Event Notification Report for October 23, 2014
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
10/22/2014 - 10/23/2014
EVENT NUMBERS
50569505635056050561
Power Reactor
Event Number: 50569
Facility: COLUMBIA GENERATING STATION
Region: 4 State: WA
Unit: [2] [] []
RX Type: [2] GE-5
NRC Notified By: DUANE SALISBURY
HQ OPS Officer: JOHN SHOEMAKER
Region: 4 State: WA
Unit: [2] [] []
RX Type: [2] GE-5
NRC Notified By: DUANE SALISBURY
HQ OPS Officer: JOHN SHOEMAKER
Notification Date: 10/25/2014
Notification Time: 23:41 [ET]
Event Date: 10/23/2014
Event Time: 10:46 [PDT]
Last Update Date: 10/25/2014
Notification Time: 23:41 [ET]
Event Date: 10/23/2014
Event Time: 10:46 [PDT]
Last Update Date: 10/25/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
WAYNE WALKER (R4DO)
WAYNE WALKER (R4DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
TURBINE BUILDING EXHAUST SAMPLE RACK DECLARED NON-FUNCTIONAL
"A planned outage for the Turbine Building Exhaust Air Radiation Indicating Switch (TEA-RIS-13) and the Turbine Building Process Radiation Monitoring Sample Rack (TEA-SR-26) for health inspection was initiated at 1046 PDT on 10/23/14. Due to maintenance retests taking longer than expected and in anticipation of possibly exceeding 72 hours for the planned outage, this event is being reported as a major loss of assessment capability under regulation 10 CFR 50.72(b)(3)(xiii). Compensatory measures have been implemented to obtain radiation readings from the associated effluent release pathway during the outage. Field team assessment function was unaffected and remains available.
"The Resident Inspector will be notified."
"A planned outage for the Turbine Building Exhaust Air Radiation Indicating Switch (TEA-RIS-13) and the Turbine Building Process Radiation Monitoring Sample Rack (TEA-SR-26) for health inspection was initiated at 1046 PDT on 10/23/14. Due to maintenance retests taking longer than expected and in anticipation of possibly exceeding 72 hours for the planned outage, this event is being reported as a major loss of assessment capability under regulation 10 CFR 50.72(b)(3)(xiii). Compensatory measures have been implemented to obtain radiation readings from the associated effluent release pathway during the outage. Field team assessment function was unaffected and remains available.
"The Resident Inspector will be notified."
Power Reactor
Event Number: 50563
Facility: PALO VERDE
Region: 4 State: AZ
Unit: [1] [2] [3]
RX Type: [1] CE,[2] CE,[3] CE
NRC Notified By: FARA ORESHACK
HQ OPS Officer: JOHN SHOEMAKER
Region: 4 State: AZ
Unit: [1] [2] [3]
RX Type: [1] CE,[2] CE,[3] CE
NRC Notified By: FARA ORESHACK
HQ OPS Officer: JOHN SHOEMAKER
Notification Date: 10/23/2014
Notification Time: 18:06 [ET]
Event Date: 10/23/2014
Event Time: 09:38 [MST]
Last Update Date: 10/23/2014
Notification Time: 18:06 [ET]
Event Date: 10/23/2014
Event Time: 09:38 [MST]
Last Update Date: 10/23/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
26.719 - FITNESS FOR DUTY
10 CFR Section:
26.719 - FITNESS FOR DUTY
Person (Organization):
WAYNE WALKER (R4DO)
WAYNE WALKER (R4DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | N | 0 | Defueled | 0 | Defueled |
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
| 3 | N | Y | 100 | Power Operation | 100 | Power Operation |
FITNESS FOR DUTY - NON LICENSED SUPERVISOR FAILED FITNESS FOR DUTY TEST
A non-licensed employee supervisor had a confirmed positive result for alcohol during a random fitness-for-duty test. The employee's access to the plant has been suspended.
The NRC Resident Inspector has been informed.
A non-licensed employee supervisor had a confirmed positive result for alcohol during a random fitness-for-duty test. The employee's access to the plant has been suspended.
The NRC Resident Inspector has been informed.
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 50560
Facility: DUANE ARNOLD
Region: 3 State: IA
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: STEPHEN SPEIRS
HQ OPS Officer: DANIEL MILLS
Region: 3 State: IA
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: STEPHEN SPEIRS
HQ OPS Officer: DANIEL MILLS
Notification Date: 10/23/2014
Notification Time: 09:48 [ET]
Event Date: 10/23/2014
Event Time: 01:07 [CDT]
Last Update Date: 12/17/2014
Notification Time: 09:48 [ET]
Event Date: 10/23/2014
Event Time: 01:07 [CDT]
Last Update Date: 12/17/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(C) - POT UNCNTRL RAD REL
10 CFR Section:
50.72(b)(3)(v)(C) - POT UNCNTRL RAD REL
Person (Organization):
PATTY PELKE (R3DO)
PATTY PELKE (R3DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | N | 0 | Refueling | 0 | Refueling |
SECONDARY CONTAINMENT INOPERABLE DUE TO BOTH AIRLOCK DOORS OPEN SIMULTANEOUSLY
"At 0107 CDT on October 23rd, 2014, both doors in one of the Secondary Containment airlocks were momentarily open concurrently. This occurred during vessel drain down following refueling activities, an Operation with the Potential to Drain the Reactor Vessel (OPDRV), which required Secondary Containment to be operable. The doors being open at the same time resulted in the momentary inoperability of Secondary Containment. One of the doors was immediately closed, and Secondary Containment was restored to an operable status.
