Facility: DUANE ARNOLD
Region: 3 State: IA
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: MARK DICKERSON
HQ OPS Officer: STEVEN VITTO
Region: 3 State: IA
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: MARK DICKERSON
HQ OPS Officer: STEVEN VITTO
Notification Date: 01/26/2017
Notification Time: 11:26 [ET]
Event Date: 01/26/2017
Event Time: 03:00 [CST]
Last Update Date: 01/26/2017
Notification Time: 11:26 [ET]
Event Date: 01/26/2017
Event Time: 03:00 [CST]
Last Update Date: 01/26/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(C) - POT UNCNTRL RAD REL
10 CFR Section:
50.72(b)(3)(v)(C) - POT UNCNTRL RAD REL
Person (Organization):
KENNETH RIEMER (R3DO)
KENNETH RIEMER (R3DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
CONTAINMENT VALVES FAILED SURVEILLANCE TESTING
"On January 25, 2017, at 1800 CST, during planned surveillance testing, the Drywell Vent Line Inboard Isolation valve, CV-4302, was found to exceed its valve leakage limits and was declared inoperable. After completion of repairs to CV-4302, post maintenance testing showed that the Drywell Vent Line Outboard Isolation valve, CV-4303, was exceeding its valve leakage limits, and therefore, was declared inoperable at 0300 CST on January 26, 2017. This resulted in a containment penetration flow path not within purge valve leakage limits and is reportable in accordance with 10 CFR 50.72(b)(3)(v)(C).
"Repairs were completed on CV-4303 and both containment valves were declared operable at 1007 CST on January 26, 2017. Secondary Containment was operable at all times.
"The NRC Resident Inspector has been informed."
"On January 25, 2017, at 1800 CST, during planned surveillance testing, the Drywell Vent Line Inboard Isolation valve, CV-4302, was found to exceed its valve leakage limits and was declared inoperable. After completion of repairs to CV-4302, post maintenance testing showed that the Drywell Vent Line Outboard Isolation valve, CV-4303, was exceeding its valve leakage limits, and therefore, was declared inoperable at 0300 CST on January 26, 2017. This resulted in a containment penetration flow path not within purge valve leakage limits and is reportable in accordance with 10 CFR 50.72(b)(3)(v)(C).
"Repairs were completed on CV-4303 and both containment valves were declared operable at 1007 CST on January 26, 2017. Secondary Containment was operable at all times.
"The NRC Resident Inspector has been informed."