Fire Endurance Test Acceptance Criteria for Fire Barrier Systems Used to Separate Redundant Safe Shutdown Trains Within the Same Fire Area (Supplement 1 to Generic Letter 86-10)
March 25, 1994 TO: ALL HOLDERS OF OPERATING LICENSES OR CONSTRUCTION PERMITS FOR NUCLEAR POWER REACTORS SUBJECT: FIRE ENDURANCE TEST ACCEPTANCE CRITERIA FOR FIRE BARRIER SYSTEMS USED TO SEPARATE REDUNDANT SAFE SHUTDOWN TRAINS WITHIN THE SAME FIRE AREA (SUPPLEMENT 1 TO GENERIC LETTER 86-10, "IMPLEMENTATION OF FIRE PROTECTION REQUIREMENTS") PURPOSE The U.S. Nuclear Regulatory Commission (NRC) is issuing Supplement 1 to Generic Letter (GL) 86-10, "Implementation of Fire Protection Requirements," April 24, 1986, to disseminate the review guidance contained in Enclosure 1, "Fire Endurance Test Acceptance Criteria for Fire Barriers Used to Separate Redundant Safe Shutdown Trains Within the Same Fire Area." This guidance will be used by the staff to review and evaluate the adequacy of fire endurance tests and fire barrier systems proposed by licensees or applicants in the future to satisfy existing NRC fire protection rules and regulations. This guidance refines and clarifies the fire barrier testing acceptance criteria specified by GL 86-10, for application in that specific (future review) context. BACKGROUND On April 24, 1986, the NRC issued GL 86-10 in order to give the industry additional guidance on implementing NRC fire protection requirements. The guidance in GL 86-10 did not change the requirement to separate one safe shutdown train from its redundant train with either a 1-hour or a 3-hour fire rated barrier. In Enclosure 2 to GL 86-10, the NRC staff responded to industry questions. Question 3.2.1 of the enclosure provided the staff position on fire endurance test acceptance criteria for fire barrier cable tray wraps. In its response, the staff stated that Chapter 7, "Tests of Nonbearing Walls and Partitions," of National Fire Protection Association (NFPA) Standard 251, "Standard Methods of Fire Tests of Building Construction," was applicable to cable-tray fire wraps. On July 30, 1991, the NRC established a special review team to identify and evaluate technical issues related to the Thermo-Lag 330-1 fire barrier system. On August 6, 1991, the NRC issued Information Notice (IN) 91-47, "Failure of Thermo-Lag Fire Barrier Material to Pass Fire Endurance Test." This IN gave licensees information on the fire endurance test performed by Gulf States Utilities Company on a Thermo-Lag 330-1 fire barrier installed on a wide aluminum cable tray and the associated fire test failure. On December 6, 1991, the NRC issued IN 91-79, "Deficiencies in the Procedures for Installing Thermo-Lag Fire Barrier Material," which gave information on deficiencies in procedures that the Thermo-Lag vendor (Thermal Science, Incorporated) provided for constructing Thermo-Lag 330-1 fire barriers. In 9403240197.response to concerns about the indeterminate qualifications of Thermo-Lag 330-1 fire barriers, on June 23, 1992, the NRC issued IN 92-46, "Thermo-Lag Fire Barrier Material Special Review Team Findings, Current Fire Endurance Tests, and Ampacity Calculation Errors." The staff found the following problems with Thermo-Lag 330-1 fire barriers: incomplete or indeterminate fire test results, questionable ampacity derating test results and a wide range of documented ampacity derating factors, some barrier installations that were not constructed in accordance with vendor-recommended installation procedures, incomplete installation procedures, and as-built fire barrier configurations that may not have been qualified by valid fire endurance tests or evaluated in accordance with the guidance of GL 86-10. After reviewing INs 91-47 and 91-79, Texas Utilities (TU) Electric Company initiated a fire endurance test program to qualify the Thermo-Lag raceway fire barrier systems for Comanche Peak Steam Electric Station. Under this program, TU Electric performed an initial fire barrier test series during the weeks of June 15 and 22, and August 19, 1992. Notwithstanding the fire test acceptance criteria guidance specified in GL 86-10, TU Electric followed the guidance of American Nuclear Insurers (ANI) as specified in ANI Information Bulletin 5(79), "ANI/MAERP Standard Fire Endurance Test Method to Qualify a Protective Envelope for Class 1E Electrical Circuits," July 1979. As a result of NRC interaction with TU Electric regarding its test program, the NRC concluded that there was uncertainty on the part of licensees as to whether or not the ANI test method established a level of fire barrier performance equivalent to that established by the GL 86-10 acceptance criteria. In addition, the NRC staff recognized that the 1-hour and 3-hour raceway fire barrier systems are unique and that additional guidance on the proper implementation of the GL 86-10 acceptance criteria would be useful. AREAS OF CONCERN The experiences with Thermo-Lag fire barrier systems at TU Electric recounted above raised the following general concerns: (1) The fire endurance test acceptance criteria used by other fire barrier vendors, applicants, and licensees may not meet the acceptance criteria of GL 86-10, and may not fully demonstrate the fire barrier performance intended. (2) Certain past cable functionality testing (i.e., circuit integrity monitoring) may not fully demonstrate the capability of protected circuits to function during and after a postulated fire. FIRE ENDURANCE CAPABILITY NRC Qualification Requirements and Guidance for Fire Barriers Section 50.48 of 10 CFR requires that each operating nuclear power plant have a fire protection plan that satisfies General Design Criterion (GDC) 3. GDC 3 requires that structures, systems, and components important to safety be designed and located to minimize, in a manner consistent with other safety requirements, the probability and effects of fires. Fire protection features required to satisfy GDC 3 include features to ensure that one train of those systems necessary to achieve and maintain shutdown conditions be maintained free of fire damage. One means of complying with this requirement is to separate one safe shutdown train from its redundant train with a fire-rated barrier. The level of fire resistance required of the barrier, 1-hour or 3-hours, depends on the other fire protection features in the fire area. The NRC issued guidance on acceptable methods of satisfying the regulatory requirements of GDC 3 in Branch Technical Position (BTP) Auxiliary and Power Conversion Systems Branch (APCSB) 9.5-1, "Guidelines for Fire Protection for Nuclear Power Plants;" Appendix A to BTP APCSB 9.5-1; BTP Chemical Engineering Branch (CMEB) 9.5-1, "Fire Protection for Nuclear Power Plants;" and GL 86-10. In the BTPs and in GL 86-10, the staff stated that the fire resistance ratings of fire barriers should be established in accordance with NFPA Standard 251, "Standard Methods of Fire Tests of Building Construction and Materials," by subjecting a test specimen that represents the materials, workmanship, method of assembly, dimensions, and configuration for which a fire rating is desired to a "standard fire exposure." Some licensees have used the acceptance criteria of ANI Bulletin No. 5(79), to evaluate the performance of their fire barrier systems. The ANI test methodology, which ANI issued for insurance purposes only, requires that cables within the fire barrier test specimen be monitored for circuit integrity while the test specimen is subjected to a test fire that follows the standard time-temperature curve specified in American Society of Testing and Materials (ASTM) Standard E-119, "Standard Methods of Fire Tests of Building Construction and Materials," and to a hose stream test. Under this criterion, the fire barrier system is evaluated by monitoring the capability of the cables inside the fire barrier to pass a low voltage circuit integrity test. During the fire and hose stream tests, if cable circuit integrity is maintained, the tests are considered successful. The ANI test methodology does not specify the following GL 86-10 acceptance criteria: (1) The fire barrier design has withstood the fire endurance test without the passage of flame or the ignition of cotton waste on the unexposed side for a period of time equivalent to the fire-resistance rating required of the barrier. (2) Analysis of temperature levels recorded on the unexposed side of the fire barrier demonstrates that the maximum temperature rise does not exceed 139 �C [250 �F] above ambient temperature. (3) The fire barrier remains intact and does not allow water to be projected beyond the unexposed surface during the hose stream test. Enclosure 1, "Interpretations of Appendix R," to GL 86-10, provided