Event Notification Report for December 15, 2012

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
12/14/2012 - 12/15/2012

EVENT NUMBERS
48597

Power Reactor
Event Number: 48597
Facility: HARRIS
Region: 2     State: NC
Unit: [1] [] []
RX Type: [1] W-3-LP
NRC Notified By: ADAM HELSEL
HQ OPS Officer: BILL HUFFMAN
Notification Date: 12/15/2012
Notification Time: 10:18 [ET]
Event Date: 12/15/2012
Event Time: 07:34 [EST]
Last Update Date: 12/15/2012
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
ALAN BLAMEY (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
TECHNICAL SUPPORT CENTER COOLING FAN INOPERABLE

"This event is reportable per 10 CFR 50.72(b)(3)(xiii) as described in NUREG-1022, Rev. 2 based on 'Loss of Response' capability.

"This is a non-emergency notification. At approximately 0734 EST on 12/15/2012 AH-17, the Technical Support Center (TSC) Cooling Fan was found exhibiting no flow. The cause of the no flow condition was a broken fan belt. Repairs are being planned and will be worked immediately.

"TSC functionality requires all areas of the TSC be maintained between 50 degrees F and 86 degrees F. The actual TSC area temperatures range from 59 degrees F to 67 degrees F.

"Should the TSC need to be activated for an event, . . . compensatory measures are in place to consider relocating the TSC to the Alternate Emergency Facility per PEP-240. This decision would he based on the existing event conditions and coordinated with the Emergency Response Manager, SEC-MCR, and Radiological Control Manager."

The licensee has notified the NRC Resident Inspector.