Skip to main content

Event Notification Report for July 09, 2023

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
07/08/2023 - 07/09/2023

EVENT NUMBERS
56614

Power Reactor
Event Number: 56614
Facility: Vogtle 3/4
Region: 2     State: GA
Unit: [3] [] []
RX Type: [3] W-AP1000,[4] W-AP1000
NRC Notified By: Taylor Joseph
HQ OPS Officer: Brian Lin
Notification Date: 07/09/2023
Notification Time: 16:57 [ET]
Event Date: 07/09/2023
Event Time: 13:28 [EDT]
Last Update Date: 07/09/2023
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS Actuation - Critical
Person (Organization):
Miller, Mark (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 A/R Y 45 Power Operation 0 Hot Standby
Event Text
AUTOMATIC REACTOR TRIP

The following information was provided by the licensee via email:

"At 1328 EDT on 07/09/2023, with Unit 3 in Mode 1 at 45 percent power, the reactor automatically tripped during power ascension testing due to low reactor coolant flow from decaying voltage to the reactor coolant pumps. The trip was not complex, with all safety-related systems responding normally post-trip.

"Operations responded and stabilized the plant. Decay heat is being removed by discharging steam via steam generator power operated relief valves to the atmosphere, and startup feedwater is supplying the steam generators. Units 1, 2, and 4 are not affected.

"Due to the Reactor Protection System actuation while critical, this event is being reported as a four-hour, non-emergency notification per 10 CFR 50.72(b)(2)(iv)(B). There was no impact on the health and safety of the public or plant personnel.

"The NRC Resident Inspector has been notified."