notified of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Lanksbury) and     |
| NMSS EO (Brain Smith).                                                       |
|                                                                              |
| * * * UPDATE AT 2235 ON 10/27/99 FROM WHITE TAKEN BY MACKINNON * * *         |
|                                                                              |
| At 1517 CDT on 10/27/99, the PSS was notified that nine corroded sprinkler   |
| heads had been discovered on High Pressure Fire Water System A-12 located in |
| the C-333 building.  This system has been declared inoperable and fire       |
| patrols have been initiated.                                                 |
|                                                                              |
| The NRC resident inspector has been notified of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Jordan) and NMSS   |
| EO (Hickey).                                                                 |
|                                                                              |
| * * * UPDATE AT 2150 ON 10/30/99 FROM UNDERWOOD TAKEN BY WEAVER * * *        |
|                                                                              |
| At 1950 CDT on 10/30/99, the PSS was notified that numerous corroded         |
| sprinkler heads had been discovered on High Pressure Fire Water Systems A-5, |
| A-9, A-11, C-5, and C-7 in the C-333 building.  Reference ATR-1 1999-6699    |
| and 6702.  These systems have been declared inoperable and fire patrols have |
| been initiated.  Also, due to the number of inoperable sprinkler heads, the  |
| remaining systems on the cell floor of C-333 were called into question and   |
| declared inoperable.  Fire patrols for the entire cell floor have been       |
| initialed.  The PSS determined that an update to this report was required.   |
|                                                                              |
| The NRC resident inspector has been notified of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Jordan) and NMSS   |
| EO (Hickey).                                                                 |
|                                                                              |
| * * * UPDATE AT 2111 ON 10/31/99 FROM UNDERWOOD TAKEN BY WEAVER * * *        |
|                                                                              |
| At 1412 CDT on 10/31/99, the PSS was notified that five corroded sprinkler   |
| heads had been discovered on High Pressure Fire Water System 9 in the C-335  |
| building.  There were two adjacent corroded heads discovered in two separate |
| locations and a third individual head at a different location.  The system   |
| was declared inoperable and fire patrols were initiated.  The corroded heads |
| have since been replaced and the system returned to operable status.         |
|                                                                              |
| The NRC resident inspector was notified of this update by Paducah personnel. |
| The NRC operations officer notified the R3DO (Jordan) and NMSS EO (Hickey).  |
|                                                                              |
| * * * UPDATE AT 2121 ON 11/01/99 FROM KEVIN BEASLEY TAKEN BY JOLLIFFE * * *  |
|                                                                              |
|                                                                              |
| At 0930 CST on 11/01/99, the PSS was notified that three corroded sprinkler  |
| heads had been discovered on the High Pressure Fire Water System B-4 in the  |
| C-337 building.  Two of these sprinkler heads are adjacent.  Two adjacent    |
| corroded sprinkler heads were also discovered on the High Pressure Fire      |
| Water System B-5 in the C-337 building.  These systems were declared         |
| inoperable and fire patrols were initiated.  Work has been initiated to      |
| replace the corroded heads.                                                  |
|                                                                              |
| The NRC resident inspector has been notified of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Jim Creed).        |
|                                                                              |
| * * * UPDATE AT 2143 ON 11/02/99 FROM KEVIN BEASLEY TAKEN BY JOLLIFFE * * *  |
|                                                                              |
|                                                                              |
| At 1400 CST on 11/02/99, the PSS was notified that numerous corroded         |
| sprinkler heads had been discovered on High Pressure Fire Water Systems C-8  |
| and D-7 in the C-333 building.  These systems had been previously declared   |
| inoperable and fire patrols were being performed at the time of discovery.   |
