Event Number: 49500
Facility: COOPER
Region: 4     State: NE
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: DAVID NELSON MADSEN
HQ OPS Officer: HOWIE CROUCH
Notification Date: 11/04/2013
Notification Time: 17:01 [ET]
Event Date: 11/05/2013
Event Time: 01:00 [CST]
Last Update Date: 11/05/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
JAMES DRAKE (R4DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
TECHNICAL SUPPORT CENTER OUT OF SERVICE FOR PLANNED MAINTENANCE

"A planned maintenance activity at Cooper Nuclear Station [CNS] will remove the TSC [Technical Support Center] ventilation system from service. The TSC ventilation system will be rendered non-functional during this maintenance period. The maintenance activity on the TSC ventilation is expected to last less than one day.

"If an emergency is declared requiring TSC activation during this period, the TSC will be staffed and activated using existing emergency planning procedures unless uninhabitable due to ambient temperature, radiological, or other conditions. CNS Station procedures provide appropriate monitoring and compensatory measures to ensure habitability of the TSC and, if necessary, instructions for relocation of TSC personnel to alternate TSC facilities, should the need arise. Both of these alternate facilities are equipped with emergency ventilation systems and are currently fully functional. In the event of TSC activation, maintenance will be expedited to restore ventilation to service.

"This notification is being made in accordance with 10 CFR 50.72(b)(3)(xiii) due to the loss of an Emergency Response Facility (ERF). An update will be provided once the TSC ventilation system has been restored to normal operation.

"The licensee has notified the NRC Resident Inspector."

* * * NOTIFIED BY JEREMY SIMS TO JOHN SHOEMAKER AT 1736 EST ON 11/05/2013 * * *

"Cooper Nuclear Station Technical Support Center ventilation system has been restored to service following planned maintenance. The NRC Resident Inspector has been informed."

Notified R4DO (Drake).


Power Reactor
Event Number: 49502
Facility: ROBINSON
Region: 2     State: SC
Unit: [2] [] []
RX Type: [2] W-3-LP
NRC Notified By: GEORGE CURTIS
HQ OPS Officer: BILL HUFFMAN
Notification Date: 11/05/2013
Notification Time: 05:00 [ET]
Event Date: 11/05/2013
Event Time: 00:41 [EST]
Last Update Date: 11/05/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
ALAN BLAMEY (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 0 Startup 0 Startup
Event Text
AUTOMATIC ACTUATION OF THE AUXILIARY FEEDWATER SYSTEM DUE TO MAIN FEED PUMP TRIP

"At 0041 hours [EST] on 11/05/2013, while placing the Condensate Polishers into service, a secondary side perturbation occurred, resulting in a loss of the one running Main Feedwater Pump ('A' Pump) on low suction pressure. At the time, the plant was in Mode 2 with Startup Low Power Physics Testing in progress. By design, this condition resulted in an automatic start of Auxiliary Feedwater. Both 'A' and 'B' Motor-Driven Auxiliary Feedwater (AFW) Pumps started as designed. Steam generator water levels were maintained by the Auxiliary Feedwater flow. The 'B' Motor Driven AFW pump was secured following its automatic start to stabilize steam generator water levels and reactor coolant system temperature. Plant conditions including steam generator water levels have been stabilized. At 0250 hours [EST] 'A' Main Feedwater Pump was restarted and at 0252 hours [EST], the 'A' Motor-Driven AFW pump was secured.

"At this time, the cause of the secondary side perturbation is being investigated. The plant remains in Mode 2 and Startup Low Power Physics Testing has resumed.

"Due to the valid actuation of AFW, this event is being reported as an 8-hour non-emergency per 10CFR50.72(b)(3)(iv)(A). At no time during this occurrence was the public or plant staff at risk as a result of this event.

"The NRC Resident Inspector has been notified."


