Skip to main content

Event Notification Report for August 07, 2012

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
08/06/2012 - 08/07/2012

EVENT NUMBERS
481784816548166

Power Reactor
Event Number: 48178
Facility: SUSQUEHANNA
Region: 1     State: PA
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: RON FRY
HQ OPS Officer: JOHN KNOKE
Notification Date: 08/10/2012
Notification Time: 17:13 [ET]
Event Date: 08/07/2012
Event Time: 17:34 [EDT]
Last Update Date: 08/10/2012
Emergency Class: NON EMERGENCY
10 CFR Section:
20.1906(d)(1) - SURFACE CONTAM LEVELS > LIMITS
Person (Organization):
ART BURRITT (R1DO)
FSME RESOURCE (EMAI)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
DRY FUEL STORAGE TRANSFER TRAILER DETECTED WITH REMOVABLE CONTAMINATION

"On Aug 7, 2012 at 1734 EDT, PPL Susquehanna personnel were in the process of releasing the Dry Fuel Storage Transfer Trailer from the Unit 1 Reactor Building 101 rail bay and detected removable contamination on the trailer.

"PPL Susquehanna Health Physics personnel identified removable surface contamination up to 30,000 dpm/100 sq cm on the transfer trailer. Gamma spectroscopy performed on smears identified the presence of Cs-137. No other radionuclides were identified on any of the analyzed smears. Cs-137, by itself, is not a nuclide characteristic to Susquehanna due to Susquehanna's high fuel integrity performance. In addition, no loose surface alpha contamination was identified.

"The area around the trailer, located in the 101 bay, has been posted and controlled as a contaminated area. Decontamination of the transfer trailer is in progress. Onsite surveys of areas that were occupied by the transfer trailer, indicate no removable surface contamination. In addition, no Susquehanna personnel contamination events have been attributed to the contamination found on the transfer trailer.

"Although the receipt of this transfer trailer was not identified as an incoming radioactive shipment to Susquehanna from its' supplier, this event is immediately reportable to the NRC Operations Center in accordance with 10 CFR 20.1906(d), since the Department of Transportation acceptance limits identified in 49 CFR 173.433 for this type of container are 22,000 DPM/100 sq. cm and PPL Health Physics personnel identified removable radioactive surface contamination in excess of the limits of 10 CFR 71.87(i) which refer to the DOT limits of 49 CFR 173.433.

"The final delivery carrier and NRC Senior Resident Inspector have been notified." The licensee will be notifying the Commonwealth of Pennsylvania.


Agreement State
Event Number: 48165
Rep Org: TEXAS DEPARTMENT OF HEALTH
Licensee: WESTLAKE LONGVIEW NOTIFICATION
Region: 4
City: LONGVIEW   State: TX
County:
License #: 06294
Agreement: Y
Docket:
NRC Notified By: KAREN BLANCHARD
HQ OPS Officer: PETE SNYDER
Notification Date: 08/07/2012
Notification Time: 11:30 [ET]
Event Date: 08/07/2012
Event Time: 00:00 [CDT]
Last Update Date: 08/07/2012
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
MICHAEL VASQUEZ (R4DO)
FSME EVENT RESOURCE (EMAI)
Event Text
AGREEMENT STATE REPORT - FIXED GAUGE SHUTTER STUCK OPEN

Texas provided the following information via email:

"On August 7, 2012, the licensee notified the Agency that on August 6, 2012, the shutter on a Ronan Model SA-1 fixed nuclear gauge, containing 100 millicuries of cesium-137, at its facility in Longview, Texas, was found to be stuck in the open position. During routine inspection and operation checks in March 2012, the licensee observed that the shutter was difficult to operate. The licensee's maintenance staff had made several unsuccessful attempts to fix the problem. On August 6th, the maintenance staff was going to make another attempt but the shutter was completed stuck and could not be freed. The shutter on this gauge is in the open position during normal operation so there was no increased risk to any individual and there have been no exposures. The licensee has contacted the manufacturer to schedule repairs, has notified employees of the gauge's status, and has implemented administrative controls to restrict access until repairs are completed. More information will be provided as it is obtained, per SA-300.

