Skip to main content

Event Notification Report for February 07, 2013

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
02/06/2013 - 02/07/2013

EVENT NUMBERS
48729487304873148732

Agreement State
Event Number: 48729
Rep Org: TEXAS DEPARTMENT OF HEALTH
Licensee: EQUISTAR CHEMICALS L.P.
Region: 4
City: PASADENA   State: TX
County:
License #:
Agreement: Y
Docket:
NRC Notified By: ART TUCKER
HQ OPS Officer: BILL HUFFMAN
Notification Date: 02/07/2013
Notification Time: 15:13 [ET]
Event Date: 02/07/2013
Event Time: 00:00 [CST]
Last Update Date: 02/07/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
DON ALLEN (R4DO)
FSME EVENTS RESOURCE (E-MA)
Event Text
AGREEMENT STATE REPORT - PROCESS GAUGE SHUTTER STUCK OPEN

The following report was received from State of Texas Radiation Branch via e-mail:

"On February 7, 2013, the Agency [State of Texas Radiation Branch] was notified by the licensee that the shutter on an Ohmart model SH-F1A nuclear gauge was stuck in the open position. The gauge contains a 50 millicurie cesium - 137 source. Open is the normal operating position for this gauge. The licensee has notified their personnel that no entry into the vessel the gauge is mounted on is allowed until the gauge is repaired. The manufacturer has been contacted and arrangements to repair the gauge are being completed. The failure does not create an exposure risk to any individual. This gauge had previously failed in February of 2012 (EN47691). Additional information will be provided as it is received in accordance with SA - 300."

Texas Report: I-9039.


Power Reactor
Event Number: 48730
Facility: FORT CALHOUN
Region: 4     State: NE
Unit: [1] [] []
RX Type: (1) CE
NRC Notified By: TIM SCHULTE
HQ OPS Officer: BILL HUFFMAN
Notification Date: 02/07/2013
Notification Time: 18:21 [ET]
Event Date: 02/07/2013
Event Time: 14:30 [CST]
Last Update Date: 02/07/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
DON ALLEN (R4DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Cold Shutdown 0 Cold Shutdown
Event Text
UNANALYZED CONDITION DUE TO POSSIBLE RUN-OUT OF HIGH PRESSURE SAFETY INJECTION PUMP

"Current design basis calculations indicate the high pressure safety injection (HPSI) pumps could potentially operate in a run-out condition under certain worst case design basis conditions. The calculated flow is beyond the pump curves. The HPSI pumps could operate in a run-out condition for an extended period following a design basis accident. The pump vendor indicates that long term operation in this condition could not be supported due to accelerated wear of pump internal components. This represents a reportable unanalyzed condition."

The NRC Resident Inspector has been notified.


Power Reactor
Event Number: 48731
Facility: COOK
Region: 3     State: MI
Unit: [1] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: GREG KANDA
HQ OPS Officer: BILL HUFFMAN
Notification Date: 02/07/2013
Notification Time: 18:37 [ET]
Event Date: 02/07/2013
Event Time: 17:35 [EST]
Last Update Date: 02/07/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
MICHAEL KUNOWSKI (R3DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
OFFSITE NOTIFICATION RELATED TO DEATH OF CONTRACTOR ONSITE

"At 1620 EST on 2/7/2013 an emergency medical report was received in Unit 1 Control Room that an individual was reported to have collapsed and was lying unconscious outside of the protected area. Fire protection and Emergency Medical personnel were dispatched to the scene. The individual was unresponsive, without a pulse and not breathing. Off-site medical assistance was immediately requested. CPR was commenced and continued until transfer of the individual to off-site medical ambulance service Medic 1. An Automatic External Defibrillator (AED) was used once, as allowed by the AED.

"Confirmation of the fatality was received at 1735 EST on 2/7/2013. The individual was pronounced dead at 1712 EST on 2/7/2013.

"Both Units remain at 100% power. This Event notification is being made due to the onsite fatality.

"The NRC Resident Inspector has been notified."


Power Reactor
Event Number: 48732
Facility: RIVER BEND
Region: 4     State: LA
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: JEFF REYNOLDS
HQ OPS Officer: BILL HUFFMAN
Notification Date: 02/07/2013
Notification Time: 19:34 [ET]
Event Date: 02/07/2013
Event Time: 15:53 [CST]
Last Update Date: 02/07/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
DON ALLEN (R4DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
INADVERTENT EMERGENCY SIREN ACTUATION

"At 1553 CST on 02/07/2013, River Bend Station emergency preparedness personnel were notified by a dispatcher at the Pointe Coupee Parish Sheriff's Office that several calls had been received regarding one or more River Bend emergency sirens sounding in the vicinity of the city of New Roads, Louisiana. The siren(s) sounded at least twice. Emergency Preparedness personnel notified the caller that no emergency condition existed at the station and made other notifications in accordance with River Bend procedure EPP-2-401 for inadvertent siren sounding. Notifications included the governors office of homeland security to notify the public that the sounding is inadvertent and that no emergency exists at the station. Additionally, the Emergency Alert System local station (WJBO/WFMF) was directly notified to broadcast the notification. The cause of the siren sounding is currently being investigated.

"The Senior Resident NRC Inspector has also been notified."