additional guidance with respect to the term "free of fire damage" as used in Appendix R. Interpretation 3, "Fire Damage," stated: "In promulgating Appendix R, the Commission has provided methods acceptable for assuring that necessary structures, systems, and components are free from fire damage (see Section III.G.2a, b, and c), that is, the structure, system or component under consideration is capable of performing its intended function during and after the postulated fire, as needed." The review guidance provided in Enclosure 1 (1) clarifies the applicability of the test acceptance criteria stated in GL 86-10 to raceway fire barrier systems, (2) specifies a set of fire endurance test acceptance criteria which are acceptable for demonstrating that fire barrier systems can perform the required fire-resistive function and maintain the protected safe shutdown train free of fire damage, (3) specifies acceptable options for hose stream testing, and (4) specifies acceptable criteria for functionality testing of cables when a deviation is necessary, such as when the fire barrier temperature rise criteria are exceeded or the test specimen cables sustain visible damage. The test methods and acceptance criteria specified in Enclosure 1 are acceptable for determining the adequacy of fire barrier systems proposed by licensees or applicants in the future to satisfy NRC fire protection rules and regulations. Applicants or licensees may propose alternative test methods and acceptance criteria to demonstrate an equivalent level of protection; the staff will review such proposals on a case-by-case basis. Enclosure 2 is a summary comparison of this review guidance against the GL 86-10 acceptance criteria. Evaluation and Application of Fire Endurance and Functionality Test Results The fire endurance qualification test is successful for a raceway fire barrier if the following conditions are satisfied (see Enclosure 3, "Fire Barrier Testing Acceptance Criteria/Logic Diagram"): (1) The average internal temperature of the fire barrier system, as measured on the exterior surface of the raceway or component, did not rise more than 139 �C [250 �F] above its initial temperature; and .(2) When cables or components are included in the test specimen, a visual inspection of the protected cables or components revealed no signs of degraded conditions from the thermal effects of the fire exposure; and (3) The fire barrier system remained intact during the fire exposure and hose stream tests without developing any openings through which the protected component, raceway, or cables are visible. For raceway fire barrier systems, the staff adopted the hose stream testing methodology specified in NUREG-0800, "Standard Review Plan (SRP) for the Review of Safety Analysis Reports for Nuclear Power Plants," Section 9.5.1, "Guidelines for Fire Protection for Nuclear Power Plants," Revision 2, July 1981, Position 5.a. This SRP position established the acceptability of using the fog nozzle method for hose stream testing of fire barrier penetration seals. The fog nozzle hose stream test method is an acceptable option for tests of the entire raceway fire barrier system under the new staff position. Licensees that propose to use fire endurance test results that deviate from the acceptance criteria as the bases for qualifying and installing fire barrier configurations, should request a deviation from the acceptance criteria based on a engineering evaluation acceptable to the staff, such as demonstrating cable functionality. For those licensees required to comply with Section III.G to Appendix R, the engineering evaluation justifying the deviating conditions should be submitted with the exemption request. The review guidance provided in Enclosure 1 provides specific guidance for demonstrating cable functionality, including subjecting the cables to Megger and high-potential tests. The results of these tests can be used to determine the insulation-resistance characteristics of the thermally damaged cable and to determine if the cable insulation would have been sufficient to maintain circuit functionality during and after the fire exposure. IMPLEMENTATION This section describes how the NRC plans to use the review guidance contained in Enclosure 1. After this supplement to GL 86-10 is issued, except in those cases in which an applicant or licensee has proposed an acceptable alternative fire endurance test method and acceptance criteria that demonstrates an equivalent level of fire protection, the NRC will use the methods and the criteria specified in the enclosed review guidance to (1) evaluate fire endurance testing programs proposed by licensees or applicants in the future for demonstrating compliance with pertinent NRC fire protection rules and regulations and (2) review the adequacy of the fire barrier systems proposed in the future by applicants or licensees. ACTIONS REQUESTED None. REPORTING REQUIREMENTS None. BACKFIT DISCUSSION The guidance transmitted by this generic letter supplement will be used by the staff for review and evaluation of the adequacy of fire barrier systems and fire endurance tests that may be proposed in the future to satisfy NRC fire protection rules and regulations. This guidance refines and clarifies the guidance specified in Generic Letter 86-10 for application in that future review context; specifically it (1) clarifies the applicability of the test acceptance criteria stated in GL 86-10 to raceway fire barrier systems, (2) specifies a set of fire endurance test acceptance criteria which are acceptable for demonstrating that fire barrier systems can serve the required fire-resistive function and maintain the protected safe shutdown train free of fire damage, (3) contains acceptable options for hose stream testing, and (4) specifies acceptable criteria for functionality testing of cables when a deviation would be necessary, such as if the fire barrier temperature rise criteria are exceeded or the cable sustains visible damage. No generic or plant-specific backfitting is intended or approved at this time in connection with issuance of this review guidance. The staff may consider the need for further generic action in that regard, if the industry guidance currently under development for addressing the pertinent fire protection issues is substantively inconsistent with this staff review guidance; but such action would be separately justified in accordance with the criteria of 10 CFR 50.109 and existing NRC backfit procedures. Similarly, if plant-specific backfits are proposed by the NRC staff consistent with this review guidance, the proposed backfits would be justified on a case-by-case basis in accordance with the criteria of 10 CFR 50.109 and existing NRC backfit procedures. .If you have any questions about this matter, please contact one of the contacts listed below or the appropriate Office of Nuclear Reactor Regulation project manager. Sincerely, /s/'d by LAReyes Luis A. Reyes Acting Associate Director for Projects Office of Nuclear Reactor Regulation Enclosures: 1. NRC Staff Review Guidance and Fire Endurance Test Acceptance Criteria for Fire Barrier Systems Used To Separate Redundant Safe Shutdown Trains Within the Same Fire Area. 2. Comparison of Staff Position on Fire Endurance Test Acceptance Criteria for Fire Barrier Systems Used To Separate Redundant Safe Shutdown Trains Within the Same Fire Area to the Acceptance Criteria of GL 86-10. 