Skip to main content

Event Notification Report for October 09, 2019

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
10/08/2019 - 10/09/2019

EVENT NUMBERS
543185431954320

Power Reactor
Event Number: 54318
Facility: VOGTLE
Region: 2     State: GA
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: KRISTINA NICHOLS
HQ OPS Officer: KERBY SCALES
Notification Date: 10/09/2019
Notification Time: 12:48 [ET]
Event Date: 10/09/2019
Event Time: 10:23 [EDT]
Last Update Date: 10/09/2019
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
EUGENE GUTHRIE (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
AUTOMATIC START OF EMERGENCY DIESEL GENERATOR AND AUXILLIARY FEEDWATER SYSTEM

"At 1023 EDT, on October 9, 2019, with Unit 2 in Mode 1 and 100 percent power, an actuation of the Emergency Diesel Generator and Auxiliary Feedwater Systems occurred. The reason for the Emergency Diesel Generator auto-start was the loss of power to the 4160V 1E electrical bus 2AA02 due to a fault at an offsite electrical switchyard. The Emergency Diesel Generator started and energized the 4160V safety bus, and Auxiliary Feedwater Systems automatically started as designed when the undervoltage condition on the safety bus was detected.
This event is being reported in accordance with 10 CFR 50.72(b)(3)(iv)(A) as an event that results in a valid actuation of the Emergency Diesel Generator and Auxiliary Feedwater Systems.

"There was no impact on the health and safety of the public or plant personnel. The NRC resident has been notified."


Fuel Cycle Facility
Event Number: 54319
Facility: GLOBAL NUCLEAR FUEL - AMERICAS
Region: 2     State: NC
Unit: [] [] []
RX Type: URANIUM FUEL FABRICATION
Comments: LEU CONVERSION (UF6 TO UO2)
LEU FABRICATION
LWR COMMERICAL FUEL
NRC Notified By: PHILLIP OLLIS
HQ OPS Officer: HOWIE CROUCH
Notification Date: 10/09/2019
Notification Time: 15:55 [ET]
Event Date: 10/09/2019
Event Time: 13:00 [EDT]
Last Update Date: 10/09/2019
Emergency Class: NON EMERGENCY
10 CFR Section:
PART 70 APP A (c) - OFFSITE NOTIFICATION/NEWS REL
Person (Organization):
EUGENE GUTHRIE (R2DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Event Text
CONCURRENT NOTIFICATION DUE TO PLANNED MAINTENANCE ON FIRE PROTECTION SYSTEM

"At 1300 (EDT) on October 9th, 2019, the New Hanover County Deputy Fire Marshall was notified per State code requirements that the electric fire pump supporting the Fuel Manufacturing Operation (FMO) was being taken offline for maintenance. An electrical disconnect was being replaced. Compensatory measures were enacted. The pump was restored to operation at 1348 (EDT). Because the New Hanover County Deputy Fire Marshall was notified, a concurrent notification to the NRC Operations Center is being made per 10 CFR 70, Appendix A(c)."

The licensee will notify NRC Region 2 and the North Carolina Department of Health and Human Services Radiation Protection Branch.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 54320
Facility: FARLEY
Region: 2     State: AL
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: WILLIAM SORRELL
HQ OPS Officer: BETHANY CECERE
Notification Date: 10/10/2019
Notification Time: 02:17 [ET]
Event Date: 10/09/2019
Event Time: 23:40 [CDT]
Last Update Date: 03/18/2020
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xii) - OFFSITE MEDICAL
Person (Organization):
EUGENE GUTHRIE (R2DO)
CHRIS MILLER (NRR EO)
SILAS KENNEDY (IRD)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Defueled 0 Defueled
Event Text
POTENTIALLY CONTAMINATED INDIVIDUAL TRANSPORTED TO AN OFFSITE MEDICAL FACILITY

"At 2340 CDT, on October 09, 2019, a site contractor was transported offsite for treatment at an offsite medical facility. Due to the nature of the medical emergency, the individual was not thoroughly surveyed prior to being transported offsite. This is an eight-hour notification, non-emergency for the transportation of a contaminated person offsite. This event is reportable in accordance with 10 CFR 50.72(b)(3)(xii).

"Following the individual being transported offsite, but prior to the individual arriving at the offsite medical facility, the individual was confirmed to not be contaminated. This occurred at approximately 2350 CDT, on October 09, 2019.

"The NRC Resident Inspector has been notified."

* * * RETRACTION ON 3/18/2020 AT 1350 EDT FROM RICHARD LENGFORD TO BRIAN LIN * * *

"Farley Nuclear Plant is retracting this notification based on the information available at the time of the notification: Health Physics personnel had completed surveys that determined that the contract worker, ambulance, and responders were free of contamination prior to reaching the hospital. The initial report was made to alert the NRC based on the individual being potentially contaminated due to radioactive surveying being deferred to support prompt medical attention. Based on the subsequent determination that the individual was not contaminated the reporting requirements of 10CFR50.72(b)(3)(xii) are not met and this event report is being retracted.

"The NRC Resident Inspector has been notified."

Notified R2DO (Miller).