Event Notification Report for October 30, 2013
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
10/29/2013 - 10/30/2013
Agreement State
Event Number: 49587
Rep Org: NEW YORK STATE DEPT. OF HEALTH
Licensee: UNSPECIFIED
Region: 1
City: State: NY
County:
License #:
Agreement: Y
Docket:
NRC Notified By: ROBERT SNYDER
HQ OPS Officer: DONG HWA PARK
Licensee: UNSPECIFIED
Region: 1
City: State: NY
County:
License #:
Agreement: Y
Docket:
NRC Notified By: ROBERT SNYDER
HQ OPS Officer: DONG HWA PARK
Notification Date: 11/27/2013
Notification Time: 10:58 [ET]
Event Date: 10/30/2013
Event Time: 00:00 [EST]
Last Update Date: 11/27/2013
Notification Time: 10:58 [ET]
Event Date: 10/30/2013
Event Time: 00:00 [EST]
Last Update Date: 11/27/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
DAN SCHROEDER (R1DO)
FSME EVENTS RESOURCE (EMAI)
DAN SCHROEDER (R1DO)
FSME EVENTS RESOURCE (EMAI)
AGREEMENT STATE REPORT - RADIOACTIVE SEED INCORRECTLY PLACED ON PATIENT
The following information was received by facsimile:
"Reported to NYS DOH [New York State Department of Health] on 11/12/2013. A patient received two seeds for right breast radioactive seed localization when only one was intended. The patient had two marker clips, a cylinder clip marking a benign biopsy site and a coil clip marking a papilloma. It was intended for her to only receive one seed placed at the papilloma site, but the benign site was marked with a 0.252 mCi iodine-125 seed. A second seed (0.251 mCi) was then placed to mark the correct site. The unintended dose from the 0.252 mCi seed in place for 2 days was 0.61 Gy @ 0.5 cm. Root cause analysis is ongoing."
Event Report Identification Number: NY-13-06
A Medical Event may indicate potential problems in a medical facility's use of radioactive materials. It does not necessarily result in harm to the patient.
The following information was received by facsimile:
"Reported to NYS DOH [New York State Department of Health] on 11/12/2013. A patient received two seeds for right breast radioactive seed localization when only one was intended. The patient had two marker clips, a cylinder clip marking a benign biopsy site and a coil clip marking a papilloma. It was intended for her to only receive one seed placed at the papilloma site, but the benign site was marked with a 0.252 mCi iodine-125 seed. A second seed (0.251 mCi) was then placed to mark the correct site. The unintended dose from the 0.252 mCi seed in place for 2 days was 0.61 Gy @ 0.5 cm. Root cause analysis is ongoing."
Event Report Identification Number: NY-13-06
A Medical Event may indicate potential problems in a medical facility's use of radioactive materials. It does not necessarily result in harm to the patient.
Power Reactor
Event Number: 49486
Facility: COOPER
Region: 4 State: NE
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: BRIAN HASSELBRING
HQ OPS Officer: HOWIE CROUCH
Region: 4 State: NE
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: BRIAN HASSELBRING
HQ OPS Officer: HOWIE CROUCH
Notification Date: 10/30/2013
Notification Time: 16:43 [ET]
Event Date: 10/30/2013
Event Time: 11:17 [CDT]
Last Update Date: 10/30/2013
Notification Time: 16:43 [ET]
Event Date: 10/30/2013
Event Time: 11:17 [CDT]
Last Update Date: 10/30/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
JAMES DRAKE (R4DO)
JAMES DRAKE (R4DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
POSTULATED FIRE EVENT THAT COULD ADVERSELY IMPACT SAFE SHUTDOWN EQUIPMENT
"A review of industry operating experience regarding the impact of unfused Direct Current (DC) ammeter circuits in the control room has determined the described condition to be applicable to the Cooper Nuclear Station resulting in a potentially unanalyzed condition with respect to 10 CFR 50 Appendix R analysis requirements. The original plant wiring design and associated analysis for the Class 1E batteries control room ampere indications do not include overcurrent protection features to limit the fault current.
"In the postulated event, a fire could cause one of the ammeter wires to short to ground. Simultaneously, it is postulated that the fire causes another DC wire from the opposite polarity on the same battery to also short to ground. This could cause a ground loop through the unprotected ammeter wiring. This event could result in excessive current flow (i.e., heating) in the ammeter wiring to the point of causing a secondary fire in the raceway system. The secondary fire could adversely affect safe shutdown equipment and potentially cause the loss of the ability to conduct a safe shutdown as required by 10 CFR. 50 Appendix R.
"This condition is being reported in accordance with 10 CFR 50.72(b)(3)(ii)(B). Interim compensatory measures (i.e.., fire watches) have been implemented for affected areas of the plant.
"The licensee has notified the NRC Resident Inspector."
"A review of industry operating experience regarding the impact of unfused Direct Current (DC) ammeter circuits in the control room has determined the described condition to be applicable to the Cooper Nuclear Station resulting in a potentially unanalyzed condition with respect to 10 CFR 50 Appendix R analysis requirements. The original plant wiring design and associated analysis for the Class 1E batteries control room ampere indications do not include overcurrent protection features to limit the fault current.
"In the postulated event, a fire could cause one of the ammeter wires to short to ground. Simultaneously, it is postulated that the fire causes another DC wire from the opposite polarity on the same battery to also short to ground. This could cause a ground loop through the unprotected ammeter wiring. This event could result in excessive current flow (i.e., heating) in the ammeter wiring to the point of causing a secondary fire in the raceway system. The secondary fire could adversely affect safe shutdown equipment and potentially cause the loss of the ability to conduct a safe shutdown as required by 10 CFR. 50 Appendix R.
"This condition is being reported in accordance with 10 CFR 50.72(b)(3)(ii)(B). Interim compensatory measures (i.e.., fire watches) have been implemented for affected areas of the plant.
"The licensee has notified the NRC Resident Inspector."
Power Reactor
Event Number: 49487
Facility: MILLSTONE
Region: 1 State: CT
Unit: [] [2] []
RX Type: [1] GE-3,[2] CE,[3] W-4-LP
NRC Notified By: TODD PERKINS
HQ OPS Officer: PETE SNYDER
Region: 1 State: CT
Unit: [] [2] []
RX Type: [1] GE-3,[2] CE,[3] W-4-LP
NRC Notified By: TODD PERKINS
HQ OPS Officer: PETE SNYDER
Notification Date: 10/30/2013
Notification Time: 16:44 [ET]
Event Date: 10/30/2013
Event Time: 15:25 [EDT]
Last Update Date: 10/30/2013
Notification Time: 16:44 [ET]
Event Date: 10/30/2013
Event Time: 15:25 [EDT]
Last Update Date: 10/30/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
PAUL KROHN (R1DO)
PAUL KROHN (R1DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
POSTULATED HOT SHORT FIRE EVENT THAT COULD ADVERSLY IMPACT SAFE SHUTDOWN EQUIPMENT
"A review of industry operating experience regarding the impact of unfused Direct Current (DC) ammeter circuits in the control room has determined the described condition to be applicable to Millstone Power Station Unit 2 resulting in an unanalyzed condition with respect to 10 CFR 50 Appendix R analysis requirements. The original plant wiring design and associated analysis for the Class 1E batteries control room ampere indications do not include overcurrent protection features to limit the fault current.
"In the postulated event, a fire in the control room could cause one of the ammeter wires to short to the ground plane. Simultaneously, it is postulated that the fire causes another DC wire from the opposite polarity on the same battery to also short to the ground plane. This could cause a ground loop through the unprotected ammeter wiring. This event could result in excessive current flow (i.e., heating) in the ammeter wiring to the point of causing a secondary fire in the raceway system. The secondary fire could adversely affect safe shutdown equipment and potentially cause the loss of the ability to conduct a safe shutdown as required by 10 CFR 50 Appendix R.
"Interim compensatory measures (i.e., fire watches) have been implemented for affected areas of the plant.
"This condition is being reported pursuant to 10 CFR 50.72(b)(3)(ii)(B)."
The licensee notified the NRC Resident Inspector.
"A review of industry operating experience regarding the impact of unfused Direct Current (DC) ammeter circuits in the control room has determined the described condition to be applicable to Millstone Power Station Unit 2 resulting in an unanalyzed condition with respect to 10 CFR 50 Appendix R analysis requirements. The original plant wiring design and associated analysis for the Class 1E batteries control room ampere indications do not include overcurrent protection features to limit the fault current.
"In the postulated event, a fire in the control room could cause one of the ammeter wires to short to the ground plane. Simultaneously, it is postulated that the fire causes another DC wire from the opposite polarity on the same battery to also short to the ground plane. This could cause a ground loop through the unprotected ammeter wiring. This event could result in excessive current flow (i.e., heating) in the ammeter wiring to the point of causing a secondary fire in the raceway system. The secondary fire could adversely affect safe shutdown equipment and potentially cause the loss of the ability to conduct a safe shutdown as required by 10 CFR 50 Appendix R.
"Interim compensatory measures (i.e., fire watches) have been implemented for affected areas of the plant.
"This condition is being reported pursuant to 10 CFR 50.72(b)(3)(ii)(B)."
The licensee notified the NRC Resident Inspector.