3. NRC Fire Testing Acceptance Criteria Logic Diagram. Technical contact: Patrick M. Madden, NRR (301) 504-2854 Lead Project Manager: Marsha K. Gamberoni, NRR (301) 504-3024 . FIRE ENDURANCE TEST ACCEPTANCE CRITERIA FOR FIRE BARRIER SYSTEMS USED TO SEPARATE REDUNDANT SAFE SHUTDOWN TRAINS WITHIN THE SAME FIRE AREA I. BACKGROUND In 1975, the Browns Ferry Nuclear power plant experienced a serious electrical cable tray fire. This fire had a significant impact on operator response to the event from a safety perspective. The fire caused spurious instrumentation indications and affected the control of several safety systems. As a result of this fire, the NRC issued the following fire protection guidelines and regulations concerning fire protection programs at nuclear power plants: May 1, 1976 Branch Technical Position (APCSB) 9.5-1, "Fire Protection Program." February 24, 1977 Appendix A to Branch Technical Position APCSB 9.5-1, "Guidelines for Fire Protection for Nuclear Power Plants Docketed Prior to July 1, 1976." February 19, 1981 10 CFR 50.48, "Fire Protection." February 19, 1981 Appendix R to 10 CFR Part 50, "Fire Protection Program for Nuclear Power Facilities Operating Prior to January 1979." July 1981 NUREG-0800, Standard Review Plan (SRP), 9.5.1, "Fire Protection for Nuclear Power Plants." In addition to the above fire protection guidance and regulations, the NRC, in an effort to clarify its fire protection requirements to the industry, issued Generic Letter (GL) 81-12, "Fire Protection Rule (45 FR 76602, November 19, 1980)," February 20, 1981; GL 83-33, "NRC Position on Certain Requirements of Appendix R to 10 CFR 50," October 19, 1983; and GL 86-10, "Implementation of Fire Protection Requirements," April 24, 1986. GL 86-10, which took precedence over previous staff guidance, provided staff interpretations to Appendix R and answers to industry questions regarding the implementation of Appendix R. The NRC, in an effort to give the licensees flexibility to make changes to its plant specific fire protection program, issued GL 88-12, "Removal of Fire Protection Requirements From Technical Specifications," August 2, 1988. Through the implementation and the adoption of a standard license condition, a licensee can make changes which do not adversely affect the ability to achieve and maintain post-fire safe shutdown to its fire protection program in accordance with 10 CFR 50.59. The aforementioned NRC documents provided NRC staff guidance concerning fire barriers separating plant fire areas, including the fire resistance (endurance) ratings for the barriers and the qualification tests that establish their fire resistance ratings. In addition, the documents provided guidance on combustibility of structural materials and tests for demonstrating low flame spread properties. The following sections of this document provide the objective for providing safe shutdown related fire barriers in nuclear power plants, definition of fire protection terms related to fire barriers, and the NRC fire endurance test acceptance criteria for fire barriers used to separate safe shutdown functions within the same fire area. II. OBJECTIVE OF FIRE BARRIERS USED TO SEPARATE SAFE SHUTDOWN FUNCTIONS WITHIN THE SAME FIRE AREA Fire rated barriers are used in nuclear power plants to provide fire area separation between redundant safety-related components and safe shutdown functions. They provide fire resistance protection, as required by Appendix R, to one safe shutdown train in those fire areas which contain both trains. The objective of the safe shutdown related Appendix R fire barrier is to ensure that a safe shutdown train is conservatively protected from fire-related thermal damage. The necessity for these fire barriers has been verified by multiple probabilistic risk assessments (PRAs). These PRAs indicated that, even with fire barriers installed, fires are a major contributor to core melt probabilities. It is the position of the NRC that fire endurance ratings of building construction and materials are demonstrated by testing fire barrier assemblies in accordance with the provisions of the applicable sections of NFPA 251, "Standard Methods of Fire Tests of Building Construction and Materials," and ASTM E-119, "Fire Test of Building Construction and Materials." Assemblies that pass specified acceptance criteria (e.g., standard time-temperature fire endurance exposure, unexposed side temperature rise, and hose stream impingement) are considered to have a specific fire resistance rating. Enclosure 1 to GL 86-10, "Interpretations of Appendix R," provided additional guidance with respect to the term "free from fire damage." Interpretation 3, "Fire Damage," states, "In promulgating Appendix R, the Commission has provided methods acceptable for assuring that necessary structures, systems, and components are free from fire damage (see Section III.G.2a, b, and c), that is, the structure, system or component under consideration is capable of performing its intended function during and after the postulated fire, as needed." GL 86-10, Response 3.2.1, also stated that, "The resulting 325 �F cold side temperature criterion is used for cable tray wraps because they perform a fire barrier function to preserve the cables free from fire damage. It is clear that cable that begins to degrade at 450 �F is free from fire damage at 325 �F." (Emphasis added.) In addition, the staff response stated that, "for newly identified conduit and cable trays requiring such wrapping new materials which meet the 325 �F criterion should be used, or justification should be provided for the use of material which does not meet the 325 �F criterion. This may be based on an analysis demonstrating that the maximum recorded temperature is sufficiently below the cable insulation ignition temperature." (Emphasis added.) The basic premise of the NRC fire resistance criteria is that fire barriers which do not exceed 163 �C [325 �F] cold side temperature and pass the hose stream test provide adequate assurance that the shutdown capability is protected without further analyses. If the temperature criteria is exceeded, sufficient additional information is needed to perform an engineering evaluation to demonstrate that the shutdown capability is protected. III. DEFINITIONS In order to support the understanding of the technical terms used throughout this document, the following definitions are provided. Combustible Material - Material that does not meet the definition of non- combustible. Fire Barrier - Those components of construction (walls, floors and their supports), including beams, joists, columns, penetration seals or closures, fire doors, and fire dampers that are rated by approving laboratories in hours of resistance to fire and are used to prevent the spread of fire. Fire Resistance Rating - The time that materials of a test assembly have withstood a standard ASTM E-119 fire exposure and have successfully met the established test acceptance criteria (fire barrier test acceptance criteria refer to Sections IV, V, and VI). Noncombustible Material - (a) Material which, in the form in which it is used and under the conditions anticipated, will not ignite, burn, support combustion, or release flammable vapors when subjected to fire or heat; (b) Material having a structural base of noncombustible material, with a surfacing not over 1/8-inch thick that has a flame spread rating of not higher than 50 when measured in accordance with ASTM E-84, "Surface Burning Characteristics of Building Materials." (There is an exception to this definition as defined by BTP Appendix A, Position D.1.d. This position allows the use of combustible interior finishes when listed by a nationally recognized test laboratory, such as Factory Mutual or Underwriters Laboratories, Incorporated, for a flame spread, smoke and fuel contribution of 25 or less in its use configuration.) Raceway - Cable trays, conduits, junction boxes, and other components used to support and route cables from circuit termination to circuit termination. Raceway Fire Barrier - Nonload bearing partition type envelope system installed around electrical components and cabling that are rated by test laboratories in hours of fire resistance and are used to maintain safe shutdown functions free of fire damage. IV. FIRE ENDURANCE TEST ACCEPTANCE CRITERIA FOR FIRE BARRIER WALLS, FLOORS, CEILINGS, AND FREE STANDING EQUIPMENT ENCLOSURES USED TO SEPARATE SAFE SHUTDOWN FUNCTIONS WITHIN THE SAME FIRE AREA To demonstrate the adequacy of fire barrier walls, floors, ceilings, and enclosures, barrier designs should be verified by fire endurance testing. NRC fire protection guidance refers to the guidance of NFPA 251 and ASTM E-119 as acceptable test methods for demonstrating fire endurance performance. The fire endurance test acceptance criteria for the subject fire barriers are: The fire barrier design has withstood the fire endurance test without the passage of flame or the ignition of cotton waste on the unexposed side for a period of time equivalent to the fire resistance rating required of the barrier; The temperature levels recorded on the unexposed side of the fire barrier are analyzed and demonstrable that the maximum temperature does not exceed 139 �C [250 �F] above ambient; and The fire barrier remains intact and does not allow projection of water beyond the unexposed surface during the hose stream test. (For acceptable hose stream test methods and time of application - See Section VII.) If the above criteria are met for fire barrier walls, floors, ceilings, and free standing equipment enclosures separating safe shutdown functions within the same fire area, the barrier is acceptable. NRC fire protection guidance also ensures that door and ventilation openings and penetrations are properly protected. The guidance requires that these openings be protected with fire doors and fire dampers which have been fire tested and listed by a nationally recognized test laboratory (e.g., Factory Mutual or Underwriters Laboratories, Incorporated). In addition, the construction and installation techniques for door and ventilation openings and other penetrations through these fire barriers should be qualified by fire endurance tests. The guidance of NFPA 251 and ASTM E-119 should be consulted with regard to construction, materials, workmanship, and details such as dimensions of parts, and the size of the specimen(s) to be tested. In addition, NFPA 251 and ASTM E-119 should be consulted with regard to the placement of thermocouples on the specimen. V. FIRE ENDURANCE TEST ACCEPTANCE CRITERIA FOR ELECTRICAL RACEWAY AND COMPONENT FIRE BARRIER SYSTEMS FOR SEPARATING SAFE SHUTDOWN FUNCTIONS WITHIN THE SAME FIRE AREA The NRC provided guidance in Appendix A to Branch Technical Position 9.5-1, Position D.3.