Event Notification Report for April 20, 2013
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
04/19/2013 - 04/20/2013
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 48949
Facility: SALEM
Region: 1 State: NJ
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: HARRY WIEDMAN
HQ OPS Officer: PETE SNYDER
Region: 1 State: NJ
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: HARRY WIEDMAN
HQ OPS Officer: PETE SNYDER
Notification Date: 04/20/2013
Notification Time: 09:46 [ET]
Event Date: 04/20/2013
Event Time: 04:22 [EDT]
Last Update Date: 06/13/2013
Notification Time: 09:46 [ET]
Event Date: 04/20/2013
Event Time: 04:22 [EDT]
Last Update Date: 06/13/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
WILLIAM COOK (R1DO)
WILLIAM COOK (R1DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
ACCIDENT MITIGATION - COMMON CONTROL ROOM EMERGENCY AIR CONDITIONING SYSTEM
"Salem Unit 2 was placed in a configuration that affected the ability to mitigate the consequences of an accident due to an inadvertent actuation of the common control room emergency air conditioning system (CREACS). CREACS was actuated as a result of an invalid Control Room air intake duct radiation monitor signal initiated on April 20, 2013 at 0422 hours [EDT].
"Salem Unit 1 is currently in Mode 6 with core offload in progress. Salem Unit 2 is in Mode 1 at 100% power. Unit 2 has two shutdown LCOs in effect. The first is for the CREACS, which is shared between Unit 1 & 2, being aligned for single train operation with the Unit 1 CREACS train out of service per LCO 3.7.6. The second shutdown LCO is for single source of offsite power due to scheduled maintenance.
"With Unit 1 having an invalid radiation monitor signal, the CREACS automatically aligned to accident pressurized mode. This mode of actuation starts the CREACS fans, isolates the Control Room Envelope from the normal control room ventilation system and aligns the two sets of CREACS outside air intake dampers. With a Unit 1 radiation monitor signal the Unit 1 CREACS intake dampers close and the Unit 2 CREACS intake dampers open. These damper positions are locked in until manually reset. With only one train of CREACS operable, the dose analysis indicates that the requirements of General Design Criteria (GDC) 19 can only be met during the worst case design basis accident if the Unit 2 CREACS intake dampers are closed and the Unit 1 CREACS intake dampers [are] open. Therefore, until the CREACS intake dampers were reset and realigned, Salem Unit 2 would not have been able to mitigate the consequences of an accident and is reportable in accordance with 10CFR50.72(b)(3)(v).
"The CREACS system actuation was reset after the failed radiation monitor (2R1B ch. II) was removed from service and the dampers were realigned to their pre-actuation alignment at 0457 hours, restoring Salem Unit 2 to within the assumptions of the dose analysis. Total duration in the condition was 35 minutes.
"The only pieces of major equipment out of service on Salem Unit 2 are the 4 Station Power Transformer and 23 Station Power Transformer which are out of service for scheduled maintenance."
The licensee will notifying Lower Alloways Creek township and the NRC Resident Inspector.
* * * RETRACTION FROM DAVID LAFLEUR TO PETE SNYDER AT 1304 EDT ON 6/13/13 * * *
"On April 20, 2013, Salem Unit 2 was placed in a configuration that was contrary to the current dose analysis of record due to an invalid actuation of the common Control Room Emergency Air Conditioning System (CREACS). The CREACS was initiated as a result of an invalid actuation of Control Room Air Intake Duct Radiation Monitoring Channel, 2R1B Channel 2. At the time of the actuation, the Unit 1 Train of CREACS was out of service due to scheduled maintenance leaving only the Unit 2 CREACS train operable. Unit 2 was at 100% power and Unit 1 was in Mode 6. With one train of CREACS out of service at the start of an accident the dose analysis of record requires that the CREACS Emergency Air Intake Dampers for the accident unit go closed and the opposite unit's emergency intake dampers go open. The actuation of the radiation monitoring channel 2R1B Channel 2 caused the Unit 2 Emergency Air Intake Dampers to open. If a design basis LOCA were to have occurred on Unit 2 during that period the alignment would have been contrary to the dose analysis-of-record.
"Subsequent to this event, an evaluation was performed utilizing the assumptions of the dose analysis of record with two exceptions. Actual measured Engineered Safety Feature system leakage outside containment and Containment Leakage at the time of the event were utilized in the evaluation. This evaluation determined that if a design basis LOCA had occurred on Unit 2 with the CREACS in accident pressurized mode with Unit 1 Emergency Intake Dampers closed and Unit 2 Emergency Intake Dampers opened, Control Room design dose limits would not have been exceeded. Based upon this evaluation, the CREACS system would have been able to maintain dose to Control Room operators below the limits of GDC-19 and the dose analysis of record. Since the CREACS was capable of performing its accident mitigation function, this event is being retracted."
