Event Number: 49862
Facility: FARLEY
Region: 2     State: AL
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: CHARLES BAREFIELD
HQ OPS Officer: JEFF ROTTON
Notification Date: 02/28/2014
Notification Time: 11:02 [ET]
Event Date: 02/28/2014
Event Time: 08:42 [CST]
Last Update Date: 02/28/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
GERALD MCCOY (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
PYRO PANEL REMOVED FROM SERVICE FOR MAINTENANCE

"At 0842 CST on February 28, 2014, the Unit 1 Pyro Panel (fire/smoke detection panel) was removed from service for required maintenance. The Pyro Panel was declared non-functional when it was removed from service. Compensatory measures have been established for all affected areas except the Unit 1 Containment Building. Since a fire in the Containment Building is an entry condition for the site's Emergency Plan, this is considered a loss of emergency assessment capability and is being reported per 10CFR50.72(b)(3)(xiii). Containment temperature is being monitored while the pyro panel is out of service, however this is not considered a satisfactory compensatory measure for maintaining effective assessment capability. A courtesy follow up notification will be sent when the pyro panel is returned to service and functional.

"The NRC Resident Inspector has been informed."

* * * UPDATE FROM RICHARD LULLING TO CHARLES TEAL AT 2215 EST ON 2/28/14 * * *

"At 1704 CST on 2/28/2014 the Unit 1 Pyro Panel was declared functional following the return of the fire indicating unit (FIU) to the original status. The Pyro Panel fire detection system was successfully tested following the maintenance. The emergency assessment capability for the site's Emergency Plan has been fully restored concerning a containment fire.

"The Senior NRC Resident Inspector has been informed."

Notified R2DO (McCoy).