"The station [Duane Arnold] has now completed the OPDRV associated with vessel drain down, and Secondary Containment is no longer required to be operable.
"The Resident Inspector has been notified."
* * * RETRACTION FROM BOB MURRELL TO JOHN SHOEMAKER AT 1232 EST ON 12/17/14 * * *
"The purpose of this notification is to retract a previous report made on 10/23/2014, at 0948 [EDT] (EN 50560). Notification of the event to the NRC was initially made as a result of an event where both doors in one of the Secondary Containment airlocks were momentarily open concurrently. This occurred during vessel drain down following refueling activities, an Operation with the Potential to Drain the Reactor Vessel (OPDRV), which required Secondary Containment to be operable. The doors being open at the same time resulted in the momentary inoperability of Secondary Containment. One of the doors was immediately closed, and Secondary Containment was restored to an operable status.
"Subsequent to the initial report, NextEra Energy Duane Arnold (NextEra) has determined that the doors in question were not mechanically degraded such that they were incapable of being closed. A momentary condition of having both secondary containment airlock doors open for a matter of seconds is not an event or condition that could have prevented the fulfillment of a safety. Furthermore, the conduct of OPDRVs during a momentary opening of both secondary containment doors that is immediately rectified does not constitute a condition prohibited by TS.
Therefore, this event is not considered a Safety System Functional Failure or a Condition Prohibited by TS and is not reportable to the NRC as a Licensee Event Report (LER) per 10 CFR 50.73.
The NRC Senior Resident Inspector has been notified.
Notified the R3DO (McCraw).
.
"At 0107 CDT on October 23rd, 2014, both doors in one of the Secondary Containment airlocks were momentarily open concurrently. This occurred during vessel drain down following refueling activities, an Operation with the Potential to Drain the Reactor Vessel (OPDRV), which required Secondary Containment to be operable. The doors being open at the same time resulted in the momentary inoperability of Secondary Containment. One of the doors was immediately closed, and Secondary Containment was restored to an operable status.
"The station [Duane Arnold] has now completed the OPDRV associated with vessel drain down, and Secondary Containment is no longer required to be operable.
"The Resident Inspector has been notified."
* * * RETRACTION FROM BOB MURRELL TO JOHN SHOEMAKER AT 1232 EST ON 12/17/14 * * *
"The purpose of this notification is to retract a previous report made on 10/23/2014, at 0948 [EDT] (EN 50560). Notification of the event to the NRC was initially made as a result of an event where both doors in one of the Secondary Containment airlocks were momentarily open concurrently. This occurred during vessel drain down following refueling activities, an Operation with the Potential to Drain the Reactor Vessel (OPDRV), which required Secondary Containment to be operable. The doors being open at the same time resulted in the momentary inoperability of Secondary Containment. One of the doors was immediately closed, and Secondary Containment was restored to an operable status.
"Subsequent to the initial report, NextEra Energy Duane Arnold (NextEra) has determined that the doors in question were not mechanically degraded such that they were incapable of being closed. A momentary condition of having both secondary containment airlock doors open for a matter of seconds is not an event or condition that could have prevented the fulfillment of a safety. Furthermore, the conduct of OPDRVs during a momentary opening of both secondary containment doors that is immediately rectified does not constitute a condition prohibited by TS.
Therefore, this event is not considered a Safety System Functional Failure or a Condition Prohibited by TS and is not reportable to the NRC as a Licensee Event Report (LER) per 10 CFR 50.73.
The NRC Senior Resident Inspector has been notified.
Notified the R3DO (McCraw).
.
Power Reactor
Event Number: 50561
Facility: GRAND GULF
Region: 4 State: MS
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: DAVE BURRUS
HQ OPS Officer: RICHARD SMITH
Region: 4 State: MS
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: DAVE BURRUS
HQ OPS Officer: RICHARD SMITH
Notification Date: 10/23/2014
Notification Time: 16:11 [ET]
Event Date: 10/23/2014
Event Time: 09:59 [CDT]
Last Update Date: 10/23/2014
Notification Time: 16:11 [ET]
Event Date: 10/23/2014
Event Time: 09:59 [CDT]
Last Update Date: 10/23/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
26.719 - FITNESS FOR DUTY
10 CFR Section:
26.719 - FITNESS FOR DUTY
Person (Organization):
WAYNE WALKER (R4DO)
WAYNE WALKER (R4DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
FITNESS FOR DUTY - EMPLOYEE SUPERVISOR FAILED FITNESS FOR DUTY TEST
A non-licensed employee supervisor had a confirmed positive result for alcohol during a for cause fitness-for-duty test. The employee's access to the plant has been suspended.
The licensee has informed the NRC Resident Inspector.
A non-licensed employee supervisor had a confirmed positive result for alcohol during a for cause fitness-for-duty test. The employee's access to the plant has been suspended.
The licensee has informed the NRC Resident Inspector.