The licensee will notify the NRC Resident Inspector. Notified R1DO (Dentel).
"Salem Unit 2 was placed in a configuration that affected the ability to mitigate the consequences of an accident due to an inadvertent actuation of the common control room emergency air conditioning system (CREACS). CREACS was actuated as a result of an invalid Control Room air intake duct radiation monitor signal initiated on April 20, 2013 at 0422 hours [EDT].
"Salem Unit 1 is currently in Mode 6 with core offload in progress. Salem Unit 2 is in Mode 1 at 100% power. Unit 2 has two shutdown LCOs in effect. The first is for the CREACS, which is shared between Unit 1 & 2, being aligned for single train operation with the Unit 1 CREACS train out of service per LCO 3.7.6. The second shutdown LCO is for single source of offsite power due to scheduled maintenance.
"With Unit 1 having an invalid radiation monitor signal, the CREACS automatically aligned to accident pressurized mode. This mode of actuation starts the CREACS fans, isolates the Control Room Envelope from the normal control room ventilation system and aligns the two sets of CREACS outside air intake dampers. With a Unit 1 radiation monitor signal the Unit 1 CREACS intake dampers close and the Unit 2 CREACS intake dampers open. These damper positions are locked in until manually reset. With only one train of CREACS operable, the dose analysis indicates that the requirements of General Design Criteria (GDC) 19 can only be met during the worst case design basis accident if the Unit 2 CREACS intake dampers are closed and the Unit 1 CREACS intake dampers [are] open. Therefore, until the CREACS intake dampers were reset and realigned, Salem Unit 2 would not have been able to mitigate the consequences of an accident and is reportable in accordance with 10CFR50.72(b)(3)(v).
"The CREACS system actuation was reset after the failed radiation monitor (2R1B ch. II) was removed from service and the dampers were realigned to their pre-actuation alignment at 0457 hours, restoring Salem Unit 2 to within the assumptions of the dose analysis. Total duration in the condition was 35 minutes.
"The only pieces of major equipment out of service on Salem Unit 2 are the 4 Station Power Transformer and 23 Station Power Transformer which are out of service for scheduled maintenance."
The licensee will notifying Lower Alloways Creek township and the NRC Resident Inspector.
* * * RETRACTION FROM DAVID LAFLEUR TO PETE SNYDER AT 1304 EDT ON 6/13/13 * * *
"On April 20, 2013, Salem Unit 2 was placed in a configuration that was contrary to the current dose analysis of record due to an invalid actuation of the common Control Room Emergency Air Conditioning System (CREACS). The CREACS was initiated as a result of an invalid actuation of Control Room Air Intake Duct Radiation Monitoring Channel, 2R1B Channel 2. At the time of the actuation, the Unit 1 Train of CREACS was out of service due to scheduled maintenance leaving only the Unit 2 CREACS train operable. Unit 2 was at 100% power and Unit 1 was in Mode 6. With one train of CREACS out of service at the start of an accident the dose analysis of record requires that the CREACS Emergency Air Intake Dampers for the accident unit go closed and the opposite unit's emergency intake dampers go open. The actuation of the radiation monitoring channel 2R1B Channel 2 caused the Unit 2 Emergency Air Intake Dampers to open. If a design basis LOCA were to have occurred on Unit 2 during that period the alignment would have been contrary to the dose analysis-of-record.
"Subsequent to this event, an evaluation was performed utilizing the assumptions of the dose analysis of record with two exceptions. Actual measured Engineered Safety Feature system leakage outside containment and Containment Leakage at the time of the event were utilized in the evaluation. This evaluation determined that if a design basis LOCA had occurred on Unit 2 with the CREACS in accident pressurized mode with Unit 1 Emergency Intake Dampers closed and Unit 2 Emergency Intake Dampers opened, Control Room design dose limits would not have been exceeded. Based upon this evaluation, the CREACS system would have been able to maintain dose to Control Room operators below the limits of GDC-19 and the dose analysis of record. Since the CREACS was capable of performing its accident mitigation function, this event is being retracted."
The licensee will notify the NRC Resident Inspector. Notified R1DO (Dentel).
