Skip to main content

Event Notification Report for January 24, 2013

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/23/2013 - 01/24/2013

EVENT NUMBERS
4869848701

Independent Spent Fuel Storage Installation
Event Number: 48698
Rep Org: PEACH BOTTOM
Licensee: EXELON GENERATION COMPANY, LLC
Region: 1
City: PHILADELPHIA   State: PA
County: YORK & LANCASTER
License #: GL
Agreement: Y
Docket: 72-29
NRC Notified By: BARRY LEVINS
HQ OPS Officer: STEVE SANDIN
Notification Date: 01/25/2013
Notification Time: 09:43 [ET]
Event Date: 01/24/2013
Event Time: 11:00 [EST]
Last Update Date: 01/25/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
MARC FERDAS (R1DO)
ERIC THOMAS (NRR)
Event Text
NON-COMPLIANCE WITH STORAGE CASK TECHNICAL SPECIFICATION LIMITS

"This report is being submitted pursuant to Transnuclear (TN)-68 Technical Specification (TS) Section 2.2, which requires reporting of non-compliances with the Functional and Operational limits of TS Section 2.1.1.

"A recent review of historical ISFSI [Independent Spent Fuel Storage Installation] fuel characterization data found that in the ISFSI 2001 campaign, a total of four Unit 3 fuel assemblies were loaded into four dry cask storage casks (i.e., one assembly per cask) having been cooled for 9.8 years, with a decay heat value of 0.201 kW each, which is well below the 0.312 kW limit (TN-68 TS 2.1.1.). Therefore, it is not expected that there were any actual thermal related concerns with the fuel or the associated cask components. However, this was contrary to the Functional and Operational limits of TS Section 2.1.1 , Table 2.1.1-1, which requires the assemblies to have been cooled for 10 years. The decay heat of the assemblies has continued to decrease since their initial loading in 2001 and all assemblies currently meet the TS 2.2.1 limits. The fuel assemblies are in a safe condition as required by TS 2.2.1.

"These casks were loaded under TN-68 Certificate of Compliance (C of C) Amendment 0 (Certificate 1027). This notification is required pursuant to TN-68 TS Section 2.2.2. This issue has been entered into the Corrective Action Program.

"The NRC Resident Inspector has been informed."


Power Reactor
Event Number: 48701
Facility: INDIAN POINT
Region: 1     State: NY
Unit: [] [3] []
RX Type: [2] W-4-LP,[3] W-4-LP
NRC Notified By: JOHN DIGNAM
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 01/25/2013
Notification Time: 12:38 [ET]
Event Date: 01/24/2013
Event Time: 23:38 [EST]
Last Update Date: 02/06/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
30.50(b)(2) - SAFETY EQUIPMENT FAILURE
Person (Organization):
MARC FERDAS (R1DO)
FSME RESOURCE
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 N Y 100 Power Operation 100 Power Operation
Event Text
RADIAC CALIBRATION SOURCE WINDOW INTERLOCK FAILURE

"At 23:38 hours on January 24, 2013, while performing daily source checks on portable radiation meters, the Shepherd Model 78-2 Calibrator (Serial # 9047) failed a pre-operational source interlock check. The 130 mCi /130 Ci Cs-137 sources were able to be raised while the shield door was not fully shut.

"This is reportable under 10 CFR 70.50(b)(2) since the interlock is required by license to prevent the accidental raising of the source with the door open. There is no equipment considered to be redundant to the interlock. The cause of the failure has not been determined at this time.

"No personnel were exposed to the sources. Sources were returned to the shielded position, the calibrator was locked and removed from service. A survey of the calibrator after securing the sources showed dose rates within expected ranges. The affected calibrator is not part of any installed plant equipment and has no impact on plant operation."

The licensee notified the NRC Resident Inspector.

* * * UPDATE FROM STEVE PRUSSMAN TO CHARLES TEAL ON 2/6/13 AT 1105 EST * * *

The licensee has changed the reporting criteria to 10 CFR 30.50(b)(2). The NRC Resident Inspector has been informed.

Notified R1DO (Powell).