Skip to main content

Event Notification Report for December 12, 2013

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
12/11/2013 - 12/12/2013

EVENT NUMBERS
4962652838

Power Reactor
Event Number: 49626
Facility: COLUMBIA GENERATING STATION
Region: 4     State: WA
Unit: [2] [] []
RX Type: [2] GE-5
NRC Notified By: QUOC VO
HQ OPS Officer: HOWIE CROUCH
Notification Date: 12/12/2013
Notification Time: 12:44 [ET]
Event Date: 12/12/2013
Event Time: 04:36 [PST]
Last Update Date: 12/13/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
GREG WERNER (R4DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
BOTH TRAINS OF PRIMARY CONTAINMENT HYDROGEN AND OXYGEN MONITORS OUT OF SERVICE FOR MAINTENANCE

"This notification is being made due to a loss of emergency assessment capability in accordance with 10 CFR 50.72(b)(3)(xiii). At 0436 (PST), on 12/12/2013 the Division 1 sample rack for monitoring primary containment oxygen and hydrogen atmospheric concentrations was removed from service for planned maintenance activities. The Division 1 sample rack is expected to be out of service for 14 hours. The redundant Division 2 sample rack was previously removed from service for maintenance and remains out of service for repairs. Compensatory measures to monitor primary containment for hydrogen and oxygen are available via grab samples using chemistry procedures."

The licensee has notified the NRC Resident Inspector.

* * * UPDATE FROM QUOC VO TO HOWIE CROUCH AT 1705 EST ON 12/13/13 * * *

"Following completion of maintenance activities, the Division 1 sample rack for monitoring primary containment oxygen and hydrogen atmospheric concentrations was returned to operable status at 1150 PST on 12/13/2013, restoring its required emergency assessment capability.

"The NRC Resident Inspector has been notified."

Notified R4DO (Walker).


Agreement State
Event Number: 52838
Rep Org: SC DIV OF HEALTH & ENV CONTROL
Licensee: CLEMSON UNIVERSITY
Region: 1
City: CLEMSON   State: SC
County:
License #: 540
Agreement: Y
Docket:
NRC Notified By: ANDREW M. ROXBURGH
HQ OPS Officer: DONG HWA PARK
Notification Date: 07/03/2017
Notification Time: 11:22 [ET]
Event Date: 12/12/2013
Event Time: 00:00 [EDT]
Last Update Date: 07/03/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
RAY POWELL (R1DO)
NMSS_EVENTS_NOTIFICA (EMAI)
Event Text
AGREEMENT STATE REPORT - UNPLANNED CONTAMINATION

The following report was received from the South Carolina Department of Health and Environmental Control via e-mail:

"This event was first reported to the State as an allegation but is now being reported as an incident because of our recent IMPEP [Integrated Materials Performance Evaluation Program] review.

"The unplanned contamination was because of the dissolution of a Po-210 Static Eliminator containing 125 microcuries. The contamination was discovered when a Graduate Research Assistance was surveying himself upon exiting the lab. The RSO was notified and the lab was thoroughly decontaminated. The laboratory was posted and access was restricted. The licensee was required to report this incident within 24 hours of discovery because the unplanned contamination caused a restricted area to be closed for more than 24 hours."