Power Reactor
Event Number: 49503
Facility: DRESDEN
Region: 3     State: IL
Unit: [] [2] []
RX Type: [1] GE-1,[2] GE-3,[3] GE-3
NRC Notified By: JEFF SIMPSON
HQ OPS Officer: HOWIE CROUCH
Notification Date: 11/05/2013
Notification Time: 15:50 [ET]
Event Date: 11/05/2013
Event Time: 08:42 [CST]
Last Update Date: 11/05/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(C) - POT UNCNTRL RAD REL
Person (Organization):
CHRISTINE LIPA (R3DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 91 Power Operation 91 Power Operation
Event Text
SECONDARY CONTAINMENT DECLARED INOPERABLE DUE TO FAILURE OF INTERLOCK MECHANISM

"At 08:42 [CST] on November 5, 2013, indication was received in the Control Room that two Secondary Containment doors, in one access opening, were opened simultaneously. The interlock mechanism preventing both doors from operating simultaneously did not operate as expected. A worker in the field reported that the Turbine Building side door was opened, and simultaneously the Reactor Building side door opened several inches and then quickly re-closed. This condition represents a failure to meet Surveillance Requirement 3.6.4.1.2. As a result, entry into Technical Specification 3.6.4.1, Condition A, was made momentarily due to Secondary Containment being inoperable. The doors were secured at 08:42 and Secondary Containment was declared Operable. This event is being reported in accordance with 10 CFR 50.72(b)(3)(v)(C) as a condition that could have prevented the fulfillment of a safety function.

"The NRC Resident Inspector has been notified."

See similar events 49153 and 49379. The licensee is tracking the failure as Incident Report 01581320.


Non-Agreement State
Event Number: 49504
Rep Org: US NAVY
Licensee: US NAVY
Region: 1
City: WASHINGTON   State: DC
County:
License #: 42-23645-01NA
Agreement: N
Docket:
NRC Notified By: CAPT. DAVIS-URGO
HQ OPS Officer: HOWIE CROUCH
Notification Date: 11/05/2013
Notification Time: 16:52 [ET]
Event Date: 11/05/2013
Event Time: 00:00 [EST]
Last Update Date: 11/05/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(i) - LOST/STOLEN LNM>1000X
Person (Organization):
JAMES NOGGLE (R1DO)
FSME EVENTS RESOURCE (EMAI)
Event Text
LOST STRONTIUM-90 SOURCE

The U.S. Navy reported the loss of an IBIS (In-flight Blade Inspection System) that contained 500 microCuries of Sr-90. The IBIS was attached to an USMC aircraft, when the co-pilot's window fell off and struck the blade resulting in the loss of the system. The incident occurred approximately 10 kilometers northeast of Naval Air Station Jacksonville.

The licensee has notified their project manager in Region 1 (Seeley).


THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf


Power Reactor
Event Number: 49505
Facility: BEAVER VALLEY
Region: 1     State: PA
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: J A DAUGHERTY
HQ OPS Officer: JOHN SHOEMAKER
Notification Date: 11/05/2013
Notification Time: 19:27 [ET]
Event Date: 11/05/2013
Event Time: 18:28 [EST]
Last Update Date: 11/05/2013
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED 50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
JAMES NOGGLE (R1DO)
DAVID SKEEN (NRR)
JANE MARSHALL (IRD)
WILLIAM DEAN (R1RA)
ERIC LEEDS (NRR)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 M/R Y 47 Power Operation 0 Hot Standby
Event Text
NOTIFICATION OF UNUSUAL EVENT DUE TO EXPLOSION AND FIRE IN THE TURBINE BUILDING

"On 11/5/13 at 1746 [EST], Beaver Valley Unit 1 Generator tripped on 'C' Transformer differential protection. The Unit was at 47%, so an automatic trip of the reactor was not expected. The reactor was tripped manually. Entered E-0 Reactor Trip Response. The Aux Feedwater Turbine Driven Pump automatically started as required and one motor driven pump was manually started.

"At 1748, the control room received report of fire in the Turbine building. The deluge system had actuated and extinguished the fire in the Turbine plant mezzanine. Off-site assistance was staged and available.

