Skip to main content

Event Notification Report for August 18, 2019

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
08/17/2019 - 08/18/2019

EVENT NUMBERS
5423354228

Power Reactor
Event Number: 54233
Facility: CATAWBA
Region: 2     State: SC
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: WALTER HUNNICUTT
HQ OPS Officer: PHIL NATIVIDAD
Notification Date: 08/20/2019
Notification Time: 20:00 [ET]
Event Date: 08/18/2019
Event Time: 17:00 [EDT]
Last Update Date: 08/20/2019
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
RANDY MUSSER (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
REFUELING WATER STORAGE TANK LEVEL LOWER THAN REQUIRED

"While performing a purification on the Unit 2 Refueling Water Storage Tank (FWST), it was discovered that the single train system was inoperable due to the level being less than the required volume per SR [Surveillance Requirement] 3.5.4.2. The condition was discovered on 8/18/19 at 1700 [EDT]. The FWST level was restored to greater than the required volume per SR 3.5.4.2 at 1744 on 8/18/19. This condition is being reported as an eight-hour, non-emergency notification per 10 CFR 50.72(b)(3)(v)(D) for an event or condition that could have prevented the fulfillment of a safety function. There was no impact on the health and safety of the public or plant personnel.

"The NRC Resident Inspector has been notified."


Agreement State
Event Number: 54228
Rep Org: ALABAMA RADIATION CONTROL
Licensee: NUCOR STEEL OF TUSCALOOSA
Region: 1
City: TUSCALOOSA   State: AL
County:
License #: 1426
Agreement: Y
Docket:
NRC Notified By: MYRON RILEY
HQ OPS Officer: KERBY SCALES
Notification Date: 08/19/2019
Notification Time: 12:04 [ET]
Event Date: 08/18/2019
Event Time: 00:00 [CDT]
Last Update Date: 08/19/2019
Emergency Class: NON EMERGENCY
10 CFR Section:
30.50(b)(2) - SAFETY EQUIPMENT FAILURE
Person (Organization):
JONATHAN GREIVES (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Event Text
AGREEMENT STATE REPORT - DAMAGED GAUGE LOCKING MECHANISM

The following report was received via fax:

"On August 19, 2019, an Environmental Engineer for Nucor Steel of Tuscaloosa, Alabama notified the Office of Radiation Control [Agency] that a gauge stored in a caster mechanism had a loss of containment and damaged the locking mechanism of the gauge. The shutter mechanism is working, but the gauge cannot be locked out.

"The licensee notified the Alabama Emergency Operations Center of the event on August 18, 2019, at 1757 CDT. The licensee chose to follow-up with the Agency to ensure proper notification. The Agency told the licensee to send a synopsis of the events and a plan of action to maintain or dispose of the gauge.

"As of 1100 CDT today, the gauge is secure, but unlockable. The licensee has contacted the manufacturer for possible repair or disposable options. This incident remains open until a decision is made by the licensee for repair or disposal."

Alabama Incident: 19-20