The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

Event Notification Report for May 16, 2002

                         
                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           05/15/2002 - 05/16/2002

                              ** EVENT NUMBERS **

38920  38921  

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38920       |
+------------------------------------------------------------------------------+
                         
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  SOLIDSTATE CONTROLS, INC             |NOTIFICATION DATE: 05/15/2002|
|LICENSEE:  SOLIDSTATE CONTROLS, INC             |NOTIFICATION TIME: 15:07[EDT]|
|    CITY:  COLUMBUS                 REGION:  3  |EVENT DATE:        04/15/2002|
|  COUNTY:                            STATE:  OH |EVENT TIME:             [EDT]|
|LICENSE#:                        AGREEMENT:  Y  |LAST UPDATE DATE:  05/15/2002|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |RONALD GARDNER       R3      |
|                                                |DANIEL HOLODY        R1      |
+------------------------------------------------+PAUL FREDRICKSON     R2      |
| NRC NOTIFIED BY:  W. G. HAMPTON (FAX)          |GREG PICK            R4      |
|  HQ OPS OFFICER:  MIKE NORRIS                  |VERN HODGE           NRR     |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|CCCC 21.21               UNSPECIFIED PARAGRAPH  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 10 CFR 21 NOTIFICATION-POTENTIAL DEFECT INVOLVING FAN ASSEMBLIES FOR UPS  
  |
| SYSTEMS                                                                      |
|                                                                              |
| "The attached 10 CFR Part 21 record, Attachment A, is submitted to report a  |
| potential for a defect in fan assemblies used in Uninterruptible Power       |
| Systems manufactured under the Solidstate Controls, Inc., 10CFR50 Appendix B |
| Program.                                                                     |
|                                                                              |
| "Nature of the defect:                                                       |
|                                                                              |
| "PROBLEM SEEN: The above assembly contains a component part - an aluminum,   |
| five-wing fan blade, which potentially could separate from the hub. If the   |
| blade should come loose there may not be an alarm indication of loss of      |
| cooling. Additionally, the loose blade may cause a short circuit if it falls |
| into the equipment and should land across opposing current carrying          |
| devices.                                                                     |
|                                                                              |
| "CAUSE: We have determined that one fan blade style from one specific        |
| manufacturer of part number 03-470100-00 could, under certain conditions,    |
| separate from its hub.                                                       |
|                                                                              |
| "EFFECT ON SYSTEM PERFORMANCE: Fan Assembly - THE SEPARATION OF THE
BLADE    |
| FROM THE HUB COULD CAUSE THE SYSTEM TO DROP POWER TO THE LOAD. If the
worst  |
| case failure mode described above were to occur, it would result in the      |
| motor continuing to operate, thereby, not allowing the internal alarm        |
| mechanism to activate. Further, the blade itself could fall into the         |
| operating equipment causing a short circuit. It is important to note that    |
| the short circuit situation has not been reported.                           |
|                                                                              |
| "US NUCLEAR PLANT IMPACTED BY THIS ACTION:  There are approximately 30       |
| plants listed"                                                               |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38921       |
+------------------------------------------------------------------------------+
                         
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: OYSTER CREEK             REGION:  1  |NOTIFICATION DATE: 05/15/2002|
|    UNIT:  [1] [] []                 STATE:  NJ |NOTIFICATION TIME: 15:30[EDT]|
|   RXTYPE: [1] GE-2                             |EVENT DATE:        05/13/2002|
+------------------------------------------------+EVENT TIME:        05:15[EDT]|
| NRC NOTIFIED BY:  JERRY FREEMAN                |LAST UPDATE DATE:  05/15/2002|
|  HQ OPS OFFICER:  RICH LAURA                   +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |DANIEL HOLODY        R1      |
|10 CFR SECTION:                                 |TIM MCGINTY          IRO     |
|NONR                     OTHER UNSPEC REQMNT    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| LATE DECLARATION OF AN UNUSUAL EVENT FOR TORNADO                             |
|                                                                              |
| The licensee reported that on May 13, 2002, the national weather service     |
| issued a tornado warning for Central Ocean County, NJ.  The Oyster Creek     |
| Station was within the tornado warning area.  At 15:30 on May 15, 2002, the  |
| licensee determined that an Unusual Event should have been declared.  No     |
| tornados were sighted nor did the conditions affect safe station operation.  |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
+------------------------------------------------------------------------------+
