Skip to main content

Alert

Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for January 10, 2003




                    U.S. Nuclear Regulatory Commission

                              Operations Center



                              Event Reports For

                           01/09/2003 - 01/10/2003



                              ** EVENT NUMBERS **



39490  39494  39496  39497  



+------------------------------------------------------------------------------+

|General Information or Other                     |Event Number:   39490       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  ARIZONA RADIATION REGULATORY AGENCY  |NOTIFICATION DATE: 01/06/2003|

|LICENSEE:  CONSTRUCTION INSPECTION AND TESTING  |NOTIFICATION TIME: 16:58[EST]|

|    CITY:  Tempe                    REGION:  4  |EVENT DATE:        01/06/2003|

|  COUNTY:                            STATE:  AZ |EVENT TIME:        16:00[MST]|

|LICENSE#:  7-98                  AGREEMENT:  Y  |LAST UPDATE DATE:  01/06/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |CHUCK CAIN           R4      |

|                                                |JOHN GREEVES         NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  AUBREY  V. GODWIN            |                             |

|  HQ OPS OFFICER:  ARLON COSTA                  |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|NAGR                     AGREEMENT STATE        |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| AGREEMENT STATE REPORT  - STOLEN MOISTURE DENSITY GAUGE                      |

|                                                                              |

| "At approximately 7:30 AM, January 6, 2003, the Agency [Arizona Radiation    |

| Regulatory Agency] received a voice mail message advising that a Troxler     |

| Model 3440 device, Serial Number 30391, was missing from 4440 West Mountain  |

| View Road, Glendale, AZ.  The device contains 8 millicuries of Cesium-137    |

| and 40 millicuries of Americium-241:Berylium.  The information supplied      |

| indicated that there is [evidence] that the device was stolen.  LICENSEE     |

| believes the source disappeared between 2:00 AM and 6:00 AM January 3, 2003. |

| Agency investigation indicates [that] the lock was cut and the device        |

| removed from the shipping case.  Glendale Police Department is also          |

| investigating this event, report number 03-972.                              |

|                                                                              |

| "The LICENSEE and the Agency continue to investigate this event.             |

|                                                                              |

| "The States of CA, CO, NV, NM, and UT and U.S. NRC and the U.S. FBI are      |

| being notified of this event.  Mexico is also being informed of this event." |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|General Information or Other                     |Event Number:   39494       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  TEXAS DEPARTMENT OF HEALTH           |NOTIFICATION DATE: 01/07/2003|

|LICENSEE:  SPECTRO INSTRUMENTS                  |NOTIFICATION TIME: 18:32[EST]|

|    CITY:  MARBLE FALLS             REGION:  4  |EVENT DATE:        01/07/2003|

|  COUNTY:                            STATE:  TX |EVENT TIME:        16:24[CST]|

|LICENSE#:  L02788                AGREEMENT:  Y  |LAST UPDATE DATE:  01/07/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |CHUCK CAIN           R4      |

|                                                |E. WILLIAM BRACH     NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  HELEN WATKINS                |                             |

|  HQ OPS OFFICER:  ARLON COSTA                  |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|NAGR                     AGREEMENT STATE        |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| AGREEMENT STATE REPORT ON LEAKING SOURCES                                    |

|                                                                              |

| Texas Department of Health received a telephone notification from Spectro    |

| Instruments that two 50 microcurie Fe-55 sources were leaking.  Sources S/N  |

| 5069LG and S/N 6172LG were leak tested 0.4 microcuries and 0.13 microcuries  |

| respectively.                                                                |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39496       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: QUAD CITIES              REGION:  3  |NOTIFICATION DATE: 01/09/2003|

|    UNIT:  [] [2] []                 STATE:  IL |NOTIFICATION TIME: 12:47[EST]|

|   RXTYPE: [1] GE-3,[2] GE-3                    |EVENT DATE:        01/09/2003|

+------------------------------------------------+EVENT TIME:        05:40[CST]|

| NRC NOTIFIED BY:  DARYL CLARK                  |LAST UPDATE DATE:  01/09/2003|

|  HQ OPS OFFICER:  RICH LAURA                   +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |ROGER LANKSBURY      R3      |

|10 CFR SECTION:                                 |                             |

|AIND 50.72(b)(3)(v)(D)   ACCIDENT MITIGATION    |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     N          Y       100      Power Operation  |100      Power Operation  |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| RHR VALVE AUTOMATICALLY WENT CLOSED INSTEAD OF OPEN DURING TESTING           |

|                                                                              |

| "At 0540 hours CST on 1/9/03 during the performance of QCOS 1000-09 (RHR     |

| Power Operated Valve Test), the RHR Injection Valve 2-1001-29A automatically |

| closed upon achieving the full open position. Group II isolation relays for  |

| both the 2-1001-29A and 2-1001-29B valves were discovered energized, which   |

| would cause these injection valves to close thereby prohibiting the low      |

| pressure injection function for both RHR subsystems (note that no Group II   |

| isolation signal was present). As such, Technical Specifications 3.5.1       |

| Condition D was entered. The isolation logic relays were reset (deenergized) |

| at 0625 CST and the 2-1001-29A and 2-1001-29B valves were satisfactorily     |

| cycled. Technical Specifications 3.5.1 Condition D has been exited. A prompt |

| investigation is in progress.                                                |

|                                                                              |

| "The notification is being made in accordance with 10CFR50.72(b)(3)(V)."     |

|                                                                              |

| The NRC Resident Inspector has been notified.                                |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39497       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: INDIAN POINT             REGION:  1  |NOTIFICATION DATE: 01/09/2003|

|    UNIT:  [] [3] []                 STATE:  NY |NOTIFICATION TIME: 13:55[EST]|

|   RXTYPE: [2] W-4-LP,[3] W-4-LP                |EVENT DATE:        01/03/2003|

+------------------------------------------------+EVENT TIME:        10:00[EST]|

| NRC NOTIFIED BY:  DAN LYON                     |LAST UPDATE DATE:  01/09/2003|

|  HQ OPS OFFICER:  RICH LAURA                   +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |RICHARD CONTE        R1      |

|10 CFR SECTION:                                 |                             |

|DDDD 73.71(b)(1)         SAFEGUARDS REPORTS     |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|3     N          Y       100      Power Operation  |100      Power Operation  |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| UNCOMPENSATED SECURITY GUARD DEGRADATION FOR 1 HOUR                          |

|                                                                              |

| Immediate compensatory measures were taken upon discovery. The licensee      |

| notified the resident inspector. Refer to the HOO log for additional         |

| details.                                                                     |

+------------------------------------------------------------------------------+

                   

Page Last Reviewed/Updated Thursday, March 25, 2021

Page Last Reviewed/Updated Thursday, March 25, 2021