Skip to main content

Event Notification Report for November 28, 2018

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
11/27/2018 - 11/28/2018

EVENT NUMBERS
537575375853759

Power Reactor
Event Number: 53757
Facility: PRAIRIE ISLAND
Region: 3     State: MN
Unit: [1] [2] []
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: JEFF HUMAN
HQ OPS Officer: KARL DIEDERICH
Notification Date: 11/28/2018
Notification Time: 12:30 [ET]
Event Date: 11/28/2018
Event Time: 00:00 [CST]
Last Update Date: 11/28/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
BILLY DICKSON (R3DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
OFFSITE NOTIFICATION DUE TO INADVERTENT SIREN ACTIVATION

"At 0752 CST, on November 28, 2018, Dakota County inadvertently actuated their sirens while performing a scheduled weekly [Emergency Planning Fixed Siren Test]. All seven (7) Dakota County sirens actuated for approximately 9 seconds before Dakota County Dispatch canceled the activation. This 4-hour non-emergency report is being made per 10 CFR 50.72(b)(2)(xi), Offsite Notification [which was made to Dakota County Dispatch]. Capability to notify the public was never degraded during this time. All Emergency Notification sirens remain in service. No press release is planned at this time."

The licensee has notified the NRC Resident Inspector.


Agreement State
Event Number: 53758
Rep Org: TEXAS DEPT OF STATE HEALTH SERVICES
Licensee: INEOS USA LLC
Region: 4
City: FREEPORT   State: TX
County:
License #: Licen-RAM-L01422
Agreement: Y
Docket:
NRC Notified By: ART TUCKER
HQ OPS Officer: KARL DIEDERICH
Notification Date: 11/28/2018
Notification Time: 17:10 [ET]
Event Date: 11/28/2018
Event Time: 00:00 [CST]
Last Update Date: 11/28/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
Person (Organization):
JASON KOZAL (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Event Text
AGREEMENT STATE - FIXED GAUGE STUCK SHUTTER

The following information was received from the State of Texas via email:

"On November 28, 2018, the Agency [Texas Department of State Health Services] was notified by the licensee that while performing a shutter test on an Ohmart-Vega Model SH-F1 gauge containing a 20 milliCurie (original activity) Cs-137 source, the shutter would not close. Open is the normal operating position for the gauge. The gauge is in a location that does not present an exposure risk to any individual. The licensee has contacted a service provider to repair the gauge. Additional information will be provided as it is received in accordance with SA-300."

Texas Incident #: I-9640.


Power Reactor
Event Number: 53759
Facility: CALLAWAY
Region: 4     State: MO
Unit: [1] [] []
RX Type: [1] W-4-LP
NRC Notified By: BRANDON LONG
HQ OPS Officer: KARL DIEDERICH
Notification Date: 11/28/2018
Notification Time: 17:25 [ET]
Event Date: 11/28/2018
Event Time: 00:00 [CST]
Last Update Date: 11/28/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(B) - POT RHR INOP 50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
JASON KOZAL (R4DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
DISCOVERY OF A CONDITION THAT COULD HAVE PREVENTED FULFILLMENT OF A SAFETY FUNCTION

"On November 28, 2018, while performing an engineering review of the bases for environmental qualification (EQ) requirements for the Atmospheric Steam Dumps (ASDs), it was determined that applicable EQ requirements had not been applied to a key component of each of the ASDs. The result of this issue is that it the availability of the ASDs for a controlled plant cooldown following a postulated steam line break outside containment cannot be assured.

"Callaway is developing a compensatory action temporary plant modification to install insulation that will protect the affected ASD components from the post Main Steam Line Break temperature.

"This condition is reportable 10 CFR 50.72(b)(3)(v) for any event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to (B) remove residual heat, or (D) mitigate the consequences of an accident."

The issue places the plant in a 24-hour Technical Specification (TS) Limiting Condition for Operations (LCO), 3.7.4.

The licensee has notified the NRC Resident Inspector.