Skip to main content

Event Notification Report for February 03, 2013

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
02/02/2013 - 02/03/2013

EVENT NUMBERS
4871148712

Power Reactor
Event Number: 48711
Facility: PRAIRIE ISLAND
Region: 3     State: MN
Unit: [] [2] []
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: STEPHEN SEILHYMER
HQ OPS Officer: DONALD NORWOOD
Notification Date: 02/03/2013
Notification Time: 13:20 [ET]
Event Date: 02/03/2013
Event Time: 12:08 [CST]
Last Update Date: 02/03/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
ANN MARIE STONE (R3DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
OFFSITE NOTIFICATION DUE TO RELEASE OF AMERTAP BALLS

"At 1208 CST, Xcel Energy notified the Minnesota State Duty Officer that up to 950 Amertap Balls had been lost from the Prairie Island Nuclear Generating Plant Unit 2 Condenser Tube Cleaning System. Since the Minnesota State Duty Officer for the Division of Emergency Management was notified, this constitutes a 4 hour non-emergency notification per 10CFR50.72(b)(2)(xi)."

The licensee notified the NRC Resident Inspector. The licensee also notified the local county sheriff's office.


Power Reactor
Event Number: 48712
Facility: PILGRIM
Region: 1     State: MA
Unit: [1] [] []
RX Type: [1] GE-3
NRC Notified By: JOE BRACKEN
HQ OPS Officer: JOHN SHOEMAKER
Notification Date: 02/03/2013
Notification Time: 19:40 [ET]
Event Date: 02/03/2013
Event Time: 12:45 [EST]
Last Update Date: 02/03/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
RONALD BELLAMY (R1DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 80 Power Operation
Event Text
INFORMATIONAL NOTIFICATION - SAFETY RELIEF VALVE POTENTIALLY INOPERABLE

"On February 3, 2013 at 1245 EST, with the reactor at 100% core thermal power (CTP) safety relief valve, RV-203-3B was declared inoperable as required by station procedural direction due to an observed reduction in first stage pilot valve temperature of greater than 35 degrees F from baseline temperatures. At 1300 EST, reactor power was lowered to approximately 80% CTP at which time the relief valve parameters returned or trended to normal steady state values. Consistent with a reactor power reduction, reactor pressure also lowered from 1035 psig to 1000 psig. This action was taken consistent with industry operating experience related to three stage target rock relief first stage pilot valve leakage.

"Currently, station engineering is evaluating the operability of RV-203-3B. Additionally, the current valve performance is being closely monitored by the main control room operating crew.

"Station Technical Specification 3.6.D.1 requires that the safety modes of all relief valves (four for [Pilgrim Nuclear Power Station] PNPS) shall be operable during reactor power operating conditions and prior to reactor startup from a Cold Shutdown, or whenever reactor coolant pressure is greater that 104 psig and temperature is greater than 340 degrees F. If this specification is not met, Technical Specification 3.6.D.2 requires that an orderly shutdown shall be initiated and the reactor coolant pressure shall be below 104 psig within 24 hours.

"This is an informational notification at this time. PNPS has not initiated an orderly shutdown as of this notification; rather reactor power was lowered to reseat the safety relief pilot valve and there is a high degree of confidence that the high standard of operability will be restored for RV-203-3B and the associated Technical Specification will be exited. If RV-203-3B is not restored to an operable status, a formal and required notification will be completed in accordance with 10 CFR 50.72(b)(2)(i), 'Initiation of any plant shutdown required by the Technical Specifications.'

"This event has no impact on the health and safety of the public.

"The USNRC Senior Resident Inspector has been informed [by the Licensee]."