Skip to main content

Event Notification Report for June 10, 2014

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
06/09/2014 - 06/10/2014

EVENT NUMBERS
5018550187501885019350183

Power Reactor
Event Number: 50185
Facility: PEACH BOTTOM
Region: 1     State: PA
Unit: [2] [3] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: CAMERON CAMPBELL
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 06/10/2014
Notification Time: 19:38 [ET]
Event Date: 06/10/2014
Event Time: 16:00 [EDT]
Last Update Date: 06/10/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
GLENN DENTEL (R1DO)
JEFFERY GRANT (IRD)
JACK DAVIS (NRR)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
3 N Y 100 Power Operation 100 Power Operation
Event Text
OFFSITE NOTIFICATION - NON-WORK RELATED ON-SITE FATALITY

"At 1600 EDT on June 10, 2014, a non-work related on-site fatality as a result of natural causes occurred at the Peach Bottom Atomic Power Station. The fatality was not related to the health and safety of the public or on-site personnel. Specifically, a contract truck driver was found non-responsive in a truck in the parking lot.

"The individual was outside of the Radiological Controlled Area and no radioactive material or contamination was involved. The location of the parking lot is outside of the Protected Area but within the owner controlled area.

"An Event of Potential Public Interest has been completed. Peach Bottom Atomic Power Station will make notifications due to a fatality on-site. This ENS notification is in response to a notification to another government agency in accordance with 10CFR50.72(b)(2)(xi).

"The licensee notified the NRC Resident Inspector."

The licensee notified the Emergency Management Agencies in Pennsylvania and Maryland, the Pennsylvania State Police, as well as the surrounding counties.


Power Reactor
Event Number: 50187
Facility: NINE MILE POINT
Region: 1     State: NY
Unit: [] [2] []
RX Type: [1] GE-2,[2] GE-5
NRC Notified By: PATRICK WALSH
HQ OPS Officer: DONG HWA PARK
Notification Date: 06/11/2014
Notification Time: 00:23 [ET]
Event Date: 06/10/2014
Event Time: 20:32 [EDT]
Last Update Date: 06/11/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(C) - POT UNCNTRL RAD REL
Person (Organization):
GLENN DENTEL (R1DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
SECONDARY CONTAINMENT DECLARED INOPERABLE

"Nine Mile Point Unit 2 Secondary Containment was declared inoperable on 6/10/14 from 2032 EDT until 2036 EDT during the restoration of Reactor Building Ventilation System to a normal lineup.

"While performing actions to restore ventilation fans the Above Refuel Floor Exhaust Fan, 2HVR-FN5A, tripped when started resulting in building differential pressure becoming less negative than -0.25 inches. Tech Spec 3.6.4.1 Secondary Containment, Action A.1 to restore within 4 hours was entered at 2032 EDT on 6/10/14.

"The standby Above Refuel Floor Exhaust Fan, 2HVR-FN5B, was started per procedure and building differential pressure was restored. Secondary Containment was declared operable at 2036 EDT on 6/10/14 and Tech Spec 3.6.4.1 action was exited.

"Secondary containment being inoperable is a 8-hour report for 10 CFR 50.72(b)(3)(v)(c), Any event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to control the release of radioactive material."

The licensee has notified the NRC Resident Inspector and will notify the State of New York.


Power Reactor
Event Number: 50188
Facility: COOK
Region: 3     State: MI
Unit: [1] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: DEAN BRUCK
HQ OPS Officer: DONG HWA PARK
Notification Date: 06/11/2014
Notification Time: 01:23 [ET]
Event Date: 06/10/2014
Event Time: 23:27 [EDT]
Last Update Date: 06/11/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
ROBERT DALEY (R3DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
OFFSITE NOTIFICATION DUE TO AN INADVERTENT ACTIVATION OF AN EMERGENCY SIREN

"On 6/10/14 at approximately 2327 EDT, the Operations Shift Manager was made aware that the Berrien County Sheriffs Department (BCSD) had been notified of an Emergency Siren that had actuated. BCSD was notified by local residents. BCSD reset the emergency siren and a local police officer verified the siren was no longer actuating.

"The cause of the actuation is under investigation at this time. The siren remains in service pending further investigation. There are a total of 70 sirens and all remain functional.

"This notification is being made under 10 CFR 50.72(b)(2)(xi), Offsite Notification, as a four (4) hour report.

"The licensee has notified the NRC Resident Inspector."


Agreement State
Event Number: 50193
Rep Org: ILLINOIS EMERGENCY MGMT. AGENCY
Licensee: NORTHWEST COMMUNITY HOSPITAL
Region: 3
City: ARLINGTON HEIGHTS   State: IL
County:
License #: IL-01094-01
Agreement: Y
Docket:
NRC Notified By: DAREN PERRERO
HQ OPS Officer: CHARLES TEAL
Notification Date: 06/12/2014
Notification Time: 11:30 [ET]
Event Date: 06/10/2014
Event Time: 00:00 [CDT]
Last Update Date: 06/12/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
ROBERT DALEY (R3DO)
FSME EVENT RESOURCE (EMAI)
Event Text
AGREEMENT STATE REPORT - PATIENT RECEIVED LESS THAN PRESCRIBED DOSE

The following information was received via email from the State of Illinois:

"On June 11, the Radiation Safety Officer/Medical Physicist for Northwest Community Hospital in Arlington Heights, IL called to report a medical event. The previous morning a patient was to be administered approximately 38 milliCi of Y-90 labeled microspheres for treatment of liver cancer in the left lobe of the liver via the hepatic artery. Instead, approximately only 21 milliCi was delivered. Post treatment measurements of the delivery system showed substantially elevated readings at the catheter/vial interface suggesting either blockage or perhaps improper flow allowing the microspheres to coagulate. The physician is considering an increase in dosage for the patient's second treatment which is scheduled in two to three weeks in order that the ideal dose be delivered. However, if that cannot be accomplished, the interventional radiologist does not believe the patient's health to be adversely affected by the under dose. A written report of the event from the licensee is pending at this time."

IL Report Number: IL-14010

A Medical Event may indicate potential problems in a medical facility's use of radioactive materials. It does not necessarily result in harm to the patient.


Power Reactor
Event Number: 50183
Facility: LASALLE
Region: 3     State: IL
Unit: [1] [2] []
RX Type: [1] GE-5,[2] GE-5
NRC Notified By: JASON DePRIEST
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 06/10/2014
Notification Time: 16:25 [ET]
Event Date: 06/10/2014
Event Time: 07:12 [CDT]
Last Update Date: 06/10/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
26.719 - FITNESS FOR DUTY
Person (Organization):
ROBERT DALEY (R3DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
FITNESS FOR DUTY

A non-licensed employee supervisor had a confirmed positive for alcohol during a for-cause fitness-for-duty test. The employee's access to the plant has been suspended.

The licensee notified the NRC Resident Inspector and the Regional Safeguards Inspector.