COOPER ENERGY SERVICES
FAX: 301-816-5151
 
January 15, 1999
  
Our Ref: QCG-10513b(K5fa45)
 
Document Control Desk
U.S. Nuclear Regulatory Commission
Washington, D.C. 20555
 
Subject: 10 CFR 21 Notification, Air Start Distributor Filter Micron
Rating Evaluation and Closing Report - Enterprise DSR-4 and DSRV-4 Emergency Diesel Engine
 

Dear Sir:

In accordance with the requirements of the Nuclear Regulatory Commission Title 10, Chapter 1, Code of Federal Regulations, Part 21, Cooper Energy Services (CES), a division of Cooper Cameron Corporation, provides final response to a 10CFR Part 21 evaluation being conducted by Cooper Energy Services.

Our investigation is of a starting air distributor filter element provided as replacement part components for the Enterprise R4 and RV4 emergency diesel generator system. The Cooper-Bessemer part number of the filter cartridge is SB-006-002.

Discussion:

During the commercial grade dedication process, filter elements from multiple suppliers were pulled from stores and inspected for nuclear safety related application. The variation in the color and the fact that some filter elements did not have the supplier part number stamped on them prompted an investigation as to the actual micron rating.

Our evaluation of the subject starting air distributor filter elements (SB-006-002) that were in questions is complete. It is Cooper Energy Services judgement that this does not fall under the Title 10 CFR Part 21 criteria. Evaluation of the suspect filter elements, as compared to the known previously qualified element, was accomplished by subjecting an element of each to identical testing, which showed that the suspect element performs as well as the previously qualified element. Cooper Energy Services believes this to be an isolated case, but further investigations are continuing to be conducted via our in-house corrective action program for transportability concerns.

Page 2
January 15, 1999
QCG-10513b

If you have any questions or comments, please contact John Horne at 724-458-3543 or Ron Billig at 724-458-3584.

Sincerely,

COOPER ENERGY SERVICES

John M. Horne
Manager, Analytical Engineering

JMH/kll

Copies to:

Mr. Stephen Alexander
Nuclear Regulatory Commission
QA Vendor Insp. & Maintenance Branch
One White Flint North
Mailstop 9A1
Washington, DC 20555

FILE: K5fa 45

01/16/1999 U.S. Nuclear Regulatory Commission
Operations Center Event Report
Page 1
General Information or Other Event # 34914
 
Rep Org: COOPER ENERGY SERVICES Notification Date / Time: 10/14/1998
15:05 (EDT)
Licensee: COOPER ENERGY SERVICES Event Date / Time: 10/13/1998
00:00 (EDT)
Last Modification: 01/15/1999
Region: 1 Docket #:
City: GROVE CITY Agreement State: No
County: License #:
State: PA
NRC Notified by: TED MILLER Notifications: CURT COWGILL R1DO
HQ Ops Officer: JOHN MacKINNON
Emergency Class: NON EMERGENCY VERN HODGE/RPM/PCEB NRR
10 CFR Section:
21.21 UNSPECIFIED PARAGRAPH

10 CFR PART 21 NOTIFICATION - AIR START DISTRIBUTOR FILTER MICRON RATING EVALUATION AND INTERIM REPORT - ENTERPRISE DSR-4 AND DSRV-4 EMERGENCY DIESEL ENGINE

THE FOLLOWING TEXT IS A PORTION OF A FACSIMILE RECEIVED FROM COOPER ENERGY SERVICES:

"OUR INVESTIGATION IS OF A STARTING AIR DISTRIBUTOR FILTER ELEMENT PROVIDED AS REPLACEMENT PART COMPONENTS FOR THE ENTERPRISE R4 AND RV4 EMERGENCY DIESEL GENERATOR SYSTEM. THE COOPER-BESSEMER PART NUMBER OF THE FILTER CARTRIDGE IS SB-006-002."

"DISCUSSION:"

"DURING THE COMMERCIAL GRADE DEDICATION PROCESS, FILTER ELEMENTS FROM MULTIPLE SUPPLIERS WERE PULLED FROM STORES AND INSPECTED FOR NUCLEAR SAFETY-RELATED APPLICATION. THE VARIATION IN THE COLOR AND THE LACK OF SOME FILTER ELEMENTS HAVING THE MICRON RATING STAMPED ON THEM PROMPTED AN INVESTIGATION AS TO THE ACTUAL MICRON RATING."

"WE ARE IN THE PROCESS OF PERFORMING INDEPENDENT LAB TESTING TO ASCERTAIN WHETHER FILTER ELEMENTS OF AN INCORRECT MICRON RATING HAVE BEEN PROVIDED TO ANY OF OUR NUCLEAR CUSTOMERS. IT IS EXPECTED THAT THIS EVALUATION WILL BE COMPLETED ON OR BEFORE NOVEMBER 30, 1998."

----- UPDATE AT 1545 ON 11/25/98 VIA FACSIMILE RECEIVED BY TROCINE -----

THE FOLLOWING TEXT IS A PORTION OF A FACSIMILE RECEIVED FROM COOPER ENERGY SERVICES:

"WE ARE CONTINUING THE PROCESS OF PERFORMING INDEPENDENT LAB TESTING TO ASCERTAIN WHETHER FILTER ELEMENTS OF AN INCORRECT MICRON RATING HAVE BEEN PROVIDED TO ANY OF OUR NUCLEAR CUSTOMERS. IT IS EXPECTED THAT THIS EVALUATION WILL BE COMPLETED ON OR

01/16/1999 U.S. Nuclear Regulatory Commission
Operations Center Event Report
Page 2
General Information or Other Event # 34914

BEFORE JANUARY 15, 1999."

THE NRC OPERATIONS OFFICER NOTIFIED NRR/RPM/PCEB (HODGE) AS WELL AS THE R1DO (DELLA GRECA), R2DO (MCALPINE), R3DO (LEACH), AND R4DO (SANBORN). (CONTACT THE NRC OPERATIONS CENTER FOR COOPER ENERGY SERVICES CONTACT NAMES AND TELEPHONE NUMBERS.)

*****UPDATE AT 1023 ON 1/15/99 VIA FACSIMILE RECEIVED BY WEAVER******

"During the commercial grade dedication process, filter elements from multiple suppliers were pulled from stores and inspected for nuclear safety related application. The variation in the color and the fact that some filter elements did not have the supplier part number stamped on them prompted an investigation as to the actual micron rating.

"Our evaluation of the subject starting air distributor filter elements (SB-006-002) that were in questions is complete. It is Cooper Energy Services judgement that this does not fall under the Title 10 CFR Part 21 criteria. Evaluation of the suspect filter elements, as compared to the known previously qualified element, was accomplished by subjecting an element of each to identical testing, which showed that the suspect element performs as well as the previously qualified element. Cooper Energy Services believes this to be an isolated case, but further investigations are continuing to be conducted via our in-house corrective action program for transportability concerns."

The Operations Officer notified Vern Hodge (NRR) by fax.


*** END OF DOCUMENT ***