Event Notification Report for June 19, 2014
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
06/18/2014 - 06/19/2014
EVENT NUMBERS
5021850215502115021350229
Agreement State
Event Number: 50218
Rep Org: TEXAS DEPARTMENT OF HEALTH
Licensee: RABA-KISTNER CONSULTANTS
Region: 4
City: AUSTIN State: TX
County:
License #: 01571
Agreement: Y
Docket:
NRC Notified By: CHRIS MOORE
HQ OPS Officer: MARK ABRAMOVITZ
Licensee: RABA-KISTNER CONSULTANTS
Region: 4
City: AUSTIN State: TX
County:
License #: 01571
Agreement: Y
Docket:
NRC Notified By: CHRIS MOORE
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 06/20/2014
Notification Time: 11:11 [ET]
Event Date: 06/19/2014
Event Time: 00:00 [CDT]
Last Update Date: 07/01/2014
Notification Time: 11:11 [ET]
Event Date: 06/19/2014
Event Time: 00:00 [CDT]
Last Update Date: 07/01/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
MICHAEL HAY (R4DO)
FSME EVENTS RESOURCE
MEXICO (E-MA)
MICHAEL HAY (R4DO)
FSME EVENTS RESOURCE
MEXICO (E-MA)
AGREEMENT STATE REPORT - LOST MOISTURE DENSITY GAUGE
The following report was received via e-mail:
"On June 20, 2014, the Agency [Texas Department of Health] was notified by the licensee of the loss of a Humboldt model 5001EZ moisture density gauge, serial #4772, containing a 1.48 GBq (40 mCi) Am-Be source and a 0.3 GBq (8 mCi) Cs-137 source. The licensee stated a technician was working at a job site on June 19, 2014, when he rushed home for a family emergency. He failed to secure the gauge in the back of the truck and he left the tailgate down. The gauge fell off the truck between the job site and his home. The licensee stated they searched the job site and the route taken by the technician."
Texas event: I-9205
* * * UPDATE AT 1040 EDT ON 7/1/2014 FROM IRENE CASARES TO MARK ABRAMOVITZ * * *
The following report was received via e-mail:
"On Saturday June 28, 2014, the gauge was reported, via email from the licensee, as found and the gauge was sent off for any damage identification and leak check. It was reported that the gauge was not damaged and passed the leak check. Two violations were cited."
Notified the R4DO (Hagar), FSME Events Resource (via e-mail) and Mexico (via e-mail)..
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
The following report was received via e-mail:
"On June 20, 2014, the Agency [Texas Department of Health] was notified by the licensee of the loss of a Humboldt model 5001EZ moisture density gauge, serial #4772, containing a 1.48 GBq (40 mCi) Am-Be source and a 0.3 GBq (8 mCi) Cs-137 source. The licensee stated a technician was working at a job site on June 19, 2014, when he rushed home for a family emergency. He failed to secure the gauge in the back of the truck and he left the tailgate down. The gauge fell off the truck between the job site and his home. The licensee stated they searched the job site and the route taken by the technician."
Texas event: I-9205
* * * UPDATE AT 1040 EDT ON 7/1/2014 FROM IRENE CASARES TO MARK ABRAMOVITZ * * *
The following report was received via e-mail:
"On Saturday June 28, 2014, the gauge was reported, via email from the licensee, as found and the gauge was sent off for any damage identification and leak check. It was reported that the gauge was not damaged and passed the leak check. Two violations were cited."
Notified the R4DO (Hagar), FSME Events Resource (via e-mail) and Mexico (via e-mail)..
