Skip to main content

Event Notification Report for February 20, 2016

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
02/19/2016 - 02/20/2016

EVENT NUMBERS
5174751816

Power Reactor
Event Number: 51747
Facility: CALVERT CLIFFS
Region: 1     State: MD
Unit: [1] [] []
RX Type: [1] CE,[2] CE
NRC Notified By: ERVIN LYSON
HQ OPS Officer: HOWIE CROUCH
Notification Date: 02/20/2016
Notification Time: 09:12 [ET]
Event Date: 02/20/2016
Event Time: 03:30 [EST]
Last Update Date: 02/20/2016
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(A) - DEGRADED CONDITION
Person (Organization):
GLENN DENTEL (R1DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Refueling 0 Refueling
Event Text
DEGRADED CONDITION DISCOVERED ON PRESSURIZER SAFETY RELIEF VALVE WELD

"During the CCNPP [Calvert Cliff Nuclear Power Plant] Unit 1 Refueling, [an ultrasonic test] examination of the Unit 1 dissimilar metal weld (DMW) of the pressurizer safety relief valve RV-201 safe end weld found an indication that is approximately 80 percent though-wall, inside diameter connected axial flaw in weld #4-SR-1006-1.

"This is an ASME Class 1 component and Unit 1 has entered the requirements of Technical Requirements Manual (TRM) 15.4.3.A.

"CCNPP Event #4254."

The licensee has notified the NRC Resident Inspector.


Part 21
Event Number: 51816
Rep Org: UNITED CONTROLS INTERNATIONAL
Licensee: MERSEN
Region: 1
City: NORCROSS   State: GA
County:
License #:
Agreement: Y
Docket:
NRC Notified By: KORINA LOOFT
HQ OPS Officer: DONG HWA PARK
Notification Date: 03/22/2016
Notification Time: 15:11 [ET]
Event Date: 02/20/2016
Event Time: 00:00 [EDT]
Last Update Date: 03/22/2016
Emergency Class: NON EMERGENCY
10 CFR Section:
21.21(d)(3)(i) - DEFECTS AND NONCOMPLIANCE
Person (Organization):
ROBERT DALEY (R3DO)
PART 21/50.55 REACT (EMAI)
Event Text
PART 21 REPORT - DEFECTIVE FUSES

The following information is a synopsis of information received via E-mail:

"On February 20, 2016 United Controls International issued a Return Material Authorization (RMA) request to First Energy - Perry Nuclear Power Plant. The RMA was issued to request the return of general purpose fuses of part number OT15 that were provided to First Energy - Perry Nuclear Power Plant under purchase order 45225736. The customer identified a fuse that had intermittent electrical continuity during resistance checks. The customer performed an evaluation which included dissection of the subject fuse and the cause of the issue was identified as being due to a lack of or inadequate solder connection of the fuse element to the fuse ferrules.

"If you have any questions or wish to discuss this matter or this report, please contact:
Wesley Hickle
Engineering Manager
whickle@unitedcontrols.com
770-496-1406 x 165"