"At 1828, an Unusual Event was declared when fire brigade reports indications that an explosion and fire had occurred in a cable tray in the Unit 1 Turbine Mezzanine.

"The [NRC] Resident Inspector was notified of the events that occurred.

"At 1836, NRC [Resident Inspector] was notified of the Unusual Event.

"Cause of the cable tray explosion and fire is being investigated."

The reactor trip was uncomplicated and Unit 1 is stable in mode 3 with decay heat being released to the main condenser. Normal offsite power is available. Unit 2 continues to operate at 100% and there is no impact on the health and safety of the public.

* * * UPDATE FROM J. A. DAUGHERTY TO JOHN SHOEMAKER AT 2005 EST ON 11/05/13 * * *

At 1959 on 11/5/13, the licensee terminated the Unusual Event.

The licensee has notified the NRC Resident Inspector.

Notified the R1DO (Noggle), NRR EO (Skeen), IRD (Marshall). Notified the DHS SWO, FEMA, DHS NICC, and Nuclear SSA via e-mail.


Power Reactor
Event Number: 49506
Facility: ROBINSON
Region: 2     State: SC
Unit: [2] [] []
RX Type: [2] W-3-LP
NRC Notified By: WARREN WONKA
HQ OPS Officer: JOHN SHOEMAKER
Notification Date: 11/05/2013
Notification Time: 21:31 [ET]
Event Date: 11/05/2013
Event Time: 18:00 [EST]
Last Update Date: 11/05/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
ALAN BLAMEY (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 A/R Y 19 Power Operation 0 Hot Standby
Event Text
AUTOMATIC REACTOR TRIP DUE TO MOMENTARY LOSS OF 4 KV BUSES AND SAFETY SYSTEM ACTUATION

"At 1800 hours EST on 11/05/2013, with the unit in Mode 1 at 19% power, an automatic reactor trip occurred. Operators were transferring loads from the Startup Transformer to the Unit Auxiliary Transformer in accordance with normal operating procedures. When breaker 52/7, Unit Aux to 4KV Bus 1 Breaker, was taken to the close position, indication on the Reactor Turbine Generator Board (RTGB) went from 'Open' to 'No' indication. Breaker 52/12, Incoming Line Startup Transformer No. 2, cycled open and then re-closed. This resulted in a momentary loss of power to 4KV Bus 2 and 4KV Bus 1. The reactor trip signal was based on a loss of 4KV bus voltage to 2 of the 3 required 4KV buses. The cause of the loss of 480V bus E-1 was a result of loss of power to 4KV Bus 2. As a result of the loss of 480V bus E-1, the 'A' Emergency Diesel Generator (EDG) auto started. The required loads sequenced onto the 'A' EDG with the exception of the 'A' Service Water (SW) pump. The cause of the failure of the 'A' SW pump is under investigation.

"The one running Main Feedwater Pump ('A' Pump) tripped on the resulting under voltage of 4 kV Bus 1. By design, this condition resulted in an automatic start of Auxiliary Feedwater due to both Main Feed pump breakers being opened. Both 'A' and 'B' Motor-Driven Auxiliary Feedwater (AFW) Pumps started as designed. Steam generator water levels were maintained in the normal operating band.

"Currently, the unit is stable in Hot Standby (Mode 3).

"This event is being reported as a 4 hour Non-Emergency per 10 CFR 50.72(b)(2)(iv)(B) due to the valid Reactor Protection System Actuation

"This event is being reported as an 8 hour Non-Emergency per 10 CFR 50.72(b)(3)(iv)(A) due to the valid actuation of AFW and EDG auto-start and subsequent starting of required under voltage loads.

"At no time during this occurrence was the public or plant staff at risk as a result of this event.

"The [NRC ] Resident Inspector has been notified."

The reactor trip was uncomplicated and the is plant is stable in mode 3 with decay heat being released to the main condenser. Normal offsite power is available with the exception of the 480V bus E-1 being supplied by the "A" Emergency Diesel Generator.