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Power Reactor
Event Number: 50215
Facility: PRAIRIE ISLAND
Region: 3 State: MN
Unit: [1] [] []
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: STEVE INGALLS
HQ OPS Officer: MARK ABRAMOVITZ
Region: 3 State: MN
Unit: [1] [] []
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: STEVE INGALLS
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 06/20/2014
Notification Time: 01:08 [ET]
Event Date: 06/19/2014
Event Time: 20:35 [CDT]
Last Update Date: 06/20/2014
Notification Time: 01:08 [ET]
Event Date: 06/19/2014
Event Time: 20:35 [CDT]
Last Update Date: 06/20/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(i) - PLANT S/D REQD BY TS
10 CFR Section:
50.72(b)(2)(i) - PLANT S/D REQD BY TS
Person (Organization):
NICK VALOS (R3DO)
NICK VALOS (R3DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 55 | Power Operation |
TECHNICAL SPECIFICATION REQUIRED SHUTDOWN
"At 1435 [CDT] on June 19, 2014 while performing Unit 1 A Train Safeguards Logic Test at power, it was discovered, while testing the Safety Injection Automatic Actuation Relay Logic, that the 1SI-15x, SI RELAY TRAIN A, was not making up the contact to energize 1SI-16x, SI AUX RELAY TRAIN A. As a result, the 8 hour exception for testing allowed under LCO 3.3.2 Condition C no longer applied, and the 6, 12, and 42 hour clocks associated with condition C were entered.
"At 2035 [CDT] on June 19, when the 6 hour time limit to complete Condition C.1 action could not be completed operators began preparation to shutdown Unit 1 to Mode 3 by 0235 on 6/20/14.
"At 2245 [CDT] on June 19, 2014 operators commenced reducing reactor power of Prairie Island Unit 1. As of 0003, June 20, Unit 1 was at 55 percent power and continuing to reduce load.
"This event is reportable per 10CFR50.72(b)(2)(i) - 'The initiation of any nuclear plant shutdown required by the plant's Technical Specification'.
"The protection of the health and safety of the public is not affected by this issue.
"The NRC Resident Inspector has been notified."
"At 1435 [CDT] on June 19, 2014 while performing Unit 1 A Train Safeguards Logic Test at power, it was discovered, while testing the Safety Injection Automatic Actuation Relay Logic, that the 1SI-15x, SI RELAY TRAIN A, was not making up the contact to energize 1SI-16x, SI AUX RELAY TRAIN A. As a result, the 8 hour exception for testing allowed under LCO 3.3.2 Condition C no longer applied, and the 6, 12, and 42 hour clocks associated with condition C were entered.
"At 2035 [CDT] on June 19, when the 6 hour time limit to complete Condition C.1 action could not be completed operators began preparation to shutdown Unit 1 to Mode 3 by 0235 on 6/20/14.
"At 2245 [CDT] on June 19, 2014 operators commenced reducing reactor power of Prairie Island Unit 1. As of 0003, June 20, Unit 1 was at 55 percent power and continuing to reduce load.
"This event is reportable per 10CFR50.72(b)(2)(i) - 'The initiation of any nuclear plant shutdown required by the plant's Technical Specification'.
"The protection of the health and safety of the public is not affected by this issue.
"The NRC Resident Inspector has been notified."
Power Reactor
Event Number: 50211
Facility: MILLSTONE
Region: 1 State: CT
Unit: [] [] [3]
RX Type: [1] GE-3,[2] CE,[3] W-4-LP
NRC Notified By: JOHN SALVATORE
HQ OPS Officer: JOHN SHOEMAKER
Region: 1 State: CT
Unit: [] [] [3]
RX Type: [1] GE-3,[2] CE,[3] W-4-LP
NRC Notified By: JOHN SALVATORE
HQ OPS Officer: JOHN SHOEMAKER
Notification Date: 06/19/2014
Notification Time: 15:08 [ET]
Event Date: 06/19/2014
Event Time: 08:03 [EDT]
Last Update Date: 06/19/2014
Notification Time: 15:08 [ET]
Event Date: 06/19/2014
Event Time: 08:03 [EDT]
Last Update Date: 06/19/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
BLAKE WELLING (R1DO)
BLAKE WELLING (R1DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 3 | N | Y | 100 | Power Operation | 100 | Power Operation |
PROCESS RADIATION MONITOR MAINTENANCE
"System affected: Normal and High Range SLCRS [Supplementary Leakage Collection and Release System] ventilation process radiation monitors.