| Work has been initiated to replace the corroded heads.                       |
|                                                                              |
| The NRC resident inspector has been notified of this update by Paducah       |
| personnel.  The NRC operations officer notified the R3DO (Jim Creed).        |
|                                                                              |
| * * * UPDATE AT 2110 EST ON 11/04/99 FROM ERIC WALKER TO S. SANDIN * * *     |
|                                                                              |
| The following text is a portion of a facsimile received from Paducah:        |
|                                                                              |
| "At 1700 [CST] on 11/04/99, the [PSS] was notified that numerous corroded    |
| sprinkler heads had been discovered on High Pressure Fire Water systems      |
| A-16, C-17, D-12, and D-16 in the C-333 building.  These systems had been    |
| previously declared inoperable, and fire patrols were being performed at the |
| time of discovery.  Work his been initiated to replace the corroded heads.   |
| The PSS determined that an update to this report was required."              |
|                                                                              |
| "It has been determined that this event is reportable under                  |
| 10CFR76.120(c)(2) as an event in which equipment is disabled or fails to     |
| function as designed."                                                       |
|                                                                              |
| The NRC senior resident inspector has been notified of this event by Paducah |
| personnel.  The NRC operations officer notified the R3DO (Creed) and NMSS EO |
| (Hodges).                                                                    |
|                                                                              |
| * * * UPDATE AT 2328 EST ON 11/23/99 FROM WHITE TAKEN BY MACKINNON * * *     |
|                                                                              |
| At 2240 CST on 11/22/99, the PSS was notified that numerous corroded         |
| sprinkler heads had been discovered on High Pressure Fire Water System B-7   |
| and B-8 in the C-337 building.  These systems were declared inoperable, and  |
| fire patrols were initiated at the time of discovery.  The PSS determined    |
| that an update to this report was required.                                  |
|                                                                              |
| The NRC resident inspector was notified of this update by the certificate    |
| holder.  The R3DO (Ron Gardner) and NMSS EO (Joe Holonich) were notified by  |
| the NRC operations officer.                                                  |
|                                                                              |
| ******************** UPDATE AT 1017 ON 11/24/99 FROM ERIC WALKER TO LEIGH    |
| TROCINE ********************                                                 |
|                                                                              |
| The following text is a portion of a facsimile received from Paducah:        |
|                                                                              |
| "At 1045 [CST] on 11/23/99, the [PSS] was notified that more than five       |
| corroded sprinkler heads per system had been discovered on both High         |
| Pressure Fire Water systems B-3 and 8-4 in the C-337 building.  Per the      |
| Authority Having Jurisdiction (AHJ), the discovery of five or more heads on  |
| one system renders the system inoperable.  These systems were declared       |
| inoperable, and actions were taken as required by the TSR.  The PSS          |
| determined that an update to this report was required."                      |
|                                                                              |
| "It has been determined that this event is reportable under                  |
| 10CFR76.120(c)(2) as an event in which equipment is disabled or fails to     |
| function as designed."                                                       |
|                                                                              |
| Paducah personnel notified the NRC resident inspector.  The R3DO (Gardner)   |
| and NMSS EO (Hickey) were notified by the NRC operations officer.            |
|                                                                              |
| ***************** UPDATE AT 2147 ON 12/08/99 FROM MIKE UNDERWOOD TO LEIGH    |
| TROCINE ****************                                                     |
|                                                                              |
| The following text is a portion of a facsimile received from Paducah:        |
|                                                                              |
| "At 1000 [CST] on 12/08/99, the [PSS] was notified that five corroded        |
