Skip to main content

Event Notification Report for December 15, 2010

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
12/14/2010 - 12/15/2010

EVENT NUMBERS
4648246483

Power Reactor
Event Number: 46482
Facility: POINT BEACH
Region: 3     State: WI
Unit: [] [2] []
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: DUANE HOFSTRA
HQ OPS Officer: STEVE SANDIN
Notification Date: 12/15/2010
Notification Time: 05:40 [ET]
Event Date: 12/15/2010
Event Time: 01:48 [CST]
Last Update Date: 12/15/2010
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
LAURA KOZAK (R3DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 M/R N 0 Startup 0 Hot Standby
Event Text
UNIT 2 MANUAL REACTOR TRIP DURING STARTUP

"On 12/15/10 at 0148 [CST] Control room personnel initiated a manual reactor trip in order to abort a startup in progress with the Unit 2 Reactor subcritical.

"During the performance of OP-1B, Reactor Startup for Unit 2 both Rod Control System Urgent and Non-Urgent alarms were received. Shortly after receiving the alarms multiple groups of control rods fell into the core as indicated by Individual Rod Position Indicators (IRPl's) and rod bottom lights. Based on these indications a manual reactor trip was initiated. All systems functioned as expected, with all control rods fully inserting. The plant is currently in Mode 3 and operating in accordance with normal plant procedures."

The cause of the control rod alarms is under investigation.

The licensee informed the NRC Resident Inspector.


Power Reactor
Event Number: 46483
Facility: SALEM
Region: 1     State: NJ
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: JOHN OSBORNE
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 12/15/2010
Notification Time: 16:37 [ET]
Event Date: 12/15/2010
Event Time: 13:20 [EST]
Last Update Date: 12/15/2010
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
DANIEL HOLODY (R1DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
OFFSITE NOTIFICATION OF AN AMMONIA SPILL INTO THE DELAWARE RIVER

"A notification was made to the New Jersey Department of Environmental Protection of a discharge of approximately 500 gallons of water containing ammonia with a concentration of 1 ppm. The discharge occurred due to the U-1 FHB [Fuel Handling Building] Supply Fan HW coil rupture. The solution was discharged into the storm drain outside of the FHB Annex door. That storm drain leads to a permitted outfall that communicates with the Delaware River. The leak has been isolated and the downstream catch basin plugged. The remaining water in the discharge line upstream of the plugged catch basin will be removed by a contractor.

"There was no out-of service safely related equipment that contributed to this event. No one was injured as a result of this event."

The licensee notified the NRC Resident Inspector.