(d), for cable tray fire barriers. This fire protection guidance states that the design of fire barriers for horizontal and vertical cable trays should, as a minimum, meet the requirements of ASTM E-119, "Fire Test of Building Construction and Materials," including hose stream test. On November 19, 1980, the NRC issued Appendix R to 10 CFR Part 50. The technical basis for Section III.M, "Fire Barrier Penetration Seal Qualification," states that "Fire barriers are `rated' for fire resistance by being exposed to a `standard test fire.' This standard test fire is defined by the American Society of Testing and Materials in ASTM E-119." In addition, this technical basis stated that "[i]f specific plant conditions preclude the installation of a 3-hour fire barrier to separate the redundant trains, a 1-hour fire barrier and automatic fire suppression and detection system for each redundant train will be considered the equivalent of a 3-hour barrier." Appendix R to 10 CFR Part 50, Section III.G, "Fire protection of safe shutdown capability," provides what the NRC views as equivalent means for ensuring that one safe shutdown train remains free of fire damage. In 1984 Appendix R workshops held with industry, and later in GL 86-10, the staff provided guidance related to fire barrier designs for raceways. In Enclosure 2, "Question and Answers," to this GL, Question 3.2.1., "Acceptance Criteria," the staff provided guidance on the cold side temperature for fire barrier cable tray wraps. In response to this question the staff stated that the acceptance criteria contained in Chapter 7 of NFPA 251, "Standard Methods of Fire Tests of Building Construction and Materials," pertaining to non- bearing fire barriers was applicable to cable tray fire barrier wraps. Chapter 5 of NFPA 251 explains the conduct of the fire test. The following is the NFPA 251 acceptance criteria: - The wall or partition withstood the fire endurance test without the passage of flame or gases hot enough to ignite cotton waste, for a period equal to that for which classification is desired; - The wall or partition withstood the fire and hose stream tests specified in Chapter 5, without the passage of flame, gases hot enough to ignite cotton waste, or the hose stream. The assembly failed the hose stream test if an opening develops that permits the projection of water from the stream beyond the unexposed surface during the hose stream test; and - Transmission of heat through the wall or partition during the fire endurance test did not raise the temperature on the unexposed surfaces more than 139 �C [250 �F] above their initial temperatures. The staff considers the fire endurance qualification test for fire barrier materials applied directly to a raceway or component to be successful if the following conditions are met: - The average unexposed side temperature of the fire barrier system, as measured on the exterior surface of the raceway or component, did not exceed 139 �C [250 �F] above its initial temperature; and (Staff Guidance: NFPA 251 and ASTM E-119 allow this temperature to be determined by averaging thermocouple temperature readings. For the purposes of this criterion, thermocouple averaging can be used provided similar series of thermocouples (e.g., cable tray side rail) are averaged together to determine temperature performance of the raceway fire barrier system. In addition, conditions of acceptance are placed on the temperatures measured by a single thermocouple. If any single thermocouple exceeds 30 percent of the maximum allowable temperature rise (i.e., 139 �C + 42 �C = 181 �F [250 �F + 75 �F = 325 �F]), the test exceeded the temperature criteria limit.) - Irrespective of the unexposed side temperature rise during the fire test, if cables or components are included in the fire barrier test specimen, a visual inspection should be performed. Cables should not show signs of degraded conditions resulting from the thermal affects of the fire exposure; and (Staff Guidance: For those cases where signs of thermal degradation are present, the fire barrier did not perform its intended fire-resistive function. For those barriers which are not capable of performing their intended function, a deviation based on demonstrating that the functionality of thermally degraded cables or component was maintained and that the cables or component would have adequately performed their intended function during and after a postulated fire exposure may be granted. The attachment to this position provides a methodology for demonstrating the functionality of cables during and after a fire test exposure. The purpose of the functionality tests is to justify observed deviations in fire barrier performance. For those fire barrier test specimens that are tested without cables, an engineering analysis justifying internal fire barrier temperature conditions greater than allowed can be based on a comparison of the fire barrier internal temperature profile measured during the fire endurance test to existing cable specific performance data, such as environmental qualification (EQ) tests.) - The cable tray, raceway, or component fire barrier system remained intact during the fire exposure and water hose stream test without developing any openings through which the cable tray, raceway, or component (e.g., cables) is visible. Section VII identifies acceptable hose stream test methods. The test specimen should be representative of the construction for which the fire rating is desired as to materials, workmanship, and details such as dimensions of parts, and should be built under representative conditions. Raceway fire barrier systems being subjected to qualification fire endurance tests should be representative of the end use. For example, if it is intended to install a cable tray fire barrier system in the plant without protecting the cable tray supports, then the test program should duplicate these field conditions. In addition, the fire test program should encompass or bound raceway sizes and the various configurations for those fire barrier systems installed in the plant. It should be noted that several test specimens will be required in order to qualify various sizes of horizontal and vertical runs of cable trays and conduits, junction boxes and pull boxes, etc. The cable tray or raceway design used for the tests should be constructed with materials and configurations representative of in plant conditions (e.g., the mass associated with typical steel conduits and cable trays, representative internal and external penetration seals). If cables are included in the raceway fire barrier test specimen, these cables should be representative of the installed plant-specific cables. Measuring cable temperatures is not a reliable means for determining excessive temperature conditions which may occur at any point along the length of the cable during the fire test. In lieu of measuring the unexposed surface temperature of the fire barrier test specimen, methods which will measure the surface temperature of the raceway (e.g., exterior of the conduit, side rails of cable trays, bottom and top of cable tray surfaces, junction box external surfaces) can be considered as equivalent if the raceway components used to construct the fire test specimen represent plant specific components and configurations. The metal surfaces of the raceway, under fire test conditions, exhibit good thermal conductivity properties. Temperatures measured on these surfaces provide a indication of the actual temperature rise within the fire barrier system. In 1979, American Nuclear Insurers (ANI) issued a fire endurance test method for raceway fire barrier systems for insurance purposes. This method, "Fire Endurance Protective Envelope Systems for Class 1E Electrical Circuits," specified that cable temperatures be monitored by thermocouples. Industry considers this the proper location for determining the temperature rise within the raceway fire barrier system. Since cable