"Source/Source Holder information:
"Model: Ronan SA-1
"Cesium-137 -- 100 millicuries
"Serial #: JJ590"

Texas Incident #: I-8973


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Agreement State
Event Number: 48166
Rep Org: ILLINOIS EMERGENCY MGMT. AGENCY
Licensee: UNIVERSITY OF CHICAGO
Region: 3
City: CHICAGO   State: IL
County:
License #: IL-01693-01
Agreement: Y
Docket:
NRC Notified By: DAREN PERRERO
HQ OPS Officer: DONG HWA PARK
Notification Date: 08/07/2012
Notification Time: 13:31 [ET]
Event Date: 08/07/2012
Event Time: 00:00 [CDT]
Last Update Date: 08/08/2012
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
CHRISTINE LIPA (R3DO)
FSME EVENTS RESOURCE
Event Text
AGREEMENT STATE REPORT - MISSING SOURCE

"The licensee's RSO at the University of Chicago called to advise that while performing a routine inventory of sealed sources, one radioactive source was determined to be missing . A radioactive strontium source which was believed to have been constructed at the University in 1972 was examined more closely than in the past and no radiation readings were detected from it. The source had been made at the University in 1974 to contain 0.828 milliCi of Sr-90. The source was not officially added to the sealed source inventory and leak test records until the mid '90s. For the past 12 years (and perhaps longer) the source had been in storage and unused while use of a similar commercially constructed source was favored. On this occasion the source was removed from the locked storage safe and from the presence of the other stored sources and direct readings from the 3 inch bolt showed no elevated radiation levels.

"No ready explanation as to why the radioactivity which had been embedded into the bored centerline of the bolt was not present was available. The item had been transferred to a new researcher in 2000 when the original researcher had retired and had not been used since. A comprehensive review of records suggests that a similar source and quantity was disposed in the 80's however direct correspondence to provide strong assurance that the disposed material and the missing quantity were a match was not possible. Interviews were conducted with the current responsible investigator, past students and colleagues of the original user. Those interviews were inconclusive on the fate of the radioactive material. No other items or sealed sources have been identified as missing from the secure storage location or the researcher's inventory.

"Without additional information to verify the source's whereabouts, the licensee has declared the source as missing with little chance of recovery. The licensee advised that a written report will be filed in advance of the 30 day deadline. The current activity of Sr-90 involved would be 317 microCi."

Illinois Item Number: IL12013

* * * RETRACTION ON 8/8/12 AT 1518 EDT FROM DAREN PERRERO TO DONG PARK * * *

"The licensee's Radiation Safety Officer called the Agency [State of Illinois] on the morning of August 8, 2012 with additional information concerning the August 7, 2012, reported missing Sr-90 source. Based on continued reviews of purchase records, inventories and direct radiation measurements from sources present at the laboratory location, the missing source of Sr-90 has been identified as being in their possession but as a different and mislabeled source. Discrepancies noted between purchase records, inventory records and leak test records caused radiation safety staff to look closer at the existing results of the physical inventories they had performed in an attempt to locate the missing source. After conducting reference radiation measurements from a known quantity source of Sr-90 and then taking measurements from the remaining Sr-90 sources on the inventory, a source holder incorrectly identified as containing a larger activity Sr-90 source was confirmed as being the missing source. The licensee's 30 day report will detail the cause of the event, corrective action taken as well as actions taken to prevent future occurrences."

Notified R3DO (Lipa) and FSME Events Resource via email.

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf

This source is not amongst those sources or devices identified by the IAEA Code of Conduct for the Safety & Security of Radioactive Sources to be of concern from a radiological standpoint. Therefore is it being categorized as a less than Category 3 source