Event Number: 56474
Facility: Turkey Point
Region: 2     State: FL
Unit: [3] [] []
RX Type: [3] W-3-LP,[4] W-3-LP
NRC Notified By: Jose Vasquez
HQ OPS Officer: Bill Gott
Notification Date: 04/18/2023
Notification Time: 03:56 [ET]
Event Date: 04/15/2023
Event Time: 11:12 [EDT]
Last Update Date: 04/18/2023
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(3)(ii)(A) - Degraded Condition
Person (Organization):
Miller, Mark (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 N N 0 Refueling 0 Refueling
Event Text
RCS PRESSURE BOUNDARY DEGRADED

The following information was provided by the licensee via email:

"At 1112 EDT on 4/15/23, it was determined that the [reactor coolant system] RCS pressure boundary does not meet ASME Section XI, Table IWB-341 0-1, `Acceptable Standards,' due to through wall leak of the flux mapper seal table guide tube H-6. Corrective actions have been scheduled. `This event is being reported pursuant to 10 CFR 50.72(b)(3)(ii)(A).

"A follow-up review of the condition revealed that 10 CFR 50.72 notification was applicable within 8 hours of the time of discovery on 04/15/23.

"The NRC Resident Inspector has been notified."