Skip to main content

Event Notification Report for March 21, 2018

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/20/2018 - 03/21/2018

EVENT NUMBERS
5327753275

Power Reactor
Event Number: 53277
Facility: VOGTLE
Region: 2     State: GA
Unit: [3] [4] []
RX Type: [3] W-AP1000,[4] W-AP1000
NRC Notified By: AMANDA PUGH
HQ OPS Officer: OSSY FONT
Notification Date: 03/22/2018
Notification Time: 09:31 [ET]
Event Date: 03/21/2018
Event Time: 15:50 [EDT]
Last Update Date: 03/22/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
26.719 - FITNESS FOR DUTY
Person (Organization):
SHANE SANDAL (R2DO)
FFD GROUP (EMAIL)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 N N 0 Under Construction 0 Under Construction
4 N N 0 Under Construction 0 Under Construction
Event Text
FITNESS FOR DUTY TEST SUBVERSION

A non-licensed contract supervisor attempted to subvert a random Fitness For Duty test using a subversion kit on their person. The employee's access to the plant has been terminated.

The NRC Resident Inspector has been notified.


Non-Agreement State
Event Number: 53275
Rep Org: 3M CORPORATE
Licensee: 3M CORPORATE
Region: 3
City: SPRINGFIELD   State: MO
County:
License #: 22-00057-03
Agreement: N
Docket:
NRC Notified By: MICHAEL LEWANDOWSKI
HQ OPS Officer: ANDREW WAUGH
Notification Date: 03/21/2018
Notification Time: 17:04 [ET]
Event Date: 03/21/2018
Event Time: 03:00 [CDT]
Last Update Date: 03/21/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
30.50(b)(2) - SAFETY EQUIPMENT FAILURE
Person (Organization):
ERIC DUNCAN (R3DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Event Text
GAUGE SHUTTER MALFUNCTION

"On March 21, 2018, at approximately 0300 CDT the shutter on an industrial beta transmission gauge malfunctioned and did not immediately close when commanded to do so. Facility maintenance personnel were able to get the shutter to fully close. The gauge was taken out of service. At approximately 0800 CDT the facility maintenance technician with the most experience working with radiation gauges inspected the device and found that the shutter opened properly, but would not fully close. The licensed service provider under contract to the facility was contacted and provided advice to the facility technician so that the shutter could be fully closed. The facility Radiation Safety Officer verified that the shutter was fully closed using a portable radiation survey meter. Electrical power to the device was locked out to prevent use. The gauge manufacturer was contacted to provide advice and to provide a replacement shutter assembly to be installed by the licensed service provider that the facility uses for more extensive maintenance on radiation gauges.

"Isotope, quantity, chemical and physical form:
"Kr-85, 1000 millicuries on January 8, 2007, encapsulated sealed source, serial number 05-709, QSA Global model KAC.D1, in LFE model SULP-77A beta thickness gauge, serial number 9281

"The event resulted in no radiation exposure to any individual."