Event Notification Report for August 11, 2010
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
08/10/2010 - 08/11/2010
EVENT NUMBERS
46167
Power Reactor
Event Number: 46167
Facility: OCONEE
Region: 2 State: SC
Unit: [] [] [3]
RX Type: [1] B&W-L-LP,[2] B&W-L-LP,[3] B&W-L-LP
NRC Notified By: MIKE JONES
HQ OPS Officer: VINCE KLCO
Region: 2 State: SC
Unit: [] [] [3]
RX Type: [1] B&W-L-LP,[2] B&W-L-LP,[3] B&W-L-LP
NRC Notified By: MIKE JONES
HQ OPS Officer: VINCE KLCO
Notification Date: 08/11/2010
Notification Time: 13:04 [ET]
Event Date: 08/11/2010
Event Time: 12:07 [EDT]
Last Update Date: 08/11/2010
Notification Time: 13:04 [ET]
Event Date: 08/11/2010
Event Time: 12:07 [EDT]
Last Update Date: 08/11/2010
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
Person (Organization):
BINOY DESAI (R2DO)
ROBERT NELSON (NRR)
BRUCE BOGER (NRR)
VICTOR McCREE (R2)
WILLIAM GOTT (IRD)
BINOY DESAI (R2DO)
ROBERT NELSON (NRR)
BRUCE BOGER (NRR)
VICTOR McCREE (R2)
WILLIAM GOTT (IRD)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 3 | N | Y | 100 | Power Operation | 100 | Power Operation |
UNIT 3 DECLARED AN UNUSUAL EVENT DUE TO LOSS OF ANNUNCIATORS
"While repairing a control room alarm panel, a screw was dropped. This appears to have caused a breaker (3D1B-27) to trip, which caused a loss of greater than 50% of the control room alarm panels.
"A team is being assembled to develop trouble shooting plan to restore alarm panels. Enhanced plant monitoring is being put in place until alarm panels are restored."
Approximately half of the control room annunciators are locked in and/or non-functional.
The licensee notified the NRC Resident Inspector. Notified DHS (Hill), FEMA (Heyman), DOE (Yates), HHS (Baker) and USDA (Shaffer).
* * * UPDATE FROM JOHN SAWYER TO VINCE KLCO ON 8/11/10 AT 2151 EDT* * *
At 2130 EDT, Unit 3 exited from the UNUSUAL EVENT based on returning to service greater than 50% of alarm panels. Compensatory measures are in place for the alarm panels which have no audible signal.
The licensee notified appropriate state and local agencies. The licensee also notified the NRC Resident Inspector.
Agencies that the licensee notified included South Carolina and North Carolina warning points, the South Carolina Emergency Management Agency and the Oconee and Pickens County Emergency Management Agencies.
Notified R2DO (Desai), NRR EO (Nelson), IRD Manager (Gott), DHS ( Gates), FEMA (Blankenship), DOE (Bailey), HHS(Grimes) and USDA (Timmons).
"While repairing a control room alarm panel, a screw was dropped. This appears to have caused a breaker (3D1B-27) to trip, which caused a loss of greater than 50% of the control room alarm panels.
"A team is being assembled to develop trouble shooting plan to restore alarm panels. Enhanced plant monitoring is being put in place until alarm panels are restored."
Approximately half of the control room annunciators are locked in and/or non-functional.
The licensee notified the NRC Resident Inspector. Notified DHS (Hill), FEMA (Heyman), DOE (Yates), HHS (Baker) and USDA (Shaffer).
* * * UPDATE FROM JOHN SAWYER TO VINCE KLCO ON 8/11/10 AT 2151 EDT* * *
At 2130 EDT, Unit 3 exited from the UNUSUAL EVENT based on returning to service greater than 50% of alarm panels. Compensatory measures are in place for the alarm panels which have no audible signal.
The licensee notified appropriate state and local agencies. The licensee also notified the NRC Resident Inspector.
Agencies that the licensee notified included South Carolina and North Carolina warning points, the South Carolina Emergency Management Agency and the Oconee and Pickens County Emergency Management Agencies.
Notified R2DO (Desai), NRR EO (Nelson), IRD Manager (Gott), DHS ( Gates), FEMA (Blankenship), DOE (Bailey), HHS(Grimes) and USDA (Timmons).