Event Notification Report for December 22, 2017
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
12/21/2017 - 12/22/2017
Agreement State
Event Number: 53633
Rep Org: COLORADO DEPT OF HEALTH
Licensee: CANYON BAKEHOUSE
Region: 4
City: JOHNSTOWN State: CO
County:
License #: GL002453
Agreement: Y
Docket:
NRC Notified By: PHILLIP PETERSON
HQ OPS Officer: JEFF HERRERA
Licensee: CANYON BAKEHOUSE
Region: 4
City: JOHNSTOWN State: CO
County:
License #: GL002453
Agreement: Y
Docket:
NRC Notified By: PHILLIP PETERSON
HQ OPS Officer: JEFF HERRERA
Notification Date: 10/01/2018
Notification Time: 10:30 [ET]
Event Date: 12/22/2017
Event Time: 00:00 [MDT]
Last Update Date: 10/01/2018
Notification Time: 10:30 [ET]
Event Date: 12/22/2017
Event Time: 00:00 [MDT]
Last Update Date: 10/01/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
10 CFR Section:
AGREEMENT STATE
Person (Organization):
THOMAS FARNHOLTZ (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB (EMAIL)
THOMAS FARNHOLTZ (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB (EMAIL)
AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGNS
The following report was received from the Colorado Department of Public Health and Environment via email:
"Canyon Bakehouse reported that three tritium exit signs were not in the building when the ownership of the building was transferred."
CO Event Report ID No.: CO180023
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
The following report was received from the Colorado Department of Public Health and Environment via email:
"Canyon Bakehouse reported that three tritium exit signs were not in the building when the ownership of the building was transferred."
CO Event Report ID No.: CO180023
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Power Reactor
Event Number: 53137
Facility: PERRY
Region: 3 State: OH
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: DANIEL HARTIGAN
HQ OPS Officer: DAVID AIRD
Region: 3 State: OH
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: DANIEL HARTIGAN
HQ OPS Officer: DAVID AIRD
Notification Date: 12/23/2017
Notification Time: 05:00 [ET]
Event Date: 12/22/2017
Event Time: 23:48 [EST]
Last Update Date: 12/23/2017
Notification Time: 05:00 [ET]
Event Date: 12/22/2017
Event Time: 23:48 [EST]
Last Update Date: 12/23/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
BILLY DICKSON (R3DO)
BILLY DICKSON (R3DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
HIGH PRESSURE CORE SPRAY SYSTEM DECLARED INOPERABLE
"High Pressure Core Spray System was declared inoperable due to the discovery of a through-wall leak on the Minimum Flow line. Leak rate is 60 drops per minute from ASME Class 2 Piping. The leak has been isolated and the High Pressure [Core Spray] System has been placed in Secured Status.
"High Pressure Core Spray is considered a single train safety system. Inoperability of [the] High Pressure Core Spray System is considered an event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to mitigate the consequences of an accident.
"This event is being reported in accordance with 10 CFR 50.72(b)(3)(v)(D).
"The NRC Senior Resident Inspector was notified."
Technical Specifications Limiting Condition for Operation 3.5.1 Condition B was entered, requiring restoration of the High Pressure Core Spray System in 14 days.
The licensee plans to notify State and Local Governments (Lake, Geauga, and Ashtabula Counties).
"High Pressure Core Spray System was declared inoperable due to the discovery of a through-wall leak on the Minimum Flow line. Leak rate is 60 drops per minute from ASME Class 2 Piping. The leak has been isolated and the High Pressure [Core Spray] System has been placed in Secured Status.
"High Pressure Core Spray is considered a single train safety system. Inoperability of [the] High Pressure Core Spray System is considered an event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to mitigate the consequences of an accident.
"This event is being reported in accordance with 10 CFR 50.72(b)(3)(v)(D).
"The NRC Senior Resident Inspector was notified."
Technical Specifications Limiting Condition for Operation 3.5.1 Condition B was entered, requiring restoration of the High Pressure Core Spray System in 14 days.
The licensee plans to notify State and Local Governments (Lake, Geauga, and Ashtabula Counties).