"Actuations and their initiation signals: None.
"Causes: Removed from service for scheduled maintenance.
"Effect of event on plant: None.
"Actions taken or planned: Complete required calibration.
"Additional information: Will be returned to service following maintenance."
The licensee notified the NRC Resident Inspector and applicable State and local agencies.
"System affected: Normal and High Range SLCRS [Supplementary Leakage Collection and Release System] ventilation process radiation monitors.
"Actuations and their initiation signals: None.
"Causes: Removed from service for scheduled maintenance.
"Effect of event on plant: None.
"Actions taken or planned: Complete required calibration.
"Additional information: Will be returned to service following maintenance."
The licensee notified the NRC Resident Inspector and applicable State and local agencies.
Power Reactor
Event Number: 50213
Facility: PERRY
Region: 3 State: OH
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: THOMAS MORSE
HQ OPS Officer: JOHN SHOEMAKER
Region: 3 State: OH
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: THOMAS MORSE
HQ OPS Officer: JOHN SHOEMAKER
Notification Date: 06/19/2014
Notification Time: 17:06 [ET]
Event Date: 06/19/2014
Event Time: 16:28 [EDT]
Last Update Date: 06/19/2014
Notification Time: 17:06 [ET]
Event Date: 06/19/2014
Event Time: 16:28 [EDT]
Last Update Date: 06/19/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
NICK VALOS (R3DO)
NICK VALOS (R3DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
UNANALYZED CONDITION DUE TO A POSTULATED HOT SHORT THAT COULD AFFECT SAFE SHUTDOWN EQUIPMENT
"A review of industry operating experience regarding the impact of unfused Direct Current (DC) circuits has determined the described condition to be applicable to the Perry Nuclear Power Plant (PNPP) resulting in an unanalyzed condition with respect to fire safe shutdown requirements.
"In the postulated event, a fire induced hot short could adversely impact safe shutdown equipment. The potential exists for a secondary fire to occur due to unfused DC control circuits associated with the Turbine Emergency Bearing Oil Pump, Reactor Feed Pump Turbine 'A' Emergency Lube Oil Pump, Turbine Emergency Seal Oil Pump, and Reactor Feed Pump Turbine 'B' Emergency Lube Oil Pump. These circuits are routed from the respective equipment to other plant areas including the Unit 1 Control Room, Division 1 Cable Spreading, and Division 1 Cable Chase.
"Without overcurrent protection for these circuits, the potential exists that an initial fire event affecting these circuits could cause short circuits without protection that would cause excessive current through the circuit beyond the capacity rating of the conductors. This could lead to a secondary fire in another plant area where these circuits are routed challenging the ability to achieve and maintain safe shutdown.
"This condition is being reported in accordance with 10 CFR 50.72(b)(3)(ii)(B). Interim compensatory measures (i.e., fire watches) have been implemented for affected areas of the plant.
"The licensee has notified the NRC Resident Inspector."
"A review of industry operating experience regarding the impact of unfused Direct Current (DC) circuits has determined the described condition to be applicable to the Perry Nuclear Power Plant (PNPP) resulting in an unanalyzed condition with respect to fire safe shutdown requirements.
"In the postulated event, a fire induced hot short could adversely impact safe shutdown equipment. The potential exists for a secondary fire to occur due to unfused DC control circuits associated with the Turbine Emergency Bearing Oil Pump, Reactor Feed Pump Turbine 'A' Emergency Lube Oil Pump, Turbine Emergency Seal Oil Pump, and Reactor Feed Pump Turbine 'B' Emergency Lube Oil Pump. These circuits are routed from the respective equipment to other plant areas including the Unit 1 Control Room, Division 1 Cable Spreading, and Division 1 Cable Chase.