jackets have a low thermal conductivity, the actual local temperatures of the cable jackets indications of barrier failure and internal fire barrier temperature rise conditions during the fire exposure are masked. Monitoring cable temperatures can give indications of low internal fire barrier temperature conditions during the fire endurance test. Using this temperature monitoring approach, cable damage can occur without indication of excessive temperatures on the cables. This, linked with no loss of circuit integrity, would give indications of a successful test. The staff considers monitoring the cable temperature as the primary means of determining cable tray or raceway fire barrier performance to be nonconservative. Therefore, the staff has incorporated the provision for a post-fire visual inspection of cables that are installed in fire barrier test specimens. As discussed above, temperatures monitored on the exterior surface of the raceway provide a more representative indication of fire barrier performance. Fire endurance tests of raceway fire barrier systems should be without cables. This method is preferred because by excluding cables from the test specimen it eliminates bias in the test results created by the thermal mass of the cables. Without this thermal mass, the internal temperature conditions measured by the test specimen thermocouples during the fire exposure will provide a more accurate determination of fire barrier thermal performance. Thermocouple Placement - Test Specimens Containing Cables The following are acceptable placements of thermocouples for determining the thermal performance of raceway or cable tray fire barrier systems that contain cables during the fire exposure: Conduits - The temperature rise on the unexposed surface of a fire barrier system installed on a conduit should be measured by placing the thermocouples every 152 mm [6 inches] on the exterior conduit surface underneath the fire barrier material. The thermocouples should be attached to the exterior conduit surface located opposite the test deck and closest to the furnace fire source. Thermocouples should also be placed immediately adjacent to all structural members, supports, and barrier penetrations. Cable Trays - The temperature rise on the unexposed surface of a fire barrier system installed on a cable tray should be measured by placing the thermocouples on the exterior surface of the tray side rails between the cable tray side rail and the fire barrier material. In addition to placing thermocouples on the side rails, thermocouples should be attached to two AWG 8 stranded bare copper conductors. The first copper conductor should be installed on the bottom of the cable tray rungs along the entire length and down the longitudinal center of the cable tray run. The second conductor should be installed along the outer top surface of the cables closest to the top and towards the center of the fire barrier. The bare copper wire is more responsive than cable jackets to temperature rise within the fire barrier enclosure. The temperature changes measured along the bare copper conductors provide indication of joint failure or material burn through conditions. Thermocouples should be placed every 152 mm [6 inches] down the longitudinal center along the outside surface of the cable tray side rails and along the bare copper conductors. Thermocouples should also be placed immediately adjacent to all structural members, supports, and barrier penetrations. Junction Boxes (JB) - The temperature rise on the unexposed surface of a fire barrier system installed on junction boxes should be measured by placing thermocouples on either the inside or the outside of each JB surface. Each JB surface or face should have a minimum of one thermocouple, located at its geometric center. In addition, one thermocouple should be installed for every one square foot of JB surface area. These thermocouples should be located at the geometric centers of the one square foot areas. At least one thermocouple should also be placed within 25 mm [1 inch] of each penetration connector/interface. Airdrops - The internal airdrop temperatures should be measured by thermocouples placed every 305 mm [12 inches] on the cables routed within the air drop and by a stranded AWG 8 bare copper conductor routed inside and along the entire length of the airdrop system with thermocouples installed every 152 mm [6 inches] along the length of the copper conductor. The copper conductor should be in close proximity with the unexposed surface of the fire barrier material. Thermocouples should also be placed immediately adjacent to all supports and barrier penetrations. With the exception of airdrops, the installation of thermocouples on cables is optional and is left to the discretion of the licensee, test sponsor, or test laboratory. Cable thermocouples are to be used for engineering purposes only. Cable thermocouples alone are not acceptable for the demonstration of fire barrier performance. However, cable thermocouples may support fire barrier deviation conditions. Temperature conditions on the unexposed surface of the fire barrier material during the fire test will be determined by averaging the temperatures measured by the thermocouples. In determining these cable tray or raceway temperature conditions, the thermocouples measuring similar fire barrier areas of performance should be averaged together and the basis of acceptance will be based on the individual averages. The following method of averaging should be followed: Conduits - The thermocouples applied to the outside metal surface of the conduit should be averaged together. Cable Trays - The thermocouples on each cable tray side rail should be averaged separately. For example, thermocouples placed on one side rail will be averaged separately from the other side rail. In addition, the temperature conditions measured by thermocouples on the two bare copper conductors should be averaged separately. Junction Boxes - For small JBs which have only one thermocouple placed on each JB surface, the individual JB surface thermocouples should be averaged together. For larger JBs which have more that one thermocouple placed on each JB surface, the thermocouples on the individual JB surfaces should be averaged together. Airdrops - The thermocouples placed on the outer cable(s) routed in the airdrop fire barrier should be averaged together. The averages of any thermocouple group during the fire test should not exceed 139 �C [250 �F] above the unexposed side temperature within the fire barrier test specimen at the onset of the fire endurance test. In addition, the temperature of each individual thermocouple will be evaluated. Individual thermocouple conditions should not exceed the 139 �C [250 �F] temperature rise by more than 30 percent. Thermocouple Placement - Test Specimens Without Cables The following are acceptable thermocouple placements for determining the thermal performance of raceway or cable tray fire barrier systems that do not contain cables: Conduits - The temperature rise of the unexposed surface of a fire barrier system installed on a conduit should be measured by placing thermocouples every 152 mm [6 inches] on the exterior conduit surface between the conduit and the unexposed surface of the fire barrier material. These thermocouples should be attached to the exterior conduit surface opposite of the test deck and closest to the furnace fire source. The internal raceway temperatures should be measured by a stranded AWG 8 bare copper conductor routed through the entire length of the conduit system with thermocouples installed every 152 mm [6 inches] along the length of the copper conductor. Thermocouples should also be placed immediately adjacent to all structural members, supports, and barrier penetrations. Cable Trays - The temperature rise on the unexposed surface of a fire barrier system installed on a cable tray should be measured by placing thermocouples every 152 mm [6 inches] on the exterior surface of each tray side rails between the side rail and the fire barrier material. Internal raceway temperatures should be measured by a stranded AWG 8 bare copper conductor routed on the top of the cable tray rungs along the entire length and down the longitudinal center of the cable tray run with thermocouples installed every 152 mm [6 inches] along the length of the copper conductor. Thermocouples should be placed immediately adjacent to all structural members, supports, and barrier penetrations. Junction Boxes - The temperature rise on the unexposed surface of a fire barrier system installed on junction boxes should be measured by placing thermocouples on either the inside or the outside of each JB surface. Each JB surface or face should have a minimum of one thermocouple, located at its geometric center. In addition, one thermocouple should be installed for every one square foot of JB surface area. These thermocouples should be located at the geometric centers of the one square foot areas. At least one thermocouple should also be placed within 25 mm [1 inch] of each penetration connector/interface. Airdrops - The internal airdrop temperatures should be measured by a stranded AWG 8 bare copper conductor routed inside and along the entire length of the airdrop system with thermocouples installed every 152 mm [6 inches] along the length of the copper conductor. The copper conductor should be in close proximity with the unexposed surface of the fire barrier material. Thermocouples should also be placed immediately adjacent to all supports and penetrations. Temperature conditions on the unexposed surfaces of the fire barrier material during the fire test will be determined by averaging the temperatures measured by the thermocouples installed in or on the raceway. In determining these temperature conditions, the thermocouples measuring similar areas of the fire barrier should be averaged together. Acceptance will be based on the individual averages. The following method of averaging should be followed: Conduits - The thermocouples applied to the outside metal surface of the conduit should averaged together. Cable Trays - The thermocouples on each cable tray side rail should be averaged separately. For example, thermocouple placed on one side rail will be averaged separately from the other side rail. In addition, the temperature conditions measured by thermocouples on the bare copper conductor should be averaged separately from the side rails. Junction Boxes - For JBs that have only one thermocouple on each JB surface, the individual JB surface thermocouples should be averaged together. For JBs that have more that one thermocouple on each JB surface, the thermocouples on the individual JB surfaces should be averaged together. Airdrops - The thermocouples placed on the copper conductor within the airdrop fire barrier should be averaged together. The average of any thermocouple group should not exceed 139 �C [250 �F] above the unexposed side temperature within the fire barrier test specimen at the onset of the fire endurance test. In addition, the temperature of each individual thermocouple will be evaluated. Individual thermocouple conditions should not exceed the 139 �C [250 �F] temperature rise by more than 30 percent. If a fire barrier test specimen without cables does not meet the average or maximum single point temperature criteria, then the internal raceway temperature profile as measured by the instrumented bare copper conductors during the fire exposure can be used to assess cable functionality through air oven tests of plant specific cable types and construction. VI. HOSE STREAM TESTS NFPA 251 and ASTM E-119 allow flexibility in hose stream testing. The standards allow the hose stream test to be performed on a duplicate test specimen subjected to a fire endurance test for a period equal to one-half of that indicated as the fire resistance rating, but not for more than 1 hour (e.g., 30 minute fire exposure to qualify a 1-hour fire rated barrier). For safe shutdown related fire barrier systems referenced in Section IV and duplicate electrical cable tray or raceway and component fire barrier test specimens that have been exposed to the �-duration test fire exposure, the staff finds the hose stream application specified by the NFPA 251 acceptable. NFPA 251 requires the stream of water to be delivered through a 6.4 cm [2�- inch] hose discharging through a standard 2.9 cm [1�-inch] playpipe nozzle onto the test specimen after the fire exposure test. The stream is applied with the nozzle orifice positioned 6.1 meters [20 feet] away from the center of the test specimen at a pressure of 207 kPa [30 psi]. The application of the stream is to all exposed parts of the specimen for a minimum duration of 1 minute for a 1-hour barrier and 2� minutes for a 3-hour barrier. As an alternate for electrical raceway fire barrier test specimens, the application of the hose stream test can be performed immediately after the completion of the full fire endurance test period. If this method is used to satisfy the hose stream test criteria, the following hose stream applications are acceptable: - The stream applied at random to all exposed surfaces of the test specimen through a 6.4 cm [2�-inch] national standard playpipe with a 2.9 cm [1�-inch] orifice at a pressure of 207 kPa [30 psi] at a distance of 6.1 meters [20 feet] from the specimen. (Duration of the hose stream application - 1 minute for a 1-hour barrier and 2� minutes for a 3-hour barrier); or - The stream applied at random to all exposed surfaces of the test specimen through a 3.8 cm [1�-inch] fog nozzle set at a discharge angle of 30 degrees with a nozzle pressure of 517 kPa [75 psi] and a minimum discharge of 284 lpm [75 gpm] with the tip of the nozzle at a maximum of 1.5 meters [5 feet] from the test specimen. (Duration of the hose stream application - 5 minutes for both 1-hour and 3-hour barriers); or - The stream applied at random to all exposed surfaces of the test specimen through 3.8 cm [1�-inch] fog nozzle set at a discharge angle of 15 degrees with a nozzle pressure of 517 kPa [75 psi] and a minimum discharge of 284 lpm [75 gpm] with the tip of the nozzle at a maximum of 3 meters [10 feet] from the test specimen. (Duration of the hose stream application - 5 minutes for both 1- hour and 3-hour barriers.) VII. FIRE BARRIER COMBUSTIBILITY The NRC's fire protection guidelines and requirements establish the need for each nuclear power plant to perform a plant-specific fire hazard analysis. The fire hazard analysis should consider the potential for in-situ and transient fire hazards and combustibles. With respect to building materials (e.g., cable insulation and jackets, plastics, thermal insulation, fire barrier materials), the combustibility, ease of ignition, and flame spread over the surface of a material should be considered by the fire hazards analysis. One method of determining combustibility is by subjecting a sample of the fire barrier material to a small scale vertical tube furnace as described by ASTM E-136. The flashover ignition temperature of the material (as determined by ASTM D-1929) and the flame spread characteristics of the material (as determined by ASTM E-84) should also be evaluated. The potential heat release of the material (as determined by ASTM D-3286 or NFPA 259), should also be factored into the fire hazards analysis. Fire barrier materials used as radiant energy heat shields inside containment and used to achieve a combustible free zone are required to be noncombustible as defined in Section III. VIII. REFERENCES U.S. Nuclear Regulatory Commission May 1, 1976 Branch Technical Position (APCSB) 9.5-1, "Fire Protection Program." February 24, 1977 Appendix A to the Branch Technical Position APCSB 9.5-1, "Guidelines for Fire Protection for Nuclear Power Plants Docketed Prior to July 1, 1976." February 19, 1981 10 CFR 50.48, "Fire protection." February 19, 1981 Appendix R to 10 CFR Part 50, "Fire Protection for Nuclear Power Plants." February 20, 1981 Generic Letter 81-12, "Staff Position - Safe Shutdown Capability." July 1981 NUREG - 0800, Standard Review Plan, 9.5.1, "Fire Protection for Nuclear Power Plants." October 19, 1983 Generic Letter 83-33, "NRC Positions on Certain Requirements of Appendix R to 10 CFR 50." April 24, 1986 Generic Letter 86-10, "Implementation of Fire Protection Requirements." American Society for Testing and Materials ASTM E-84, "Surface Burning Characteristics of Building Materials." ASTM E-119, "Fire Test of Building Construction and Materials." ASTM E-136, "Behavior of Materials in a Vertical Tube Furnace at 750�C." ASTM D-1929, "Test Method for Ignition Properties of Plastics." ASTM D-3286, "Test Method for Gross Calorific Value of Solid Fuel by the Isothermal-Jacket Bomb Calorimeter." American Nuclear Insurers (ANI) July 1979, ANI Information Bulletin No. 5 (79) test criteria for "Fire Endurance Protective Envelope Systems for Class 1E Electrical Circuits." National Fire Protection Association (NFPA) NFPA 251, "Standard Methods of Fire Tests of Building Construction and Materials." NFPA 259, "Standard Test Method for Potential Heat of Building Materials." . ACCEPTABLE METHODS FOR DEMONSTRATING FUNCTIONALITY OF CABLES PROTECTED BY RACEWAY FIRE BARRIER SYSTEMS DURING AND AFTER FIRE ENDURANCE TEST EXPOSURE I. INTRODUCTION The NRC considers fire barrier systems that meet the acceptance criteria adequate under NRC fire protection regulations. The licensee, where the criteria are not met, should submit an engineering analysis to the staff that clearly demonstrates the functionality of the protected cables. This engineering analysis should consider the cable insulation type, actual voltage and current conditions, cable function, and thermal affects on the cable and its ability to function. This evaluation should also consider cable operating temperatures within the fire barrier at the onset of the fire exposure. II. CABLE CIRCUIT INTEGRITY TESTS In 1979, American Nuclear Insurers (ANI) issued a fire endurance test method for raceway fire barrier systems for insurance purposes. This method, "Fire Endurance Protective Envelope Systems for Class 1E Electrical Circuits," specified a circuit integrity test. The intent of this test was to identify the onset of fire damage to the cables within the raceway fire barrier test specimen during the fire endurance test period. The circuit integrity test voltage is 8 to 10 volts DC; therefore the loss of circuit integrity under these voltage conditions may occur only as a result of a dead short or open circuit. During fire tests of raceway fire barrier systems, thermal damage to the cables has been observed. This thermal damage has led to cable jacket and insulation degradation without the loss of circuit integrity as monitored using ANI criteria. Since cable voltages used for ANI circuit integrity tests do not replicate cable operating voltages, loss of cable insulation conditions can exist during the fire test without a dead short occurring. It is expected that if the cables were at rated power and current, a fault would propagate. The use of circuit integrity monitoring during the fire endurance test is not a valid method for demonstrating that the protected shutdown circuits are capable of performing their required function during and after the test fire exposure. Therefore, circuit integrity monitoring is not required to satisfy NRC acceptance criteria for fire barrier qualification. III. EQUIPMENT QUALIFICATION Comparison of the fire barrier internal time-temperature profile measured during the fire endurance test to existing cable performance data, such as data from environmental qualification (EQ) tests, could be proposed to the staff as a method for demonstrating cable functionality. EQ testing is typically performed to rigorous conditions, including rated voltage and current. By correlating the EQ test time-temperature profile to the fire test time-temperature profile, the EQ test data would provide a viable mechanism to ensure cable functionality. A large body of EQ test data for many cable types exists today. The use of EQ data represents a cost-effective approach for addressing cable functionality for fire tests for those cases where the 163 �C [325 �F] limit is exceeded. The staff agrees that a comparison of fire test temperature profiles to existing EQ and Loss of Cooling Accident (LOCA) test results or air oven test results is an acceptable approach to demonstrate cable functionality provided the subject analysis incorporates the anticipated temperature rise due to self heating effects of installed power cables with the fire test results. IV. CABLE INSULATION TESTS The two principal materials used as cable insulation and cable jackets by the nuclear industry are thermoplastics and thermosetting polymeric materials. A thermoplastic material can be softened and resoftened by heating and reheating. Conversely, thermosetting cable insulation materials cure by chemical reaction and do not soften when heated. Under excessive heating thermosetting insulation becomes stiff and brittle. Electrical faults may be caused by softening and flowing of thermoplastic insulating materials at temperatures as low as 149 �C [300 �F]. Thermosetting electrical conductor insulation materials usually retain their electrical properties under short- term exposures to temperatures as high as 260 �C [500 �F]. Insulation resistance (Megger) tests provide indications of the condition of the cable insulation resistance, whereas the high potential (Hi-Pot) test provides assurance that the cable has sufficient dielectric strength to withstand the applied rated voltage. A cable insulation failure usually results from two breakdown modes: one failure mode is excessive dielectric loss which is due to low insulation resistance, and the other failure mode is overpotential stress which is due to loss of dielectric strength of the insulation material. If Megger tests are not performed at frequent intervals during the fire exposure, indications of insulation damage in insulation may go undetected. When removed from elevated temperatures, insulation will reset. Megger tests of insulated cables after the fire endurance test and after the cable has sufficiently cooled may not detect degradation in the insulation resistance. Therefore, wet or dry Megger of cables after a fire exposure does not provide reasonable assurance that the cables would have functioned as intended during the fire exposure. To provide reasonable assurance that the cables would have functioned during and after the fire exposure, Megger tests need to be performed before the fire test, at multiple time intervals during the fire exposure (i.e, every 20 minutes during the 1-hour fire test and every hour during the 3-hour fire test) for instrumentation cables only, and immediately after the fire endurance test to assess the cable insulation resistance levels. This testing will assure that the cables will maintain the insulation resistance levels necessary for proper operation of instruments. The Megger tests (pre-fire, during the fire [if performed], and immediately after the fire test conditions) should be done conductor-to-conductor for multi-conductor and conductor-to-ground for all cables. The minimum acceptable insulation resistance (IR) value, using the test voltage values as shown in the table below, is determined by using the following expression: IR (Mega-ohms) > {[K+1 Mega-ohm ] * 1000 (ft) } Length (ft) Where K = 1 Mega-ohm/KV * Operating Voltage (expressed in KV) In addition, to determine the insulation resistance levels required for nuclear instrumentation cables, an assessment of the minimum insulation resistance value (e.g., one mega-ohm) and its potential impact on the functionality of these cables should be evaluated. An ac or dc high potential (Hi-Pot) test for power cables greater than 1000 volts (V) should also be performed after the post-fire Megger tests to assess the dielectric strength. This test provides assurance that the cable will withstand the applied voltage during and after a fire. The high potential test should be performed for a 5 minute duration at 60 percent of either 80 V/mil ac or 240 V/mil dc (e.g., 125 mil conductor insulation thickness x 240 V/mil dc x 0.6 = 18,000 V dc). The table below summarizes the Megger and Hi-Pot test voltages which, when applied to power, control and instrumentation cables, would constitute an acceptable cable functionality test. OPERATING MEGGER TEST HIGH POTENTIAL TYPE VOLTAGE VOLTAGE TEST VOLTAGE Power > 1000 V ac 2500 V dc 60% x 80 V/mil (ac) 60% x 240 V/mil (dc) Power < 1000 V ac 1500 V dc* None Instrument < 250 V dc 500 V dc None and < 120 V ac Control * A Megger test voltage of 1000 V dc is acceptable provided a Hi-Pot test is performed after the Megger test for power cables rated at less than 1000 V ac. The electrical cable functionality tests recommended above are one acceptable method. Alternate methods to assess degradation of cable functionality will be evaluated by the staff for acceptability on a case-by-case basis. The above table summarizing the Megger and Hi-Pot test voltages are "typical" and the applicant can follow the applicable industry standards and manufacturer's recommendations for the specific cable application in the performance of the insulation resistance and Hi-Pot tests. V. AIR OVEN TESTS Air oven tests can be used to evaluate the functionality of cables for those cable tray or raceway fire barrier test specimens tested without cables. This testing method consists of exposing insulated wires and cables at rated voltage to elevated temperatures in a circulating air oven. The temperature profile for regulating the temperature in the air oven during this test is the temperature measured by the AWG 8 bare copper conductor during the fire exposure of those cable tray or raceway test specimen which were tested without cables. The staff finds the test method described by UL Subject 1724, "Outline of Investigation for Fire Tests for Electrical Circuit Protective Systems", Issue Number 2, August 1991, Appendix B, "Qualification Test for Circuit Integrity of Insulated Electrical Wires and Cables in Electrical Circuit Protection Systems", with the following modifications, acceptable: 1. During the air oven test the cables are to be energized at rated voltage. The cables are to be monitored for conductor-to- conductor faults in multi-conductor cables and conductor-to-ground faults in all conductors. 