Skip to main content

Event Notification Report for January 09, 2017

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/08/2017 - 01/09/2017

EVENT NUMBERS
524785247953209

Power Reactor
Event Number: 52478
Facility: PEACH BOTTOM
Region: 1     State: PA
Unit: [2] [3] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: MIKE SCHWEIGLER
HQ OPS Officer: STEVEN VITTO
Notification Date: 01/09/2017
Notification Time: 16:56 [ET]
Event Date: 01/09/2017
Event Time: 15:30 [EST]
Last Update Date: 01/09/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION 50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
ANTHONY DIMITRIADIS (R1DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
3 N Y 100 Power Operation 100 Power Operation
Event Text
EMERGENCY DIESEL GENERATORS NON-CONFORMING WITH LICENSING BASIS FOR TORNADO GENERATED MISSILES

"On January 9, 2017, during evaluation of protection for Technical Specification (TS) equipment from the damaging effects of tornado generated missiles, Peach Bottom Atomic Power Station identified a non-conforming condition in the plant design such that specific TS equipment is considered to not be adequately protected from tornado generated missiles. A tornado could generate multiple missiles that could strike one or more of the four emergency diesel generator (EDG) exhaust stacks. This could result in crimping of the stack, which could affect the ability of the EDG to perform its design function if such a tornado would occur.

"This condition is reportable per 10 CFR 50.72(b)(3)(ii)(B) for any event or condition that results in the nuclear power plant being in an unanalyzed condition that significantly degrades plant safety, and per 10 CFR 50.72(b)(3)(v)(D) for any event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to mitigate the consequences of an accident.

"This condition is being addressed in accordance with NRC enforcement guidance provided in EGM 15-002 and DSS-ISG-2016-01. Compensatory measures have been implemented in accordance with these documents.

"The NRC Resident Inspector has been informed of this notification."


Research Reactor
Event Number: 52479
Rep Org: UNIV OF MISSOURI-COLUMBIA
Licensee: UNIVERSITY OF MISSOURI
Region: 0
City: COLUMBIA   State: MO
County: BOONE
License #: R-103
Agreement: N
Docket: 05000186
NRC Notified By: BRUCE MEFFERT
HQ OPS Officer: JEFF HERRERA
Notification Date: 01/10/2017
Notification Time: 09:56 [ET]
Event Date: 01/09/2017
Event Time: 00:00 [CST]
Last Update Date: 01/10/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
GEOFFREY WERTZ (RTRP)
ANTHONY MENDIOLA (PROB)
Event Text
ABNORMAL OCCURRENCE DURING MOVEMENT OF A REGULATING BLADE

On Jan 09, 2017, during movement of a reactor regulating blade, an expected annunciator did not occur. This required entry into Technical Specification 3.2.F.8. The rod run in relay and contact block were replaced and the system tested satisfactorily. Technical Specification 3.2.F.8 was subsequently exited.

The licensee will be notifying the Research and Test Reactor Project Manager.


Agreement State
Event Number: 53209
Rep Org: PA BUREAU OF RADIATION PROTECTION
Licensee: RADIOCAT
Region: 1
City: PITTSBURGH   State: PA
County:
License #: PA-1060
Agreement: Y
Docket:
NRC Notified By: DAVID ALLARD
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 02/14/2018
Notification Time: 14:56 [ET]
Event Date: 01/09/2017
Event Time: 00:00 [EST]
Last Update Date: 02/14/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
FRED BOWER (R1DO)
NMSS_EVENTS_NOTIFICA (EMAI)
Event Text
AGREEMENT STATE REPORT - IODINE-131 SPILL

The following report was received via fax:

"On February 13, 2018, during a routine inspection, the licensee informed the Department [Pennsylvania Department of Environmental Protection] of a contamination event that occurred on January 9, 2017 (over a year earlier). The event is reportable under 10 CFR 30.50 (b)(1)(i).

"On January 9, 2017, during a routine injection of 5 milliCuries of iodine-I31 (l-131) into a feline, the needle was removed before the injection was complete, resulting in a spill of I-131 onto the fur of the animal. The spill was not noticed until the animal was being relocated from the injection table to the isolation cage. This resulted in contamination of the technician's skin, clothing, and shoes, and the floor of the injection room. The technician immediately decontaminated her skin, and placed the contaminated clothing into a plastic bag for decay. It was estimated by the licensee she received a skin dose of 1 millirem. The floor of the room was decontaminated and access to the room was restricted over the period of a week until decontamination was complete. All surrounding areas and personnel were monitored and no other contamination was discovered.

"The Department [Pennsylvania Department of Environmental Protection] plans to have a 'call for conference' with the licensee and issue violations regarding this event. More information will be provided as received."

Pennsylvania report: PA180004

A Medical Event may indicate potential problems in a medical facility's use of radioactive materials. It does not necessarily result in harm to the patient.