"Without overcurrent protection for these circuits, the potential exists that an initial fire event affecting these circuits could cause short circuits without protection that would cause excessive current through the circuit beyond the capacity rating of the conductors. This could lead to a secondary fire in another plant area where these circuits are routed challenging the ability to achieve and maintain safe shutdown.
"This condition is being reported in accordance with 10 CFR 50.72(b)(3)(ii)(B). Interim compensatory measures (i.e., fire watches) have been implemented for affected areas of the plant.
"The licensee has notified the NRC Resident Inspector."
Power Reactor
Event Number: 50229
Facility: SUMMER
Region: 2 State: SC
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-AP1000,[3] W-AP1000
NRC Notified By: WILLIAM TAYLOR
HQ OPS Officer: STEVE SANDIN
Region: 2 State: SC
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-AP1000,[3] W-AP1000
NRC Notified By: WILLIAM TAYLOR
HQ OPS Officer: STEVE SANDIN
Notification Date: 06/26/2014
Notification Time: 15:15 [ET]
Event Date: 06/19/2014
Event Time: 11:45 [EDT]
Last Update Date: 06/26/2014
Notification Time: 15:15 [ET]
Event Date: 06/19/2014
Event Time: 11:45 [EDT]
Last Update Date: 06/26/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(ii) - LOST/STOLEN LNM>10X
10 CFR Section:
20.2201(a)(1)(ii) - LOST/STOLEN LNM>10X
Person (Organization):
DANIEL RICH (R2DO)
DANIEL RICH (R2DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
ONE INCORE DETECTOR CONTAINING U-235 UNACCOUNTED FOR DURING INVENTORY
"This is a non-emergency notification regarding a very small amount of Special Nuclear Material (SNM) which is unaccounted for. On May 30, 2014, a discrepancy was found in the V.C. Summer Nuclear Station SNM inventory. After extensive review, it was determined on June 19, 2014 that one nuclear instrumentation incore detector could not be located at V.C. Summer Nuclear Station. Detectors of this type are used to measure incore neutron flux (intensity of neutron radiation) inside the reactor vessel. This is being reported under 10 CFR 20.2201 (a)(1)(ii) Reports of Theft or Loss of Licensed Material.
"According to V.C. Summer documentation, there should be 42 such detectors in storage. Only 41 detectors could be physically located. There is no evidence of theft or diversion of the detector. Detectors of this type contain very small amounts of Uranium-235 (.0041 grams/detector), which qualifies them as SNM. The detector is believed to be located in a storage location in the Reactor Building (RB). The RB storage location will be inspected during the next refueling outage.
"This event had no effect on plant operations. No impact on public health and safety has been identified. A written report will be made in accordance with 10 CFR 20.2201(b)(1)(i-vi).
"The NRC Resident Inspector has been notified by the licensee."
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
"This is a non-emergency notification regarding a very small amount of Special Nuclear Material (SNM) which is unaccounted for. On May 30, 2014, a discrepancy was found in the V.C. Summer Nuclear Station SNM inventory. After extensive review, it was determined on June 19, 2014 that one nuclear instrumentation incore detector could not be located at V.C. Summer Nuclear Station. Detectors of this type are used to measure incore neutron flux (intensity of neutron radiation) inside the reactor vessel. This is being reported under 10 CFR 20.2201 (a)(1)(ii) Reports of Theft or Loss of Licensed Material.
"According to V.C. Summer documentation, there should be 42 such detectors in storage. Only 41 detectors could be physically located. There is no evidence of theft or diversion of the detector. Detectors of this type contain very small amounts of Uranium-235 (.0041 grams/detector), which qualifies them as SNM. The detector is believed to be located in a storage location in the Reactor Building (RB). The RB storage location will be inspected during the next refueling outage.
"This event had no effect on plant operations. No impact on public health and safety has been identified. A written report will be made in accordance with 10 CFR 20.2201(b)(1)(i-vi).
"The NRC Resident Inspector has been notified by the licensee."
THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf