Skip to main content

Event Notification Report for June 01, 2013

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
05/31/2013 - 06/01/2013

EVENT NUMBERS
49086

Power Reactor
Event Number: 49086
Facility: CRYSTAL RIVER
Region: 2     State: FL
Unit: [3] [] []
RX Type: [3] B&W-L-LP
NRC Notified By: WILLIAM KISNER
HQ OPS Officer: DONG HWA PARK
Notification Date: 06/02/2013
Notification Time: 04:38 [ET]
Event Date: 06/01/2013
Event Time: 21:29 [EDT]
Last Update Date: 06/02/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
BRIAN BONSER (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 N N 0 Defueled 0 Defueled
Event Text
VALID ACTUATION OF EMERGENCY DIESEL GENERATOR

"On June 1, 2013 at 2129 [EDT], a valid actuation of the 'B' Emergency Diesel Generator occurred when power was lost to the 'B' 4160V engineered safeguards bus due to failure of the 'B' Unit 6900 V bus feeder breaker 3104. There were no interruptions of spent fuel pool cooling during this event.

"This event is reportable as an 8-hour notification per 10 CFR 50.72(b)(3)(iv)(B)(8).