The purpose of this regulatory conference is to discuss a finding and apparent violation identified at Waterford Steam Electric Station, Unit 3. This finding is associated with through-wall corrosion of vent piping for emergency diesel generator fuel oil

Meeting Details

Category 1
Date
April 7, 2015
Time
9:00 am–12:00 pm EDT
Location
NRC Region IV Office

1600 East Lamar Boulevard
Arlington, TX

Agenda
Meeting Info

Purpose

The purpose of this regulatory conference is to discuss a finding and apparent violation identified at Waterford Steam Electric Station, Unit 3. This finding is associated with through-wall corrosion of vent piping for emergency diesel generator fuel oil day tanks. The holes in these vent pipes could allow water to enter the day tanks and contaminate the diesel fuel oil, challenging the operability and functionality of both safety-related emergency diesel generators. The apparent violation is discussed in NRC Inspection Report 05000382/2014007, dated January 22, 2015 (ADAMS Accession No. ML15022A637).

Teleconference

Bridge Number: 8889579871
Passcode: 2489913

Docket

05000382 - Waterford 3

Documents

Document Title Description
ML15082A444 04/07/2015 Regulatory Conference with Entergy Operations, Inc.

Comments

EA: 14-228

Contact

John Dixon

(817) 200-1434