| sprinkler heads had been discovered on High Pressure Fire Water system B-1   |
| in the C-337 building.  Two heads are at column Y-X/4, two heads at column   |
| Wb-4, and one head at column Wa-4 on the ground floor.  Per the Authority    |
| Having Jurisdiction (AHJ), the discovery of five or more heads on the system |
| renders the system inoperable.  The system was declared inoperable, and      |
| actions were taken by the TSR.  The PSS determined that an update to this    |
| required."                                                                   |
|                                                                              |
| "It has been determined that this event is reportable under                  |
| 10CFR76.120(c)(2) as an event in which equipment is disabled or fails to     |
| function as designed."                                                       |
|                                                                              |
| Paducah personnel notified the NRC resident inspector.  The R3DO (Hiland)    |
| and NMSS EO (Sherr) were notified by the NRC operations officer.             |
|                                                                              |
| * * * UPDATE AT 2315 ON 12/09/99 FROM TOM WHITE TAKEN BY JOLLIFFE * * *      |
|                                                                              |
| At 1405 CST on 12/09/99, the PSS was notified that twelve (12) corroded      |
| sprinkler heads had been discovered on High Pressure Fire Water System #B-1  |
| in the C-337 building. Two heads are at column X-6, three heads at column    |
| Wb-3, four heads at column Wa-5, one head at column Wb-8, one head at column |
| X-6, and one head at column W4, all on the ground floor.  Per the Authority  |
| Having Jurisdiction, the discovery of five or more heads on one system       |
| renders the system inoperable and three locations have two adjacent heads    |
| corroded and this renders the system inoperable as well.  The system was     |
| declared inoperable and actions were taken as required by the technical      |
| safety requirement. The PSS determined that an update to this report was     |
| required.                                                                    |
|                                                                              |
| The NRC Resident lnspector has been notified of this event.                  |
|                                                                              |
| The NRC Operations Officer notified the R3DO Pat Hiland.                     |
+------------------------------------------------------------------------------+

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Fuel Cycle Facility                              |Event Number:   36455       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PORTSMOUTH GASEOUS DIFFUSION PLANT   |NOTIFICATION DATE: 11/20/1999|
|   RXTYPE: URANIUM ENRICHMENT FACILITY          |NOTIFICATION TIME: 09:47[EST]|
| COMMENTS: 2 DEMOCRACY CENTER                   |EVENT DATE:        11/19/1999|
|           6903 ROCKLEDGE DRIVE                 |EVENT TIME:        16:00[EST]|
|           BETHESDA, MD 20817    (301)564-3200  |LAST UPDATE DATE:  12/09/1999|
|    CITY:  PIKETON                  REGION:  3  +-----------------------------+
|  COUNTY:  PIKE                      STATE:  OH |PERSON          ORGANIZATION |
|LICENSE#:  GDP-2                 AGREEMENT:  N  |THOMAS KOZAK         R3      |
|  DOCKET:  0707002                              |JOSEPHINE PICCONE    NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  JIM MCCLEERY                 |                             |
|  HQ OPS OFFICER:  FANGIE JONES                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NONR                     OTHER UNSPEC REQMNT    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 24 HOUR REPORT - VALID SAFETY SYSTEM ALARM                                   |
|                                                                              |
| "ON 11/19/99 AT 1600,  X-326 CASCADE BUILDING OPERATIONS RECEIVED A SMOKE    |
| HEAD ALARM ACTUATION AT THE ERP 1A WITHDRAWAL STATION DURING A CYLINDER      |
| CONNECTION EVOLUTION.  WHILE CONNECTING THE PIGTAIL TO THE CYLINDER, A       |
| SLIGHT WISP OF UF6 SMOKE APPEARED BETWEEN THE PIGTAIL AND THE MANIFOLD       |
| SAFETY VALVE.  EMERGENCY RESPONSE PERSONNEL RESPONDED AND MONITORED THE      |
| AREA.  ALL AIR SAMPLE RESULTS FOR HYDROGEN FLUORIDE AND UF6 WERE BELOW       |
| DETECTABLE LEVELS.  THIS EVENT IS REPORTABLE DUE TO THE VALID ACTUATION OF A |
| "Q" SAFETY SYSTEM.  THERE WAS NO LOSS OF HAZARDOUS/RADIOACTIVE MATERIAL OR   |
| RADIOACTIVE/RADIOLOGICAL CONTAMINATION EXPOSURE AS A RESULT OF THIS EVENT."  |
|                                                                              |
| THE LICENSEE NOTIFIED THE NRC RESIDENT INSPECTOR AND THE DOE SITE            |
