Skip to main content

Event Notification Report for March 04, 2018

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/03/2018 - 03/04/2018

EVENT NUMBERS
53244

Non-Power Reactor
Event Number: 53244
Rep Org: UNIV OF MISSOURI-COLUMBIA
Licensee: UNIVERSITY OF MISSOURI
Region: 0
City: COLUMBIA   State: MO
County: BOONE
License #: R-103
Agreement: N
Docket: 05000186
NRC Notified By: BRUCE MEFFERT
HQ OPS Officer: STEVEN VITTO
Notification Date: 03/05/2018
Notification Time: 13:14 [ET]
Event Date: 03/04/2018
Event Time: 03:08 [CST]
Last Update Date: 03/05/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
GEOFFREY WERTZ (NRR)
ELIZABETH REED (NRR)
Event Text
TECHNICAL SPECIFICATION DEVIATION

"On 3/4/17 at 0308 CST, the MURR [University of Missouri Research Reactor] emergency power generator was switched out of automatic control for approximately 10 to 15 seconds while the reactor was operating due to human error. With the emergency power generator in manual control, the emergency electrical power system is considered inoperable because the emergency electrical power system would not have supplied power in the event of a loss of normal electrical power.

"This email is a required notification per MURR Technical Specification (TS) 6.6.c.(1) to report to the NRC Operations Center that an Abnormal Occurrence as defined by MURR TS 1.1 happened. Specifically, MURR was not in compliance with the Limiting Condition for Operation TS 3.6.a which states, 'The reactor shall not be operated unless the emergency electrical power system is operable.' When the emergency power generator was switched out of automatic control, a Control Room alarm notified the Console Operator. Another operator placed the emergency power generator back into automatic mode which was the quickest way to regain compliance with TS 3.6.a. The MURR continued to operate at 10 MW. A detailed event report will follow within 14 days as required by MURR TS 6.6.c.(3)."

The licensee notified the NRC Research and Test Reactor Project Manager (Wertz).