Event Number: 52518
Facility: VOGTLE
Region: 2 State: GA
Unit: [1] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: MATTHEW NORRIS
HQ OPS Officer: DONG HWA PARK
Region: 2 State: GA
Unit: [1] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: MATTHEW NORRIS
HQ OPS Officer: DONG HWA PARK
Notification Date: 01/30/2017
Notification Time: 14:38 [ET]
Event Date: 01/30/2017
Event Time: 11:43 [EST]
Last Update Date: 01/30/2017
Notification Time: 14:38 [ET]
Event Date: 01/30/2017
Event Time: 11:43 [EST]
Last Update Date: 01/30/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
BRANNEN ADKINS (R2DO)
MICHAEL F. KING (NRR)
BERNARD STAPLETON (IRD)
BRANNEN ADKINS (R2DO)
MICHAEL F. KING (NRR)
BERNARD STAPLETON (IRD)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
OFFSITE NOTIFICATION DUE TO ONSITE FATALITY
"At approximately 1049 EST, an individual was discovered to be unresponsive at a site training facility outside of the Protected Area. The individual was transported via ambulance to the Burke County Hospital and was declared deceased at 1143 EST.
"The licensee has notified the NRC Resident Inspector. The licensee notified the State of Georgia Department of Labor - OSHA at 1414 EST."
"At approximately 1049 EST, an individual was discovered to be unresponsive at a site training facility outside of the Protected Area. The individual was transported via ambulance to the Burke County Hospital and was declared deceased at 1143 EST.
"The licensee has notified the NRC Resident Inspector. The licensee notified the State of Georgia Department of Labor - OSHA at 1414 EST."
Power Reactor
Event Number: 52519
Facility: LASALLE
Region: 3 State: IL
Unit: [] [2] []
RX Type: [1] GE-5,[2] GE-5
NRC Notified By: WAYNE CLAYTON
HQ OPS Officer: DONG HWA PARK
Region: 3 State: IL
Unit: [] [2] []
RX Type: [1] GE-5,[2] GE-5
NRC Notified By: WAYNE CLAYTON
HQ OPS Officer: DONG HWA PARK
Notification Date: 01/30/2017
Notification Time: 23:34 [ET]
Event Date: 01/30/2017
Event Time: 19:08 [CST]
Last Update Date: 01/30/2017
Notification Time: 23:34 [ET]
Event Date: 01/30/2017
Event Time: 19:08 [CST]
Last Update Date: 01/30/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
ERIC DUNCAN (R3DO)
ERIC DUNCAN (R3DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | Y | 98 | Power Operation | 98 | Power Operation |
ONE DIVISION EMERGENCY DIESEL GENERATOR COOLING WATER SYSTEM DECLARED INOPERABLE
"This report is being made pursuant to 10 CFR 50.72(b)(3)(v)(D), event or condition that could have prevented fulfillment of a safety function needed to mitigate the consequences of an accident. During routine surveillance testing of the Unit 2 Division 3 Emergency Diesel Generator (LOS-DG-M3), the Cooling Water Strainer Backwash Valve, 2E22-F319, was identified to have stem/disk separation and could not be opened.
"This condition has been evaluated and the Division 3 Diesel Generator Cooling Water system has been declared inoperable. The Division 3 Diesel Generator Cooling Water system is a support system for the Division 3 Emergency Diesel Generator and the High Pressure Core Spray System (HPCS). The required actions of Technical Specification (TS) 3.5.1 were entered on 1/30/17 at 1908 CST when the HPCS system was determined to be inoperable.
"This condition could have prevented the HPCS, a single train safety system, from performing its design function."
The licensee has notified the NRC Resident Inspector.
"This report is being made pursuant to 10 CFR 50.72(b)(3)(v)(D), event or condition that could have prevented fulfillment of a safety function needed to mitigate the consequences of an accident. During routine surveillance testing of the Unit 2 Division 3 Emergency Diesel Generator (LOS-DG-M3), the Cooling Water Strainer Backwash Valve, 2E22-F319, was identified to have stem/disk separation and could not be opened.
"This condition has been evaluated and the Division 3 Diesel Generator Cooling Water system has been declared inoperable. The Division 3 Diesel Generator Cooling Water system is a support system for the Division 3 Emergency Diesel Generator and the High Pressure Core Spray System (HPCS). The required actions of Technical Specification (TS) 3.5.1 were entered on 1/30/17 at 1908 CST when the HPCS system was determined to be inoperable.
"This condition could have prevented the HPCS, a single train safety system, from performing its design function."
The licensee has notified the NRC Resident Inspector.
Agreement State
Event Number: 52521
Rep Org: OK DEQ RAD MANAGEMENT
Licensee: NDE SOLUTIONS, LLC
Region: 4
City: BRYAN State: TX
County:
License #: L05879
Agreement: Y
Docket:
NRC Notified By: KEVIN SAMPSON
HQ OPS Officer: DONG HWA PARK
Licensee: NDE SOLUTIONS, LLC
Region: 4
City: BRYAN State: TX
County:
License #: L05879
Agreement: Y
Docket:
NRC Notified By: KEVIN SAMPSON
HQ OPS Officer: DONG HWA PARK
Notification Date: 01/31/2017
Notification Time: 15:05 [ET]
Event Date: 01/30/2017
Event Time: 00:00 [CST]
Last Update Date: 01/31/2017
Notification Time: 15:05 [ET]
Event Date: 01/30/2017
Event Time: 00:00 [CST]
Last Update Date: 01/31/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
GEOFFREY MILLER (R4DO)
NMSS_EVENTS_NOTIFIC (EMAI)
GEOFFREY MILLER (R4DO)
NMSS_EVENTS_NOTIFIC (EMAI)
AGREEMENT STATE REPORT - RADIOGRAPHY CAMERA MALFUNCTION
The following report was received via e-mail:
"We [Oklahoma Department of Environmental Quality] have just been informed of an incident which occurred yesterday (1/30/2017) involving the failure of an industrial radiography source to retract. The licensee was NDE Solutions, LLC (TX license L05879) operating out of Bryan, TX. The incident occurred at a temporary job site near Checotah, OK. The licensee was working in Oklahoma under reciprocity. According to the report the drive cable failed, it isn't clear whether the source just wouldn't retract or became disconnected. The source was retrieved yesterday. The drive cable has been removed from service and is being returned to Texas."
The following report was received via e-mail:
"We [Oklahoma Department of Environmental Quality] have just been informed of an incident which occurred yesterday (1/30/2017) involving the failure of an industrial radiography source to retract. The licensee was NDE Solutions, LLC (TX license L05879) operating out of Bryan, TX. The incident occurred at a temporary job site near Checotah, OK. The licensee was working in Oklahoma under reciprocity. According to the report the drive cable failed, it isn't clear whether the source just wouldn't retract or became disconnected. The source was retrieved yesterday. The drive cable has been removed from service and is being returned to Texas."