Event Notification Report for June 19, 2010

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
06/18/2010 - 06/19/2010

EVENT NUMBERS
46032

Power Reactor
Event Number: 46032
Facility: POINT BEACH
Region: 3     State: WI
Unit: [] [2] []
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: KILE HESS
HQ OPS Officer: JOE O'HARA
Notification Date: 06/19/2010
Notification Time: 11:25 [ET]
Event Date: 06/19/2010
Event Time: 06:36 [CDT]
Last Update Date: 06/19/2010
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
MICHAEL KUNOWSKI (R3DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 M/R Y 0 Startup 0 Hot Standby
Event Text
MANUAL REACTOR TRIP DUE TO GENERATOR LOCKOUT

"At 0636 hours, control room personnel initiated a manual reactor trip of Unit 2 from MODE 2 at 0% power. Just prior to the initiation of the manual reactor trip, an automatic turbine trip had occurred as a result of the receipt of a generator lockout signal. Prior to the automatic turbine trip, an orderly power reduction to 44% power had been completed and the unit was being maintained in a stable condition in MODE 1. At the time of the turbine trip, two sets of condenser steam dump valves were isolated, in preparation for scheduled condenser waterbox tube cleaning. Following the manual reactor trip, all safety systems and equipment operated as expected. The cause of the turbine trip, including receipt of the generator lockout signal, is under investigation. The unit is stable in MODE 3 at normal RCS temperature and pressure.

"This event is being reported in accordance with 10 CFR 50.72(b)(2)(iv)(B) t and 10 CFR 50.72(b)(3)(iv)(A). The NRC Senior Resident Inspector has been notified."

Just prior to the trip, the unit was critical in Mode 2. All rods are fully inserted into the core.