Agreement State
Event Number: 48954
Rep Org: WA DIVISION OF RADIATION PROTECTION
Licensee: MISTRAS GROUP, INC
Region: 4
City: KENT State: WA
County:
License #: WN-IR011-1
Agreement: Y
Docket:
NRC Notified By: JAMES KILLINGBECK
HQ OPS Officer: CHARLES TEAL
Licensee: MISTRAS GROUP, INC
Region: 4
City: KENT State: WA
County:
License #: WN-IR011-1
Agreement: Y
Docket:
NRC Notified By: JAMES KILLINGBECK
HQ OPS Officer: CHARLES TEAL
Notification Date: 04/22/2013
Notification Time: 19:18 [ET]
Event Date: 04/20/2013
Event Time: 00:00 [PDT]
Last Update Date: 04/29/2013
Notification Time: 19:18 [ET]
Event Date: 04/20/2013
Event Time: 00:00 [PDT]
Last Update Date: 04/29/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
10 CFR Section:
Person (Organization):
JACK WHITTEN (R4DO)
FSME EVENT RESOURCE (EMAI)
JACK WHITTEN (R4DO)
FSME EVENT RESOURCE (EMAI)
AGREEMENT STATE REPORT - RADIOGRAPHY SOURCE STUCK IN GUIDE TUBE
The following was received from the State of Washington via email:
"Mistras Group, Inc. was conducting industrial radiographic operations at Shell Puget Sound Refinery. After a routine exposure, the radiographer attempted to crank the source back into the camera, but the source became stuck. The source could not make it past a crimp in the guide tube, which was caused earlier when the camera fell on it. The radiography crew moved their restricted area boundaries to increase the size of the restricted area and to provide additional protection to anyone in the area. Fortunately, nobody other than the radiography crew were in that portion of the refinery. The radiography crew and assistant radiation safety officer were able to manually pull the source back into the shielded position in the camera. The highest exposure to any person, as read from a pocket dosimeter, was 10 millirem. Note: This is a preliminary report - we [State of Washington] will obtain additional information from the licensee and provide a more complete report in the near future."
Washington Item Number: WA130001
* * * UPDATE ON 4/29/2013 AT 1931 EDT FROM JAMES KILLINGBECK TO MARK ABRAMOVITZ * * *
The following information was received via fax:
"An industrial radiography crew retracted the source, checked to verify that the source was fully retracted and locked, and discovered that it was not. The crew made more attempts to retract the source, but were unsuccessful. They attempted to straighten out the crank assembly, then the radiographic exposure device fell about 46 inches from a pipe onto a platform, after which the drive cable would not move using the crank handle. The restricted area was expanded to the 2 mR/hr line and facility management and the licensee's radiation safety personnel were notified and traveled to the site. The guide tube was moved onto the platform and lead shot bags were placed onto the collimator to provide extra shielding. Licensee radiation safety staff found that the drive cable was hung up in the crank assembly conduit but moved freely in the source tube. So, the staff manually pulled on the drive cable and returned the source to the fully retracted and locked position in the radiographic exposure device. It was discovered that there was a crimp in the crank assembly conduit that kept the drive cable from moving. The highest pocket dosimeter reading was 18 millirem. The radiographic exposure device was sent to the manufacturer for evaluation."
Notified the R4DO (Haire) and FSME Event Resources (via e-mail).
The following was received from the State of Washington via email:
"Mistras Group, Inc. was conducting industrial radiographic operations at Shell Puget Sound Refinery. After a routine exposure, the radiographer attempted to crank the source back into the camera, but the source became stuck. The source could not make it past a crimp in the guide tube, which was caused earlier when the camera fell on it. The radiography crew moved their restricted area boundaries to increase the size of the restricted area and to provide additional protection to anyone in the area. Fortunately, nobody other than the radiography crew were in that portion of the refinery. The radiography crew and assistant radiation safety officer were able to manually pull the source back into the shielded position in the camera. The highest exposure to any person, as read from a pocket dosimeter, was 10 millirem. Note: This is a preliminary report - we [State of Washington] will obtain additional information from the licensee and provide a more complete report in the near future."
Washington Item Number: WA130001
* * * UPDATE ON 4/29/2013 AT 1931 EDT FROM JAMES KILLINGBECK TO MARK ABRAMOVITZ * * *
The following information was received via fax:
"An industrial radiography crew retracted the source, checked to verify that the source was fully retracted and locked, and discovered that it was not. The crew made more attempts to retract the source, but were unsuccessful. They attempted to straighten out the crank assembly, then the radiographic exposure device fell about 46 inches from a pipe onto a platform, after which the drive cable would not move using the crank handle. The restricted area was expanded to the 2 mR/hr line and facility management and the licensee's radiation safety personnel were notified and traveled to the site. The guide tube was moved onto the platform and lead shot bags were placed onto the collimator to provide extra shielding. Licensee radiation safety staff found that the drive cable was hung up in the crank assembly conduit but moved freely in the source tube. So, the staff manually pulled on the drive cable and returned the source to the fully retracted and locked position in the radiographic exposure device. It was discovered that there was a crimp in the crank assembly conduit that kept the drive cable from moving. The highest pocket dosimeter reading was 18 millirem. The radiographic exposure device was sent to the manufacturer for evaluation."
Notified the R4DO (Haire) and FSME Event Resources (via e-mail).