2. The cables being evaluated should be subjected to the Megger and high potential tests, recommended above in Section IV, "Cable Insulation Tests." 3. The impact force test, which simulates the force of impact imposed on the raceway by the solid stream test, described in UL 1724, Appendix B, paragraph B3.16, is not required to be performed. VI. CABLE THERMAL EXPOSURE THRESHOLD The following analysis, which is based on determining whether a specific insulation material will maintain electrical integrity and operability within a raceway fire barrier system during and after an external fire exposure, is an acceptable method for evaluating cable functionality. In order to determine cable functionality, it is necessary to consider the operating cable temperatures within the fire barrier system at the onset of the fire exposure and the thermal exposure threshold (TET) temperature of the cable. For example, if the TET of a specific thermoplastic cable insulation (Brand X) is 149 �C [300 �F] and the normal operating temperature within the fire barrier system is 66 �C [150 �F], then the maximum temperature rise within the fire barrier system should not exceed 83 �C [150 �F] during exposure to an external fire of a duration equal to the required fire resistance rating of the barrier. For this example the TET limit for Brand X cable is 83 �C [150 �F] above the cable operating temperatures within the fire barrier system at the onset of the external fire exposure. The cable TET limits in conjunction with a post test visual cable inspection and the Hi-Pot test described above should readily demonstrate the functionality of the cable circuit during and after a fire. The normal cable operating temperature can be determined by loading cable specimens installed within a thermal barrier system in the test configuration with rated voltage and current. The TET temperature limits for most cable insulation may be obtained from the manufacturer's published data which is given as the short-circuit rating limit. With the known TET and normal operating temperature for each thermal barrier system configuration, the maximum temperature rise limit within a fire barrier system may then be determined. . COMPARISON OF FIRE ENDURANCE TEST CRITERIA FOR FIRE BARRIER SYSTEMS USED TO SEPARATE SAFE SHUTDOWN FUNCTIONS WITHIN THE SAME FIRE AREA GL 86-10, SUPP. 1.GL 86-10.RATIONALE FOR CLARIFICATION.Temperature, as measured on the external surface of the Raceway, should not exceed 163 �C [325 �F] (Note 1). This temperature is determined by averaging temperature readings of similar series of thermocouple (e.g., cable tray side rail) (Note 2). Barrier Condition - Fire barrier should remain intact. No visible signs of component, raceway or cables after fire and hose stream test. Hose Stream Test - solid stream test as specified in NFPA 251 on second test specimen after being subjected to a fire exposure of 1/2 duration (Note 4) or a fog stream after the full fire exposure. .Temperature, as measured on the unexposed side of the fire barrier material, should not exceed 163 �C [325 �F]. Barrier Condition - The barrier should have withstood the fire and hose stream test without the passage of flame or hot gasses hot enough to ignite cotton waste. Hose Stream Test - solid stream test as specified in NFPA 251. .Temperature - Difficult to measure a uniform temperature on the fire barrier material surface. Raceway temps provide good indication of internal temp-rise and potential barrier failure locations during the test. Barrier Condition - Cotton waste has not been used in raceway fire barrier testing as an indicator of barrier failure. Visual inspection process provides a better indication of barrier condition after the fire and hose stream test. Hose Stream Test - To reflect alternative methods found acceptable (Note 3). The use of a fog nozzle for the hose stream at the end of a full duration of the fire test provides a good method for testing erosion and cooling effects. .GL 86-10, SUPP. 1.GL 86-10.RATIONALE FOR CLARIFICATION.Cable condition - When cables are included in the test specimen, post-fire condition must be visually inspected. Cables should show no signs of degraded conditions resulting from the thermal affects of the fire exposure..Cable condition - No consideration given to determining the material condition of the cable. .Cable condition - The objective of these fire barriers is to assure that thermal damage to protected safe shutdown cables or components does not occur. GUIDANCE FOR ENGINEERING EVALUATIONS JUSTIFYING DEVIATIONS FROM THE FIRE BARRIER ACCEPTANCE CRITERIA Functionality should be demonstrated if any of the preceding criteria are exceeded (Note 5). Methods when cables are excluded from test specimen: Comparison of internal temp. profiles to EQ and LOCA test data. Air oven test of cables at rated voltage with Megger and Hi-Pot tests (Note 6) Method when cables are in test specimen include megger and Hi-Pot testing (Note 7) Demonstration of functionality should also consider operating temperature of the cables inside the fire barrier at the onset of the fire exposure. .Functionality - No guidance provided. Up to licensees to demonstrate by engineering analysis. Analysis kept on file for NRC review. Engineering analysis generally based on internal temperature below the ignition temperature. No consideration given cable operating temperatures within the barrier at the onset of the fire exposure. .Functionality is considered to be a deviation from the acceptance criteria and must be justified on a case-by-case basis which includes an assessment of cable jacket material. Note 1: The 163 �C [325 �F] temperature condition was established by allowing the internal temperature on the raceway surface to rise a maximum of 139 �C [250 �F] above the initial temperature of the test specimen (assumed to be 24 �C [75 �F]). Note 2: NFPA 251/ASTM-E119 allows the temperature condition to be determined by averaging the thermocouple readings. The conditions of acceptance are also placed on the temperature conditions measured by a single thermocouple. Under these conditions of acceptance, if any single thermocouple exceeds 30 percent above the maximum allowable temperature rise (i.e., max. allowable 139 �C + 42 �C = 181 �C [250 �F + 75 �F = 325 �F]) the test is considered to have exceeded the criteria temperature limit. Note 3: SRP 9.5.1 recognizes the use of a fog stream as an alternative hose stream testing method for qualifying fire barrier penetration seals. Note 4: This hose stream test method provides assurance that the cable tray or raceway fire barrier system has sufficient structural integrity to resist minor fire related barrier breaches caused by falling objects. Note 5: A fire barrier system that does not meet the acceptance criteria is not considered a rated fire barrier. For those conditions (e.g., high raceway temperature, barrier openings, water projection, cable damage) which deviate from the acceptance criteria, an engineering analysis which clearly demonstrates the functionality of the protected components or cables should be submitted to the staff for review. The purpose of the recommended functionality tests is to justify observed deviations in fire barrier performance. Engineering analyses justifying these deviations should not rely substantially upon the equipment (e.g., cable) qualification as the basis for acceptance. Deviations will be evaluated by the staff on a case-by-case basis. Note 6: For fire barrier systems tested without cables, plant-specific cable types should be subjected to air oven tests when the fire barrier temperature rise criteria are exceeded. These cables will be exposed to a temperature profile as determined by the internal raceway thermocouples during the fire test. Cables will be tested at rated voltage. Megger and Hi-Pot testing should be performed in a consistent manner to those tests performed for cables included in a fire barrier test specimen and subjected to the fire endurance test. Note 7: Megger tests of cables included in the fire test specimen should be performed before, during (instrumentation cables only) and immediately after the fire exposure and subjecting power cables which have voltage ratings > 1000 volts ac to a Hi-Pot test (60 percent) immediately after the fire exposure
Page Last Reviewed/Updated Tuesday, March 09, 2021
Page Last Reviewed/Updated Tuesday, March 09, 2021