Non-Agreement State
Event Number: 49519
Rep Org: E.I. DUPONT
Licensee: E.I. DUPONT
Region: 1
City: WASHINGTON   State: WV
County:
License #: 47-01876-01
Agreement: N
Docket:
NRC Notified By: RICHARD BONAR
HQ OPS Officer: DONG HWA PARK
Notification Date: 11/08/2013
Notification Time: 11:52 [ET]
Event Date: 11/05/2013
Event Time: 12:30 [EST]
Last Update Date: 11/08/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(ii) - LOST/STOLEN LNM>10X
Person (Organization):
JAMES NOGGLE (R1DO)
FSME EVENTS RESOURCE (EMAI)
ILTAB (EMAI)
Event Text
MISSING NICKEL-63 SOURCE

The licensee called to report a missing 15 milliCurie Nickel-63 source. This source is used in an unknown nuclear device. The licensee believes that the device, which was previously removed from a wall was taken to a scrap metal yard. The licensee has searched the scrap yard and is still searching for the source. The licensee is investigating and will update this report when more information is obtained.

The following was received via email:

"Serial number of 466AN. The plant number for this device is J-128.

"Below is a brief sequence of events:
"06/04/2013 - J-128 was observed mounted in place and a leak test was performed (A035645).

"We [E.I. DuPont] are not sure of the date, but we have evidence that sometime in August maintenance removed the analyzer from the wall to make space for other equipment. There was a clear 'Caution Radioactive Material' label on the front of the unit.

"10/30/2013 - J-128 was verified not in place.
"10/30/2013 - We have pictures of this device. An extensive plant wide search began. This search then intensified to include all metal dumpsters on site, all operating areas, all scrap metal trailers scheduled to go off site, and then off site locations where metal may have been sent. The local scrapyard with acres of storage piles was searched using heavy equipment.
"11/05/2013 - Even with all our efforts to locate the device, we were unable to locate it. On this date our formal investigation began and is ongoing.
"11/08/2013 - Called the NRC to report this incident."

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf


Power Reactor
Event Number: 49515
Facility: SUMMER
Region: 2     State: SC
Unit: [] [2] [3]
RX Type: [1] W-3-LP,[2] W-AP1000,[3] W-AP1000
NRC Notified By: DEAN KERSEY
HQ OPS Officer: DANIEL MILLS
Notification Date: 11/07/2013
Notification Time: 16:05 [ET]
Event Date: 11/05/2013
Event Time: 08:26 [EST]
Last Update Date: 11/07/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
26.417(b)(1) - FFD PROGRAMMATIC FAILURE
Person (Organization):
ALAN BLAMEY (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N N 0 Under Construction 0 Under Construction
3 N N 0 Under Construction 0 Under Construction
Event Text
FITNESS FOR DUTY - VENDING MACHINE MAINTENANCE CONTRACTOR USED ANOTHER WORKER'S BADGE

"On November 7, 2013, at 0826 EST, an investigation determined that a Fitness for Duty (FFD) policy violation as defined in 10 CFR 26.417(b)(1) had occurred in the Chicago Bridge & Iron (CB&I) FFD Program at the South Carolina Electric & Gas (SCE&G) V.C. Summer Units 2 and 3 construction site.

"On November 5, 2013, a CB&I contractor vending machine service employee, in the presence of a CB&I contract security officer, used another contractor vending machine service employee's badge to gain access to the construction site after his badge did not allow access due to being inactivated in an effort to facilitate a random FFD test. The contractor vending machine service employee was escorted out of the construction site.

"Subsequent investigation uncovered that it was a practice within the contractor vending machine service company to maintain an employee's badge in the vehicle and periodically use it to ensure the badge was not deactivated.

"The contractor vending machine service company employee badges have been deactivated pending further investigation. The individuals involved in this event are under 10 CFR 26, Subpart K, and do not perform safety or security related work. This event has been entered in the CB&I and SCE&G Corrective Action Programs for resolution and development of appropriate corrective actions.

"SCE&G is providing this notification in accordance with 10 CFR 26.417(b)(1).

"The NRC Resident Inspector has been notified."