| REPRESENTATIVE.                                                              |
|                                                                              |
| * * * UPDATE AT 1600 ON 12/09/99 BY ERIC SPATH TO JOLLIFFE * * *             |
|                                                                              |
| PORTSMOUTH PERSONNEL DESIRE TO RETRACT THIS EVENT BASED ON THE DETERMINATION |
| THAT THE ACTUAL PLANT CONDITIONS WHICH THE SAFETY SYSTEM IS DESIGNED TO      |
| PROTECT AGAINST DID NOT EXIST.  THE 1A WITHDRAWAL POSITION PIGTAIL WAS       |
| ISOLATED FROM THE LIQUID UF6 SYSTEM BY A CLOSED MANIFOLD VALVE AND NO LIQUID |
| UF6 WAS INVOLVED IN THE OUT GASSING.  A WITHDRAWAL WAS TAKING PLACE AT THE   |
| ADJACENT 1B POSITION, WHICH SHARES THE SAME COMPRESSORS, PIPING, AND         |
| ACCUMULATOR, BUT THE LEAK WAS NOT ASSOCIATED WITH THIS POSITION.  THE TECH   |
| SPEC REQUIREMENT BASIS STATEMENT INDICATES THAT THE PURPOSE OF THE PIGTAIL   |
| LINE ISOLATION SYSTEM IS TO MINIMIZE A RELEASE OF LIQUID UF6 DUE TO A        |
| PIGTAIL FAILURE DURING A WITHDRAWAL.  SINCE THE PIGTAIL WAS ISOLATED FROM    |
| THE LIQUID UF6 SYSTEM WHILE THE CYLINDER WAS BEING CONNECTED, THE PIGTAIL    |
| LINE ISOLATION SYSTEM SAFETY FUNCTION WAS NOT REQUIRED.                      |
|                                                                              |
| PORTSMOUTH PERSONNEL NOTIFIED THE NRC RESIDENT INSPECTOR.  THE NRC           |
| OPERATIONS OFFICER NOTIFIED THE R3DO PAT HILAND AND THE NMSS EO TED SHERR.   |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36496       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SOUTH TEXAS              REGION:  4  |NOTIFICATION DATE: 12/09/1999|
|    UNIT:  [1] [] []                 STATE:  TX |NOTIFICATION TIME: 12:46[EST]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        12/09/1999|
+------------------------------------------------+EVENT TIME:        11:25[CST]|
| NRC NOTIFIED BY:  HOWARD ALLGEYER              |LAST UPDATE DATE:  12/09/1999|
|  HQ OPS OFFICER:  DICK JOLLIFFE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |BILL JOHNSON         R4      |
|10 CFR SECTION:                                 |                             |
|DDDD 73.71               UNSPECIFIED PARAGRAPH  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| - SECURITY REPORT -                                                          |
|                                                                              |
| UNESCORTED ACCESS GRANTED TO A CONTRACTOR INAPPROPRIATELY.  COMPENSATORY     |
| MEASURES IMMEDIATELY TAKEN UPON DISCOVERY.  CORRECTIVE ACTIONS BEING         |
| DETERMINED.  THE LICENSEE PLANS TO NOTIFY THE NRC RESIDENT INSPECTOR.        |
| CONTACT THE NRC OPERATIONS OFFICER FOR ADDITIONAL DETAILS.                   |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36497       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FITZPATRICK              REGION:  1  |NOTIFICATION DATE: 12/09/1999|
|    UNIT:  [1] [] []                 STATE:  NY |NOTIFICATION TIME: 22:54[EST]|
|   RXTYPE: [1] GE-4                             |EVENT DATE:        12/09/1999|
+------------------------------------------------+EVENT TIME:        22:30[EST]|
| NRC NOTIFIED BY:  MARK ABRANSKI                |LAST UPDATE DATE:  12/09/1999|
|  HQ OPS OFFICER:  DICK JOLLIFFE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |CLIFFORD ANDERSON    R1      |
|10 CFR SECTION:                                 |                             |
|ASHU 50.72(b)(1)(i)(A)   PLANT S/D REQD BY TS   |                             |
|AOUT 50.72(b)(1)(ii)(B)  OUTSIDE DESIGN BASIS   |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| -TECH SPEC REQD PLANT SHUTDOWN DUE TO INCORRECT FLOW BIASED APRM SCRAM       |
| SETPOINTS-                                                                   |
|                                                                              |
| Engineering analysis based on in-situ plant data identified a discrepancy in |
| the 100% drive flow value used to develop the flow biased APRM scram         |
| setpoints specified in the core operating limits report.  The discrepancy is |
| such that the flow biased scram line on the power-to-flow map has a greater  |
| slope than specified in the core operating limits report. This condition     |
| results in a non-conservative APRM scram setpoint at lower core flows. The   |
| APRM scram function (Tech Spec Table 3.1-1) is considered inoperable until   |
| this condition can be corrected.  Tech Specs require that all operable       |
| control rods be inserted within 4 hours or reduce power to IRM range and     |
| place the mode switch in startup within 8 hours.  New APRM gain values are   |
| being established which will correct this discrepancy.                       |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Wednesday, March 24, 2021